2007-03-21 15:41:08 | DENIED |
| REFERENCE: FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING |
| POOLS; FBC-2004 CHAPTER 1, THE CITY OF WEST PALM BEACH |
| AMENDMENTS; FLORIDA ADMINISTRATIVE CODE; |
| |
| THE FOLLOWING CORRECTION/INFORMATION IS REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PER FBC-2004 CHAPTER 1, SECTION 106.1 SUBMITTAL |
| DOCUMENTS. CONSTRUCTION |
| DOCUMENTS, SPECIAL INSPECTION AND |
| STRUCTURAL OBSERVATION PROGRAMS, AND |
| OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| MORE SETS WITH EACH APPLICATION FOR A |
| PERMIT. |
| NOTE: ONLY ONE SET OF CONSTRUCTION DOCUMENTS WERE |
| SUBMITTED. |
| |
| 2. PER FLORIDA ADMINISTRATIVE CODE AND FBC-2004 |
| CHAPTER 1, SECTION 106.1: |
| FAC-61G15-23.002 SEAL SIGNATURE AND DATE |
| SHALL BE AFFIXED: |
| EACH SHEET OF PLANS AND PRINTS WHICH |
| MUST BE SEALED UNDER PROVISIONS OF |
| CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| DATED BY THE PROFESSIONAL ENGINEER IN |
| RESPONSIBLE CHARGE. ENGINEERS SHALL |
| LEGIBLY INDICATE THEIR NAME, ADDRESS, |
| AND LICENSE NUMBER ON EACH SHEET. IF |
| PRACTICING THROUGH A DULY AUTHORIZED |
| ENGINEERING BUSINESS, ENGINEERS SHALL |
| LEGIBLY INDICATE THEIR NAME LICENSE NUM- |
| BER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF |
| THE ENGNEERING BUSINESS ON EACH SHEET. |
| NOTE: AFFXED SEAL IS WEAK. |
| |
| 3. PLEASE CORRELATE THE VENT SIZE. THE VENT TABLE |
| MAXIMUM LENGTH TABLE INDICATES A 1" VENT. THE PIPING |
| SCHEMATIC AND THE MAIN DRAIN DETAIL INDICATE A 1-1/2" |
| VENT. PLEASE CORRECT AND CORRELATE THE VENT SIZE ON THE |
| RESUBMITTAL. |
| |
| 4. COMPLY WITH FBC-2004 SEC 424.2, OR |
| FBCR-2004 SEC R4101 PRIVATE SWIMMING |
| POOLS. |
| (PLEASE ADD TO NOTES ON THE RESUBMITTAL) |
| |
| 5. FBC-2004 SEC. 424.2.14.1, OR |
| FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| SHEETS REQUIRED, PLEASE SUBMIT) |
| |
| 6. FBC-2004 SEC. 424.2.14.2, OR |
| FBCR-2004 SEC. R4101.14.2 WATER |
| RETENTION, PROVIDE A POSITIVE MEANS OF |
| RETAINING WATER IN THE HEATER WHEN PUMP |
| IS SHUT OFF.(MANUFACTURE SHEETS |
| REQUIRED, PLEASE SUBMIT) |
| |
| 7. THE POOL DATA & EQUIPMENT, AND SWIMMING POOL PLAN |
| SEEM INCOMPLETE. THERE ARE NO MAIN DRAINS, INLETS, |
| SKIMMER, CLEANER LINE OR VACUUM FITTING (OPTIONAL) |
| INDICATED FOR THE POOL. PER FBC-2004 SECTION 424.2.6.2 |
| REQUIRED EQUIPMENT: EVERY SWIMMING POOL SHALL BE |
| EQUIPPED COMPLETE WITH APPROVED MECHANICAL EQUIPMENT |
| CONSISTING OF FILTER, PUMP, PIPING VALVES AND COMPONENT |
| PARTS. PLEASE CLARIFY THE FILTER CYCLE INDICATED AS |
| 2.55 HRS IS THIS FOR THE POOL OR THE SPA OR FOR BOTH. |
| PLEASE CLARIFY AND CORRECT ON THE RESUBMITTAL. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |