Plan Review Details - Permit 07020570
Plan Review Stops For Permit 07020570
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-28 Cont ID  
Sent By lmartine Date 2007-08-28 Time 17:45 Rev Time 0.00
Received By lmartine Date 2007-08-28 Time 17:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-27 Cont ID  
Sent By lmartine Date 2007-06-27 Time 19:05 Rev Time 0.00
Received By lmartine Date 2007-06-27 Time 18:41 Sent To  
Notes
2007-06-27 19:04:48BUILDING REVIEW COMMENTS
  
 THANK YOU FOR THE SURVEYS.
  
 THE PRODUCT APPROVAL PROVIDED IS ONLY TESTED FOR SMALL
 MISSLE ON INSTALLATIONS OVER 30', LARGE MISSLE TESTING
 IS REQUIRED ON INSTALLATIONS UNDER 30'.
  
 THE PLAN SHOWS NEW DOORS, SIDING AND STRUCTURAL
 FASTENERS, PLEASE SUBMIT APPROPRIATE APPROVALS.
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-04 Cont ID  
Sent By lmartine Date 2007-04-04 Time 16:55 Rev Time 0.00
Received By lmartine Date 2007-02-26 Time 10:41 Sent To  
Notes
2007-04-04 17:23:08 
 BUILDING REVIEW COMMENTS
  
  
 SUBMIT 2 COPIES OF SURVEY.
 SUBMIT 2 COPIES OF FLORIDA PRODUCT APPROVALS FOR ANY
 NEW WINDOWS , SHUTTERS , DOORS , ROOF COVER ,
 HARDIPANEL SIDING , AND ALL STRUCTURAL FASTNERS.
 SOIL AT NEW DECK AREA SHALL BE TERMITE TREATED.
 PROVIDE ENERGY CALCULATIONS COMPLYING WITH CHAPTER 6,
 2004 FBC.
  
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710
2007-02-26 10:43:10THIS WAS PREINSPECTED. THE SCOPE AND VALUATION OF WORK
 APPEARS TO BE OK. REQUIRE PLAN REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-06 Cont ID  
Sent By btrobaug Date 2007-08-06 Time 17:22 Rev Time 0.00
Received By btrobaug Date 2007-08-06 Time 17:14 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2007-08-06 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-03-28 Cont ID  
Sent By btrobaug Date 2007-03-28 Time 16:26 Rev Time 0.33
Received By btrobaug Date 2007-03-28 Time 16:15 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-28 Cont ID  
Sent By adarroug Date 2007-07-28 Time 14:51 Rev Time 0.00
Received By adarroug Date 2007-07-28 Time 14:51 Sent To Z
Notes
2007-07-28 14:53:06TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 09:49 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 09:49 Sent To B
Notes
2007-06-07 09:49:53TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 14:03 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 14:03 Sent To Z
Notes
2007-06-01 14:03:56TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-27 Cont ID  
Sent By spalmer Date 2007-03-27 Time 17:41 Rev Time 0.00
Received By spalmer Date 2007-03-27 Time 17:41 Sent To  
Notes
2007-03-27 17:41:49TO SFR "ELEC"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-24 Cont ID  
Sent By shill Date 2007-03-24 Time 08:33 Rev Time 0.00
Received By shill Date 2007-03-24 Time 08:33 Sent To  
Notes
2007-03-24 08:35:51RESIDENTIAL REMOD, NEEDS ZONING, ELECTRIC, BLDG
  
 ROUTED TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-04 Cont ID  
Sent By lmartine Date 2007-04-04 Time 17:23 Rev Time 0.00
Received By lmartine Date 2007-02-27 Time 15:24 Sent To  
Notes
2007-02-27 15:25:11TO "MISC" BOX#1

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-08 Cont ID  
Sent By mperson Date 2007-08-08 Time 09:18 Rev Time 0.33
Received By mperson Date 2007-08-08 Time 09:18 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-26 Cont ID  
Sent By mperson Date 2007-06-26 Time 09:57 Rev Time 0.33
Received By mperson Date 2007-06-26 Time 09:57 Sent To B
Notes
2007-06-26 10:03:53DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS WERE NOT
 ADDRESSED. PLEASE COMPLY ON THE RESUBMITTAL:
  
 1. SHEET A-1 TITLE BLOCK IS INCOMPLETE: FAC-61G1-16.004
 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 NOTE: A SPACE FOR THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS MISSING AND THE SIGNATURE ON
 THE SEAL APPEAR TO BE INITIALED INSTEAD OF BEING
 SIGNED. PLEASE SUBMIT A NOTARIZED COPY OF SIGNITURE FOR
 VARIFICATION TO BE FILED FOR FUTURE REFERENCE.
  
 2. SHEET A-1 PLUMBING NOTES NUMBER 1: PLEASE DELETE THE
 YEAR 2001 AND ADD IN ITS PLACE 2004 FLORIDA BUILDING
 CODE.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-29 Cont ID  
Sent By mperson Date 2007-03-29 Time 11:22 Rev Time 0.45
Received By mperson Date 2007-03-29 Time 11:22 Sent To E
Notes
2007-03-29 11:44:02DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A-1 TITLE BLOCK IS INCOMPLETE: FAC-61G1-16.004
 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 NOTE: A SPACE FOR THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS MISSING AND THE SIGNATURE ON
 THE SEAL APPEAR TO BE INITIALED INSTEAD OF BEING
 SIGNED. PLEASE SUBMIT A NOTARIZED COPY OF SIGNITURE FOR
 VARIFICATION TO BE FILED FOR FUTURE REFERENCE.
  
 2. SHEET A-1 PLUMBING NOTES NUMBER 1: PLEASE DELETE THE
 YEAR 2001 AND ADD IN ITS PLACE 2004 FLORIDA BUILDING
 CODE.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-07-31 Cont ID  
Sent By adavila Date 2007-07-31 Time 09:44 Rev Time 0.00
Received By adavila Date 2007-07-30 Time 09:44 Sent To E
Notes
2007-07-31 09:44:45PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-06-06 Cont ID  
Sent By adavila Date 2007-06-06 Time 17:12 Rev Time 0.00
Received By adavila Date 2007-06-04 Time 13:13 Sent To I
Notes
2007-06-06 17:12:45PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. THE EXISTING ACCESSORY APARTMENT AND GARAGE, IS A
 NONCONFORMING USE WITH NO ADVERSE IMPACTS AS DEFINED IN
 THE NONCONFORMING SECTION OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.THEREFORE, ANY ALTERATIONS OR
 REPAIRS SHALL BE SUBJECT TO THE NONCONFORMING
 REGULATIONS, ARTICLE XVI, OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 2. SURVEY AND FLOOR PLAN DIMENSIONS DO NOT MATCH.
 PLEASE NOTE THAT THE SURVEY AND FLOOR PLAN SHALL
 REFLECT SAME ACTUAL CONDITIONS.IN THE EVENT THAT
 ADDITIONAL STRUCTURE WILL BE ADDED, THIS SHALL BE
 INDICATED AND REFLECTED ON BOTH COPIES OF THE SURVEY.
  
 3. PURSUANT TO SECTION 94-513(A)(2), NONCONFORMING
 STRUCTURES MAY BE IMPROVED, CONSTRUCTED, ENLARGED OR
 ALTERED AS LONG AS NO NEW NONCONFORMITY IS CREATED OR
 ANY EXISTING NONCONFORMITY INCREASED.
 A. PROVIDE SETBACK DIMENSIONS FROM THE WEST PROPERTY
 LINE TO ALL POINTS OF THE PART OF THE ACCESSORY
 APARTMENT THAT WILL BE DEMOLISHED AND REBUILT.THE
 REBUILT PORTION OF THE STRUCTURE SHALL BE NO LESS THAN
 FIVE (5) FEET FROM THE WEST PROPERTY LINE.
 B. PROVIDE BUILDING HEIGHT FROM GRADE.
 C. PROVIDE ROOF OVERHANG DIMENSION.PLEASE NOTE THAT
 PER SECTION 94-305(B)(2), ROOF OVERHANGS MAY NOT
 PROJECT MORE THAN THREE (3) FEET INTO ANY SETBACK.
  
 4. PURSUANT TO SECTION 94-513(B) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, NONCONFORMING USES WITH NO
 ADVERSE IMPACTS MAY BE ALTERED OR REPAIRED PROVIDED
 THAT THE COSTS INCURRED WITHIN ANY 12-MONTH PERIOD
 SHALL NOT EXCEED 50 PERCENT OF THE VALUE OF THE
 STRUCTURE PRIOR TO THE COMMENCEMENT THEREOF.PROVIDE
 THE VALUE OF THE ACCESSORY APARTMENT AND GARAGE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-27 Cont ID  
Sent By adavila Date 2007-03-27 Time 10:15 Rev Time 0.00
Received By adavila Date 2007-03-27 Time 08:48 Sent To I
Notes
2007-03-27 09:44:00PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.TWO (2) SIGNED AND SEALED SURVEYS SHALL BE
 PROVIDED.THE SURVEYS SHALL BE LESS THAN A YEAR OLD.
  
 2.SURVEYS SHALL SHOW ALL SETBACK DIMENSIONS FROM
 PROPERTY LINE TO STRUCTURES, AS WELL AS SETBACK
 DIMENSIONS FROM ALL EXISTING STRUCTURES.
  
 3.PLEASE INDICATE WHETHER OR NOT ANY SQUARE FOOTAGE
 WILL BE ADDED TO THE EXISTING STRUCTURE(S).
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  
  