Plan Review Stops For Permit 07020515
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-03-23 Cont ID  
Sent By shill Date 2007-03-23 Time 16:51 Rev Time 0.00
Received By shill Date 2007-03-23 Time 16:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-03-29 Cont ID  
Sent By jleahy Date 2007-03-29 Time 14:01 Rev Time 0.45
Received By jleahy Date 2007-03-29 Time 14:01 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-03-14 Cont ID  
Sent By btrobaug Date 2007-03-14 Time 09:43 Rev Time 0.33
Received By btrobaug Date 2007-03-14 Time 09:19 Sent To M
Notes
2007-03-14 09:57:02 
  
 PROVISO
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 PLEASE COMPLY PRIOR TO RESUBMITTING FOR REVIEW.
  
 THE NOTICE OF COMMENCEMENT IS INCORRECT AND VOID.
 PLEASE PROVIDE A CURRENT NOTICE FOR THIS PROJECT.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-03-29 Cont ID  
Sent By mperson Date 2007-03-29 Time 15:13 Rev Time 0.55
Received By mperson Date 2007-03-29 Time 15:13 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By mperson Date 2007-03-15 Time 11:29 Rev Time 0.45
Received By mperson Date 2007-03-15 Time 11:29 Sent To B
Notes
2007-03-15 12:00:07DENIED
 REFERENCE: FBC-2004 FUEL GAS; THE CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS; RESIDENTIAL
 GENERATOR PERMIT APPLICATION REQUIREMENTS;
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. UNTIL THE ZONING ISSUE IS RESOLVED GAS PERMIT CAN
 NOT BE ISSUED DUE TO THE FACT THAT THE GENERATORS
 PLACEMENT MIGHT CHANGE.
  
 2. THE SUBMITTED MANUFACTURER SPECIFICATIONS HAVE
 PROPANE INDICATED AS THE FUEL SOURCE AND THE SUBMITTED
 GAS PERMIT APPLICATION AND PLANS ARE INDICATING NATURAL
 GAS AS THE FUEL SOURCE. PLEASE CORRELATE AND RESUBMIT.
  
 3. THE SUBMITTED MANUFACTURER SPECIFICATIONS FOR THE
 GENERATOR ARE INDICATING THE NATURAL GAS BTU LOAD AS
 560,000 AND THE SUBMITTED GAS DRAWINGS ARE INDICATING
 THE GENERATOR BTU LOAD AS 548,000. PLEASE CORRECT THE
 GAS DRAWINGS TO REFLECT THE GENERATOR MANUFACTURER
 SPECIFICATIONS AND CORRECT THE TOTAL BTU LOAD OF
 1,197,000 ON THE RESUBMITTAL.
  
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 5. THE SUBMITTED NOTICE OF COMMENCEMENT IS INCORRECT
 AND VOID. PLEASE PROVIDE A CURRENT NOTICE OF
 COMMENCEMENT RECORDED WITH THE CLERK OF THE COURT.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-28 Cont ID  
Sent By spalmer Date 2007-03-28 Time 17:19 Rev Time 0.00
Received By spalmer Date 2007-03-28 Time 17:19 Sent To E
Notes
2007-03-28 17:20:03TO ELEC BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 13:01 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 13:01 Sent To E
Notes
2007-03-06 13:02:17TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 18:05 Sent To  
Notes
2007-02-22 18:05:19TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-03-15 Cont ID  
Sent By tgordon Date 2007-03-15 Time 08:39 Rev Time 0.25
Received By tgordon Date 2007-03-15 Time 08:38 Sent To G
Notes
2007-03-15 08:40:36*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURER'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-03-29 Cont ID  
Sent By mcruz Date 2007-03-29 Time 14:44 Rev Time 0.00
Received By mcruz Date 2007-03-29 Time 14:44 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-02 Cont ID  
Sent By mcruz Date 2007-03-02 Time 12:57 Rev Time 0.00
Received By mcruz Date 2007-03-29 Time 14:43 Sent To I
Notes
2007-03-02 12:57:08PLANNING & ZONING: ** FAILED**
  
 1.PLEASE PROVIDE RESPONSE IN WRITING.
  
 2.PROVIDE A LETTER FROM THE IBIS HOME OWNERS
 ASSOCIATION (HOA) AND/OR ARCHITECTURAL REVIEW BOARD
 ALLOWING THE INSTALLATION OF THE GENERATOR ON THE SIDE
 OF THE PROPERTY. PLEASE ENSURE THE LETTER SPECIFICALLY
 ADDRESSES THE LOCATION OF THE EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 MARGARITA CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 561-822-1444