Plan Review Details - Permit 07020687
Plan Review Stops For Permit 07020687
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-03-12 Cont ID  
Sent By mawillia Date 2007-03-12 Time 15:26 Rev Time 0.00
Received By mawillia Date 2007-03-12 Time 15:07 Sent To  
Notes
2007-03-12 15:16:44-*****APPROVED*****
  
 SHEETS FP-2, FP-3, AND FP-4 WERE STAMPED, INTIALED, AND
 DATED.READY FOR PERMIT ISSUANCE.
  
  
 **REMINDERS**
  
 1.WATERFLOW ACTIVATION SHALL INTIATE A GENERAL ALARM
 WITHIN 45 TO 60 SECONDS.
  
 2.SPRINKLER SYSTEM IS TO BE MONITORED.
  
 3.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY.
 COORDINATE WITH THE GENERAL AND/OR FIRE ALARM CONTRATOR
 BY FINAL SPRINKLER/FIRE ALARM INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-12 Cont ID  
Sent By mawillia Date 2007-03-12 Time 15:07 Rev Time 0.00
Received By mawillia Date 2007-02-27 Time 17:22 Sent To  
Notes
2007-02-27 17:22:19TO "F" BOX