Plan Review Details - Permit 07020476
Plan Review Stops For Permit 07020476
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2008-02-08 Cont ID  
Sent By mperson Date 2008-02-08 Time 13:32 Rev Time 0.00
Received By mperson Date 2008-02-08 Time 13:32 Sent To PC
Notes
2008-02-08 13:35:46REVISION: "OK" CHANGED LAYOUT AND ADDED GENERATOR.
 REFERENCE GEN/RES PERMIT #07110219.
  
 ****************PROVISO****************
 A} PER FBC-2004 FUEL GAS, SECTION 404.8 PROTECTION
 AGAINST CORROSION: METALLIC PIPE EXPOSED TO CORROSIVE
 ACTION, SUCH AS SOIL CONDITION OR MOISTURE SHALL BE
 PROTECTED IN AN APPROVED MANNER.
 B} PER FBC-2004 FUEL GAS, SECTION 404.8.2 PROTECTIVE
 COATINGS AND WRAPPING: PIPE PROTECTIVE COATINGS AND
 WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND
 SHALL BE FACTORY APPLIED.
 C} PER FBC-2004 FUEL GAS, SECTION 404.11 PIPING
 UNDERGROUND BENEATH BUILDINGS: PIPING INSTALLED
 UNDERGROUND BENEATH BUILDINGS IS PROHIBITED EXCEPT
 WHERE THE PIPING IS SLEEVED IN ACCORDANCE WITH THIS
 SECTION.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGSREQUIRED
 PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,900 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-10-19 Cont ID  
Sent By mperson Date 2007-10-19 Time 11:58 Rev Time 0.00
Received By mperson Date 2007-10-19 Time 11:58 Sent To PC
Notes
2007-10-19 13:08:25REVISION DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE GAS REVISION WITH THE ADDED GENERATOR IS
 DENIED. THE REFERENCED MASTER PERMIT #06020782 DOES NOT
 HAVE AN APPROVED GENERATOR. A SEPERATE GEN/RES PERMIT
 IS REQUIRED FOR THE PROPOSED GENERATOR. PLEASE
 REFERENCE THE ATTACHED "CITY OF WEST PALM BEACH
 RESIDENTIAL GENERATOR PLAN REVIEW" REQUIREMENTS TO THE
 DENIED GAS COMMENTS FOR THE RESUBMITTAL.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE REVISED DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-03-06 Cont ID  
Sent By mperson Date 2007-03-06 Time 11:18 Rev Time 0.33
Received By mperson Date 2007-03-06 Time 11:18 Sent To PC
Notes
2007-03-06 11:29:48****************PROVISO****************
 A} PER FBC-2004 FUEL GAS, SECTION 404.8 PROTECTION
 AGAINST CORROSION: METALLIC PIPE EXPOSED TO CORROSIVE
 ACTION, SUCH AS SOIL CONDITION OR MOISTURE SHALL BE
 PROTECTED IN AN APPROVED MANNER.
 B} PER FBC-2004 FUEL GAS, SECTION 404.8.2 PROTECTIVE
 COATINGS AND WRAPPING: PIPE PROTECTIVE COATINGS AND
 WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND
 SHALL BE FACTORY APPLIED.
 C} PER FBC-2004 FUEL GAS, SECTION 404.11 PIPING
 UNDERGROUND BENEATH BUILDINGS: PIPING INSTALLED
 UNDERGROUND BENEATH BUILDINGS IS PROHIBITED EXCEPT
 WHERE THE PIPING IS SLEEVED IN ACCORDANCE WITH THIS
 SECTION.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGSREQUIRED
 PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,900 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-02-26 Cont ID  
Sent By mperson Date 2007-02-26 Time 14:32 Rev Time 0.45
Received By mperson Date 2007-02-26 Time 14:32 Sent To PC
Notes
2007-02-26 14:58:26DENIED
 REFERENCE: FBC-2004 FUEL GAS; CITY OF WEST PALM BEACH
 GAS PERMIT APPLICATION REQUIREMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE INDICATE THE BTU LOAD OF EACH APPLIANCE AND
 THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: PLEASE INDICATE THE BTU LOADS OF THE APPLIANCES
 ON THE RESUBMITTAL.
  
 2. PLEASE INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: CLEARLY INDICATE THE DELIVERY PRESSURE ON THE
 RESUBMITTAL. THERE ARE TWO DELIVERY PRESSURES INDICATED
 ON THE SUBMITTED DRAWINGS, ONE IS 21 LB AND THE OTHER
 IS O.5 PSI, PLEASE CLARIFY ON THE RESUBMITTAL WITH ONLY
 INDICATING ONE DELVERY PRESSURE.
  
 3. PLEASE CLEARLY INDICATE ON THE RESUBMITTAL IF THE
 GAS PIPING IS ABOVE GROUND OR UNDERGROUND, AND WHAT GAS
 PIPING IS EXISTING OR NEW.
  
 ******IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-09 Cont ID  
Sent By adarroug Date 2007-10-09 Time 16:53 Rev Time 0.00
Received By adarroug Date 2007-10-09 Time 16:53 Sent To G
Notes
2007-10-09 16:53:57TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-01 Cont ID  
Sent By adarroug Date 2007-03-01 Time 13:33 Rev Time 0.00
Received By adarroug Date 2007-03-01 Time 13:33 Sent To G
Notes
2007-03-01 13:34:20TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-26 Cont ID  
Sent By mperson Date 2007-02-26 Time 14:58 Rev Time 0.00
Received By mperson Date 2007-02-21 Time 10:16 Sent To  
Notes
2007-02-21 10:16:44TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved