Plan Review Stops For Permit 07020761 |
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2007-03-07 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-03-07 |
Time |
15:18 |
Rev Time |
0.45 |
Received By |
mperson |
Date |
2007-03-07 |
Time |
15:18 |
Sent To |
PC |
|
Notes |
2007-03-07 15:35:11 | ****************PROVISO**************** | | A) FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE | | GEN/RES PERMIT REQUIRED WITH ZONING, ELECTRICAL, | | MECHANICAL, AND GAS APPROVAL OF GENERATOR PLACEMENT. | | | | B) FBC-2004 FUEL GAS SEC. 404.12 OUTLETCLOSURES: GAS | | OUTLETS THAT DO NOT CONNECT TO APPLIANCES SHALL BE | | CAPPED GAS TIGHT. | | | | C) NOTE: MINIMUM SIZE EXISTING 2 PSI GAS PIPING SIZE | | IS 1/2" FOR SCH 40, PE, AND CSST. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-03-07 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-03-07 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-03-01 |
Time |
14:33 |
Sent To |
|
|
Notes |
2007-03-01 14:33:17 | TO "G" BOX |
|
|
|