Plan Review Details - Permit 07020699
Plan Review Stops For Permit 07020699
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-20 Cont ID  
Sent By shill Date 2007-04-20 Time 17:59 Rev Time 0.00
Received By shill Date 2007-04-20 Time 17:59 Sent To I
Notes
2007-04-20 18:00:16NEEDS ZONING

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-29 Cont ID  
Sent By shill Date 2007-03-29 Time 16:19 Rev Time 0.00
Received By shill Date 2007-03-29 Time 16:19 Sent To  
Notes
2007-03-29 16:20:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)TWO ORIGINAL SETS REQUIRED
  
 2.)SEE PLUMBING REVIEWER'S COMMENT REGARDING THE
 ILLEGIBLE SEAL.
  
 3.)POOL IS TO COMPLY WITH FBC R4101.NO SAFETY NOTES
 ON PLAN.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-19 Cont ID  
Sent By btrobaug Date 2007-04-19 Time 10:21 Rev Time 0.33
Received By btrobaug Date 2007-04-19 Time 10:15 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By bpowell Date 2007-03-13 Time 15:38 Rev Time 0.50
Received By btrobaug Date 2007-03-15 Time 07:10 Sent To P
Notes
2007-03-15 07:22:44 
 DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 IF AN ELECTRIC HEATER IS TO BE INSTALLED
 PLEASE SUBMIT CALCULATIONS FOR THE MAINSERVICE. IF
 THE PANEL IS EXISTING, PLEASE INDICATE SAME ON THE
 SCHEMATIC, HAVE THE ENGINEER OF RECORD INITIAL SAME.
  
 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW POOL AND HEATER
 EQUIPMENT. 215.5 NEC 2005.
  
 3}TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 11:46 Rev Time 0.00
Received By shill Date 2007-05-03 Time 11:46 Sent To Z
Notes
2007-05-03 11:46:31TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 08:11 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 08:11 Sent To Z
Notes
2007-04-23 08:12:16TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-06 Cont ID  
Sent By shill Date 2007-04-20 Time 18:33 Rev Time 0.00
Received By spalmer Date 2007-04-06 Time 17:15 Sent To E
Notes
2007-04-06 17:15:43TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 14:26 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 14:26 Sent To E
Notes
2007-03-14 14:27:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-29 Cont ID  
Sent By shill Date 2007-03-29 Time 16:20 Rev Time 0.00
Received By shill Date 2007-02-27 Time 17:26 Sent To  
Notes
2007-02-27 17:26:49TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-20 Cont ID  
Sent By mperson Date 2007-04-20 Time 09:05 Rev Time 0.33
Received By mperson Date 2007-04-20 Time 09:05 Sent To B
Notes
2007-04-20 09:06:08NOTE: POOL HEATER IS AN ELECTRIC HEAT PUMP.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-21 Cont ID  
Sent By mperson Date 2007-03-21 Time 15:15 Rev Time 0.33
Received By mperson Date 2007-03-21 Time 15:15 Sent To B
Notes
2007-03-21 15:41:08DENIED
 REFERENCE: FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING
 POOLS; FBC-2004 CHAPTER 1, THE CITY OF WEST PALM BEACH
 AMENDMENTS; FLORIDA ADMINISTRATIVE CODE;
  
 THE FOLLOWING CORRECTION/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.1 SUBMITTAL
 DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
 NOTE: ONLY ONE SET OF CONSTRUCTION DOCUMENTS WERE
 SUBMITTED.
  
 2. PER FLORIDA ADMINISTRATIVE CODE AND FBC-2004
 CHAPTER 1, SECTION 106.1:
 FAC-61G15-23.002 SEAL SIGNATURE AND DATE
 SHALL BE AFFIXED:
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME LICENSE NUM-
 BER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF
 THE ENGNEERING BUSINESS ON EACH SHEET.
 NOTE: AFFXED SEAL IS WEAK.
  
 3. PLEASE CORRELATE THE VENT SIZE. THE VENT TABLE
 MAXIMUM LENGTH TABLE INDICATES A 1" VENT. THE PIPING
 SCHEMATIC AND THE MAIN DRAIN DETAIL INDICATE A 1-1/2"
 VENT. PLEASE CORRECT AND CORRELATE THE VENT SIZE ON THE
 RESUBMITTAL.
  
 4. COMPLY WITH FBC-2004 SEC 424.2, OR
 FBCR-2004 SEC R4101 PRIVATE SWIMMING
 POOLS.
 (PLEASE ADD TO NOTES ON THE RESUBMITTAL)
  
 5. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 6. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 7. THE POOL DATA & EQUIPMENT, AND SWIMMING POOL PLAN
 SEEM INCOMPLETE. THERE ARE NO MAIN DRAINS, INLETS,
 SKIMMER, CLEANER LINE OR VACUUM FITTING (OPTIONAL)
 INDICATED FOR THE POOL. PER FBC-2004 SECTION 424.2.6.2
 REQUIRED EQUIPMENT: EVERY SWIMMING POOL SHALL BE
 EQUIPPED COMPLETE WITH APPROVED MECHANICAL EQUIPMENT
 CONSISTING OF FILTER, PUMP, PIPING VALVES AND COMPONENT
 PARTS. PLEASE CLARIFY THE FILTER CYCLE INDICATED AS
 2.55 HRS IS THIS FOR THE POOL OR THE SPA OR FOR BOTH.
 PLEASE CLARIFY AND CORRECT ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-05-03 Cont ID  
Sent By bpowell Date 2007-05-03 Time 16:18 Rev Time 0.00
Received By bpowell Date 2007-05-03 Time 16:18 Sent To I
Notes
2007-05-03 16:29:56SEE PERMIT 06051189 FOR FENCE ENCLOSURE.BOBBY POWELL,
 JR. PLANNER

Review Stop Z ZONING
Rev No 2 Status F Date 2007-04-30 Cont ID  
Sent By bpowell Date 2007-04-30 Time 10:56 Rev Time 0.00
Received By bpowell Date 2007-04-30 Time 10:56 Sent To  
Notes
2007-04-30 10:55:291.A SEPARATE PERMIT IS REQUIRED FOR SCREEN
 ENCLOSURES.ALSO BOTH THE PERMIT FOR THE POOL, AND FOR
 THE SCREEN ENCLOSURE SHALL BE SUBMITTED CONCURRENTLY.
  
 2. PLEASE PROVIDE THE EXACT LOCATION OF THE POOL
 EQUIPMENT AND THE DIMENSION FROM THE PROPERTY LINE TO
 THE CLOSEST POINT OF THE EQUIPMENT.MECHANICAL
 EQUIPMENT SHALL NOT ENCROACH MORE THAN FOUR (4) FEET
 INTO ANY REQUIRED SETBACK.
  
 FOR QUESTIONS OR COMMENTS CONTACT:
 BOBBY POWELL, JR., PLANNER, (561) 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-13 Cont ID  
Sent By bpowell Date 2007-03-13 Time 11:28 Rev Time 0.00
Received By bpowell Date 2007-03-13 Time 11:28 Sent To E
Notes
2007-03-13 15:40:56PER ANDROS ISLE DESIGN GUIDELINES, POOLS SHALL BE
 SETBACK A MINIMUM OF 5 FEET FROM SIDE AND REAR PROPERTY
 LINES.
  
 BOBBY POWELL, JR., PLANNER, 822-1435,
 [email protected]