Plan Review Details - Permit 07020761
Plan Review Stops For Permit 07020761
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-03-07 Cont ID  
Sent By mperson Date 2007-03-07 Time 15:18 Rev Time 0.45
Received By mperson Date 2007-03-07 Time 15:18 Sent To PC
Notes
2007-03-07 15:35:11****************PROVISO****************
 A) FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING, ELECTRICAL,
 MECHANICAL, AND GAS APPROVAL OF GENERATOR PLACEMENT.
  
 B) FBC-2004 FUEL GAS SEC. 404.12 OUTLETCLOSURES: GAS
 OUTLETS THAT DO NOT CONNECT TO APPLIANCES SHALL BE
 CAPPED GAS TIGHT.
  
 C) NOTE: MINIMUM SIZE EXISTING 2 PSI GAS PIPING SIZE
 IS 1/2" FOR SCH 40, PE, AND CSST.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-07 Cont ID  
Sent By mperson Date 2007-03-07 Time 15:36 Rev Time 0.00
Received By mperson Date 2007-03-01 Time 14:33 Sent To  
Notes
2007-03-01 14:33:17TO "G" BOX