2007-03-30 09:11:42BUILDING PLAN REVIEW
 PERMIT: 07020640
 ADD: 250 S. AUSTRALIAN AVE. # 100
 CONT: FISHER CONTRACTING CORP
 TEL: (561) 691-4716
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A4.1 SERVING LINE DETAIL INDICATES A CUT
 SECTION5 & 6 OF A1.1 IN NEATHER SECTION IS THE HEIGHT
 OF THE SERVING COUNTER PROVIDED.
 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION
 OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN
 LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH
 SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 3B) ALSO SEE THE COUNTER HEIGTH OF THE ISLAND A1.1
 DEETAIL# 9, PLEASE CORRECT.
  
 4) PLEASE INDICATE THE AREAS FOR ACCESSIBLITY. 11-5.1
 GENERAL.
 EXCEPT AS SPECIFIED OR MODIFIED IN THIS SECTION,
 RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35 .
 WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS
 CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE
 ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS
 REQUIRED IN SECTION 11-4.1.3 (18). IN ESTABLISHMENTS
 WHERE SEPARATE AREAS ARE DESIGNATED FOR SMOKING AND
 NONSMOKING PATRONS, THE REQUIRED NUMBER OF ACCESSIBLE
 FIXED TABLES (OR COUNTERS) SHALL BE PROPORTIONALLY
 DISTRIBUTED BETWEEN THE SMOKING AND NONSMOKING AREAS.
 IN NEW CONSTRUCTION, AND WHERE PRACTICABLE IN
 ALTERATIONS, ACCESSIBLE FIXED TABLES (OR COUNTERS)
 SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR FACILITY.
 11-5.2
  
  
 5 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED. PLANS SUBMITTED AFTER DEC. 8,
 2006 ARE TO BE REVIEWED UNDER FBC 2006 AMENDMEENTS
 NOTE ALSO TO BE REVIEWED UNDER THE 2006 FBC EXISTING
 BUILDING CODE, PROVIDE LEVEL OF ALTERATION
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-20 Cont ID  
Sent By dpalmer Date 2007-08-20 Time 11:21 Rev Time 0.00
Received By dpalmer Date 2007-08-20 Time 11:21 Sent To  
Notes
2007-08-20 11:22:40REDLINED
 A2.1 SHOWS OLD REFLECTED LIGHTING/CEILING PLANS.
 NOTE REDLINED TO SEE NEW REVISED E1.1 FOR REVISED
 LIGHTING.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-19 Cont ID  
Sent By dpalmer Date 2007-06-19 Time 18:38 Rev Time 0.00
Received By dpalmer Date 2007-06-19 Time 17:03 Sent To  
Notes
2007-06-19 18:38:35*** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW STILL
 NEED TO BE CLARIFIED.
 SOME COMMENTS ARE NEW DUE TO INFORMATION ONLY NOW BEING
 SUBMITTED OR SHOWN ON PLANS.
  
  
 1) NOTE: PLEASE SEE THE PLANS NOW MENTIONS NEW LIGHTING
 CONTROLS BEING INSTALLED HOWEVER THE RESPONSE LETTER
 MENTIONS TO SEE KEY NOTE ON PLANS. THE KEY NOT ON PLANS
 ONLY STATES THE NEW DEVICES ARE TO COMPLY WITH THE FBC
 CHAPTER 13. PLEASE KNOW THAT QUOTING THE CODE ON PLANS
 IN LIEU OF SHOWING CODE COMPLIANCE DETAIL(S) IS NOT
 ACCEPTABLE.
 PLEASE SHOW LOCATIONS OF THESE DEVICES AS THE CODE DOES
 REQUIRE THEM TO BE LOCATED IN SPECIFIC LOCATIONS.
 PLEASE INDICATE THE TYPE OF DEVICE WHICH IS TO BE
 INSTALLED SO THAT MINIMUM COVERAGE AND CONTROL AND CAN
 BE VERIFIED FOR THE ENERGY CODE AND LIFE SAFETY CODE.
 PLEASE INDICATE THE MAXIMUM AMOUNT OF TIME ON DEVICES:
 THIS WILL DEPEND ON THE TYPE OF DEVICE CHOSEN. (4HRS
 MAX FOR TIMER TYPE AND 30MINS MAXIMUM FOR OS TYPE
 DEVICES)
 13-415.1.ABC.1.1, .1.2
 PLEASE SEE THE NUMBER OF LIGHTING FIXTURES LISTED ON
 PERFORMANCE CALCULATIONS DO NOT COORDINATE WITH PLANS.
 PLEASE GO THROUGH ALL FIXTURES AND PLEASE SEE RECESSED
 LIGHTS WHICH BULBS ARE BEING CHANGED OUT SHOULD
 INDICATE THE NEW WATTAGE.
 PLEASE CALL TO GO OVER ITEMS IN THE CODE WHICH GIVES
 YOU ADDITIONAL WATTAGE PER SQ FT IF NEEDED.
  
 2) NOTE: PLEASE SEE THE LIGHTING FIXTURES FOR EMERGENCY
 LIGHTING ON PLANS AND FIXTURE LEGEND IS VERY FAINT.
 PLEASE SEE SEVERAL OF THESE ARE REDLINED WITH CIRCLES
 ON PLANS AND FIXTURE LEGEND. PLEASE ADJUST PRINTING O
 THIS FOR LS 101 7.8, 7.9
 ALREADY CORRECTED CIRCUITING.
  
 3) NOTE: PLEASE SEE PLANS MENTIONS THE TRANSFORMER IS
 TO BE RELOCATED HOWEVER PLANS DO NOT INDICATE THE NEW
 LOCATION? PLEASE SEE 450.13, 110.26 AS THE LOCATION IS
 NOT PERMITTED ABOVE CEILINGS FOR THE SIZE UNIT ETC AND
 MINIMUM CLEARANCES ON FLOOR IS ALSO REQUIRED.
 PLEASE COMPLETE.
  
 4) NOTE: PLEASE SEE RISER HAS NOW BEEN REVISED TO
 INCLUDE A NEW DISCONNECT ON THE LOAD SIDE OF THE
 TRANSFORMER HOWEVER THE PLANS DO NOT SHOW THIS
 DISCONNECT. REVIEW FOR LOCATION FOR 240.21,110.26 AND
 240.24 ETC CAN NOT BE VERIFIED AT THIS TIME.
 PLEASE SHOW LOCATION OF THIS NEW DISCONNECT ON PLANS.
  
 5) NOTE: PLEASE SEE MY PREVIOUS COMMENT WITH RESPECT TO
 GFI PROTECTION OF RECEPTACLES IN KITCHEN (210.8B2) AND
 THE RESPONSE MENTIONED TO SEE REVISED ELECTRICAL NOTE.
 THE ELECTRICAL NOTE HAD NO REFERENCE TO GFI PROTECTION
 AND ONLY MENTION *MOISTURE PROOF*?
  
 6) NOTE: PLEASE SEE THE PREVIOUS PLANS INDICATE CLEAR
 DEFINITIONS OF WALLS ETC FROM DINING AREA TO KITCHEN
 AND BAR AREA HOWEVER THE NEW SHEETS HAVE THESE
 REMOVED?
 PLEASE SEE PREVIOUS PLANS ATTACHED.
 FBC 106.1.2
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 13:49 Sent To  
Notes
2007-03-04 14:24:16** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGE SIN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE ALSO SEE ELECTRICAL CHANGES UNDER THE 2005
 INCLUDING ANY SECTIONS OF CODES WHICH ARE REFLECTED ON
 PLANS FROM THE PREVIOUS 2002 NEC.
 PLEASE LIST THE FOLLOWING FOR THIS REVIEWER AT A
 MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE:PLEASE SUBMIT ENERGY/PERFORMANCE CALCULATIONS
 FOR NEW LIGHTING.
 PLEASE KNOW THAT ALL NEW SHALL COMPLY WITH THE CHAPTER
 13 REQUIREMENTS.
 PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED
 FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS
 ON THE ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1,
 13-415.2.
  
 3) NOTE: PLEASE SEE THAT PLANS DO NOT INDICATE ANY
 METHODS FOR THE REQUIRED AUTOMATED CONTROLS PER FBC
 2004 W/2006 REVISIONS. ANY NEW AREAS, LIGHTING AND
 CONTROLS.
 THE SCOPE OF WORK AS NOTED AND SHOWN ON PLANS WILL
 REQUIRE CHAPTER 13 COMPLIANCE FOR CONTROLS AND
 LIGHTING.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 4) NOTE: PLEASE PROVIDE LOCATIONS FOR ELECTRICAL PANELS
 WHETHER NEW OR EXISTING ALONG WITH TRANSFORMER
 LOCATION.
 PLEASE KNOW AT THIS TIME ONE PANEL IS BEING NOTED AS
 BEING PLACED IN A STORAGE ROOM WHICH IS NOT PERMITTED.
 PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE
 ELECTRICAL PANEL(S) NEED TO MEET 110.26.
 PLEASE ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY
 IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES
 WITH OVER CURRENT PROTECTION DEVICES.
 PLEASE ADJUST PLANS.
 PLEASE SEE 450.9, 450.13, 450.21 FOR TRANSFORMER
 LOCATIONS.
  
 5) NOTE:PLEASE SEE PANELS SEEMS TO BE NOTED AS
 EXISTING; HOWEVER THE RISER DOES NOT SEEM TO SHOW WHAT
 IS EXISTING OR WHAT IS NEW.
 PLEASE CLARIFY.
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE KNOW WHETHER NEW OR EXISTING THE PANEL
 ON THE SECONDARY SIDE OF THE TRANSFORMER WILL REQUIRE A
 MCB IF NOT EXISTING.
 PLEASE ALSO SEE THE TAP CONDUCTOR RULES AS STATED IN
 240.21C
 PLEASE ALSO SEE 408.16
  
 7) NOTE: PLEASE SEE PLANS MENTIONS TO REMOVE ALL HORNS
 AND STROBES, PLEASE BE SURE TO NOTE ON PLANS THAT ANY
 NEW DEVICES BEING RE-INSTALLED SHALL MEET FBC
 11-4.28.1,.2 AND .3(4). PLEASE STATE LEVELS FOR THESE
 DEVICES FOR ADA COMPLIANCE.
 PLEASE KNOW ANY OLD DEVICES WHICH MAY NOT MEET CODE
 WILL NOT BE PERMITTED TO BE RE-INSTALLED. NEW DEVICES
 WILL BE REQUIRED.
  
 8) NOTE: PLEASE CLARIFY THE RECEPTACLE DEVICES IN
 KITCHEN/FOOD AREAS MEETING 210.8B3
  
 9) NOTE: PLEASE CLARIFY THE NOTE ON PANEL *PB* WHICH
 MENTIONS 2-POLE 40AMP BREAKER ON #10 CONDUCTORS ALONG
 WITH 6 ADDITIONAL #10 CONDUCTORS IN ONE SINGLE 1/2 INCH
 CONDUIT. PLEASE SEE TABLES IN CHAPTER 9 AS PIPE FILL IS
 EXCEEDED. (C.1)
  
 10) NOTE: PLEASE KNOW IF THE SCOPE OF ELECTRICAL WORK
 IS THE INSTALLATION OF THE SERVICE EQUIPMENT AS SHOWN
 ON RISER AND ALL SERVICE EQUIPMENT DOES NOT EXIST AT
 PRESENT AND IS NEW, THEN THE PLANS WILL BE REQUIRED TO
 BE SIGNED, DATED AND SEALED BY A PE. FS
 471.003(2)(H)(2A)
  
 11) NOTE: PLEASE SHOW GROUNDING ATTACHMENT FOR THE
 TRANSFORMER IF NEW.
 250.20, 250.30, 250.66
  
 12) NOTE: PLEASE NOTE IF EM/EXT LTS ARE WIRED PER
 700.12E (LOCAL LIGHTING BRANCH CIRCUIT).
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-02 Cont ID  
Sent By mwennerg Date 2007-07-02 Time 14:49 Rev Time 0.00
Received By mwennerg Date 2007-07-02 Time 14:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By mwennerg Date 2007-03-30 Time 14:11 Rev Time 0.00
Received By mwennerg Date 2007-03-30 Time 14:11 Sent To  
Notes
2007-03-30 14:29:01***DENIED***
  
 1) FOOD THAT PRODUCES GREASE LADEN SMOKE AND VAPORS
 SHALL BE PROTECTED BY AN APPROVED HOOD/SUPPRESSION
 SYSTEM IN ACCORDANCE WITH NFPA 96. SEPARATE SHOP
 DRAWINGS AND PERMITS REQUIRED FOR HOOD AND SUPPRESSION
 SYSTEMS. PLEASE CLARIFY HOW EXISTING SYSTEM WILL BE
 IMPACTED BY THIS WORK.
  
 2) SEPARATE SHOP DRAWINGS REQUIRED FOR FIRE SPRINKLER
 AND FIRE ALARM REMODEL.
  
 3) "K" TYPE FIRE EXTINGUISHER IS REQUIRED IN KITCHEN
 AREA.
  
 4)ANY DOOR IN A MEANS OF EGRESS SERVING AN OCCUPANT
 LOAD OF 100 OR GREATER THAN 100 PERSONS, SHALL COMPLY
 WITH NFPA 101, SEC. 12.2.2.2.3, AND SHALL BE PROVIDED
 WITH PANIC HARDWARE.
  
 5) 2A-10B,C RATED FIRE EXTINGUISHERS SHALL BE PROVIDED
 IN LOCATIONS NOT TO EXCEED 75' TRAVEL DISTANCE TO REACH
 AN EXTINGUISHER.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-03 Cont ID  
Sent By shill Date 2008-07-03 Time 16:54 Rev Time 0.00
Received By shill Date 2008-07-03 Time 16:54 Sent To E
Notes
2008-07-03 16:54:52TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-31 Cont ID  
Sent By adarroug Date 2007-07-31 Time 15:36 Rev Time 0.00
Received By adarroug Date 2007-07-31 Time 15:36 Sent To  
Notes
2007-08-15 08:51:06TO "COMM" BD#5
2007-07-31 15:36:55WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 14:51 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 14:51 Sent To  
Notes
2007-06-12 13:40:58TO "COMM" BD#61
2007-05-23 14:52:11WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-30 Cont ID  
Sent By mwennerg Date 2007-03-30 Time 14:37 Rev Time 0.00
Received By mwennerg Date 2007-02-27 Time 08:53 Sent To  
Notes
2007-03-01 11:17:37TO "COMM" BD#14
2007-02-27 08:53:13WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-03-19 Cont ID  
Sent By rregueir Date 2007-03-19 Time 08:52 Rev Time 0.00
Received By rregueir Date 2007-03-19 Time 07:31 Sent To  
Notes
2007-03-19 08:52:28PLEASE NOTE:
  
 PAGE D1 INDICATED KITCHEN HOOD TO BE REMOVED, STORED
 AND REINSTALLED DURING THE RENOVATION PROCESS. SEPARATE
 MECHANICAL PERMITS WILL BE REQUIRED FOR THE HOOD AS
 WELL AS THE HOOD SUPPRESSION SYSTEMS.
  
 THE SCOPE OF WORK AS DESCRIBED IN THE CONSTRUCTION
 DOCUMENTS INDICATES THAT A MECHANICAL PERMIT IS NOT
 REQUIRED FOR ANY WORK RELATED TO THE AIR CONDITIONING
 SYSTEM IN THIS AREA. SHOULD IT BECOME NECESSARY TO
 REPLACE ANY OF THE DUCTWORK, PLEASE SUBMIT A NEW
 MECHANICAL PERMIT APPLICATION PRIOR TO THE COMMENCEMENT
 OF THAT WORK.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-15 Cont ID  
Sent By kstevens Date 2007-09-15 Time 10:51 Rev Time 0.00
Received By kstevens Date 2007-09-15 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-06 Cont ID  
Sent By kstevens Date 2007-07-06 Time 09:45 Rev Time 0.00
Received By kstevens Date 2007-07-06 Time 09:45 Sent To  
Notes
2007-07-06 09:52:17DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW
  
 1. OK
  
 2. SHT P1.1 THE RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN.TWO FLOOR SINKS AND A FLOOR CLEANOUT SHOWN
 ON THE RISER DIAGRAM ARE NOT SHOWN ON THE RISER
 DIAGRAM.--THE SINK IN THE CABINET IS SHOWN ON THE
 LEFT SIDE OF THE BUILDING DRAIN LINE ON THE FLOOR PLAN,
 BUT ON THE RIGHT SIDE OF THE DRAIN LINE ON THE RISER
 DIAGRAM.--THE FLOOR PLAN SHOWS A LINE FROM THE
 3-COMPARTMENT SINK TO THE BRANCH LINE TO THE MOP SINK
 AND A DRAINAGE LINE FROM THE LAV TO THE BRANCH LINE TO
 THE MOP SINK. THESE LINES ARE NOT INDICATED ON THE
 RISER DIAGRAM.PLEASE CORRELATE THE INFORMATION
 BETWEEN THE RISER AND THE FLOOR PLAN. SECTION 106.1.1.
 (SEE RED LINE MARK-UP ON ONE SET OF P1.1).
 ****THE LAV SHALL CONNECT TO THE SANITARY RISER DIAGRAM
 AS WAS INDICATED ON THE TOILET ROOM RISER DIAGRAM FIRST
 SUBMITTED. THE INTENT WAS TO HAV THE LAV TO THE GREASE
 SYSTEM DELETED FROM THE FLOOR PLAN. ONLY GREASE LADEN
 WASTE SHALL DISCHARGE INTO THE GREASE SYSTEM. THE LAV
 WILL ACT AS THE WET VENT FOR THE TOILET ROOM.
  
 3. OK
 4. OK
 5. OK
  
 6. SHT P1.1 THE DOMESTIC WATER RISER DIAGRAM INDICATES
 AN ICE MAKER. AN INDIRECT WASTE RECEPTOR IS REQUIRED
 FOR THE DRAINAGE OF THE ICE MAKER. PLEASE INDICATE THE
 LOCATION OF THE ICE MAKER AND THE FLOOR SINKON THE
 FLOOR PLAN. SECTION 106.1.1. A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE SUPPLY TO THE ICE MAKER. SECTION
 604.9.
 ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR SHALL
 BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 204 & MANUFACTURE
 INSTALLATION INSTRUCTIONS.
  
 7. OK
  
 ****NEW COMMENT:
  
 1B. THE STAMPED PLANS FROM DBPR ARE NOW NOT SUBMITTED.
 PLEASE SUBMIT THE ORIGINAL SHEETS A1.1 IN THE NEW SETS
 OF PLANS BEING SUBMITTED AND INDICATE THAT THEY ARE FOR
 "REFERENCE TO THE DBPR REVIEW" AND TO SEE REVISED SHEET
 A1.1 FOR ALL OTHERAPPROVED INFORMATION. SECTION
 102.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-17 Cont ID  
Sent By kstevens Date 2007-03-17 Time 16:31 Rev Time 0.00
Received By kstevens Date 2007-03-17 Time 16:31 Sent To  
Notes
2007-03-17 16:51:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT A1.1 FLOOR PLAN KEYNOTE #2 NOT SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1.
  
 2. SHT P1.1 THE RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN.TWO FLOOR SINKS AND A FLOOR CLEANOUT SHOWN
 ON THE RISER DIAGRAM ARE NOT SHOWN ON THE RISER
 DIAGRAM.--THE SINK IN THE CABINET IS SHOWN ON THE
 LEFT SIDE OF THE BUILDING DRAIN LINE ON THE FLOOR PLAN,
 BUT ON THE RIGHT SIDE OF THE DRAIN LINE ON THE RISER
 DIAGRAM.--THE FLOOR PLAN SHOWS A LINE FROM THE
 3-COMPARTMENT SINK TO THE BRANCH LINE TO THE MOP SINK
 AND A DRAINAGE LINE FROM THE LAV TO THE BRANCH LINE TO
 THE MOP SINK. THESE LINES ARE NOT INDICATED ON THE
 RISER DIAGRAM.PLEASE CORRELATE THE INFORMATION
 BETWEEN THE RISER AND THE FLOOR PLAN. SECTION 106.1.1.
 (SEE RED LINE MARK-UP ON ONE SET OF P1.1).
  
 3. SHT P1.1 THE GREASE LINE UPSTREAM OF THE GREASE
 INTERCEPTOR IS LABELED AS A SANITARY LINE. PLEASE
 CORRECT. SECTION 106.1.1.
  
 4. SHT P1.1 THE INLET AND OUTLET PIPING FOR THE GREASE
 INTERCEPTOR REQUIRES A 2-WAY CLEANOUT ON EACH PIPE.
  
 5. SHT P1.1 PLUMBING NOTES #1 INDICATES THE CODE
 REFERENCE AS FBC-2001. PLANS SHOULD INDICATE FBC-2004
 AS THE DESIGN CODE.
  
 6. SHT P1.1 THE DOMESTIC WATER RISER DIAGRAM INDICATES
 AN ICE MAKER. AN INDIRECT WASTE RECEPTOR IS REQUIRED
 FOR THE DRAINAGE OF THE ICE MAKER. PLEASE INDICATE THE
 LOCATION OF THE ICE MAKER AND THE FLOOR SINKON THE
 FLOOR PLAN. SECTION 106.1.1. A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE SUPPLY TO THE ICE MAKER. SECTION
 604.9.
  
 7. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE CONTACT RODNEY
 COMPO @ (561) 822-2272, OR FAX (561) 822- 2287, OR
 E-MAIL [email protected]. FOR A DETERMINATION. SECTION III
 OF THE MUNICIPAL CODE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]