Plan Review Details - Permit 07020647
Plan Review Stops For Permit 07020647
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-03 Cont ID  
Sent By mwennerg Date 2007-04-03 Time 11:53 Rev Time 0.00
Received By mwennerg Date 2007-04-03 Time 11:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-03-13 Cont ID  
Sent By mawillia Date 2007-03-13 Time 18:30 Rev Time 0.00
Received By mawillia Date 2007-03-13 Time 18:16 Sent To  
Notes
2007-03-13 18:30:27*****UNSAT*****
  
  
  
 1.)61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 2.)471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 IF FURTHER INFORMATION IS NEEDED IN REFERENCE TO THE
 ABOVE MATTERS, CONTACT MR. ROBERT BROWN, LICENSE &
 PERMIT SERVICES MANAGER AT (561) 805-6652.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-05 Cont ID  
Sent By mawillia Date 2007-03-05 Time 17:05 Rev Time 0.00
Received By mawillia Date 2007-03-05 Time 16:43 Sent To  
Notes
2007-03-05 17:04:39*****DENIED*****
  
  
  
  
 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK IS
 BEING CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.THE NUMERICAL ADDRESS IS REQUIRED. ON LOCATION
 SECTION OF HYDRAULIC DESIGN INFORMATION SHEET.
  
 3.THE SPECIFICATION SHEET FOR THE STYLE 009 FIRELOCK
 EZ RIGID COUPLING HAS THE STAMPING OF THE TOWN OF
 JUPITER.ALL SUCH PAPERWORK WILL BE STAMPED BY THE
 (AHJ) CITY OF WEST PALM BEACH.
  
 4.PLEASE PROVIDE SAFETY MARGIN CALCULATION FOR THIS
 SYSTEM.AS PER WEST PALM BEACH FIRE PREVENTION, A
 SAFETY MARGIN OF NO LESS THAN 5.0 PSI IS REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS , INCLUDE A
 RESPONSE LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-28 Cont ID  
Sent By spalmer Date 2007-03-28 Time 17:39 Rev Time 0.00
Received By spalmer Date 2007-03-28 Time 17:39 Sent To FIRE
Notes
2007-03-28 17:39:48TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 13:04 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 13:04 Sent To FIRE
Notes
2007-03-10 13:04:45TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-05 Cont ID  
Sent By mawillia Date 2007-03-05 Time 16:44 Rev Time 0.00
Received By mawillia Date 2007-02-27 Time 11:33 Sent To  
Notes
2007-02-27 11:33:46TO "F" BOX