|
 |
 |
 |
 |
 |
Plan Review Details - Permit 07020476
Plan Review Stops For Permit 07020476 |
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
P |
Date |
2008-02-08 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2008-02-08 |
Time |
13:32 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2008-02-08 |
Time |
13:32 |
Sent To |
PC |
|
Notes |
2008-02-08 13:35:46 | REVISION: "OK" CHANGED LAYOUT AND ADDED GENERATOR. | | REFERENCE GEN/RES PERMIT #07110219. | | | | ****************PROVISO**************** | | A} PER FBC-2004 FUEL GAS, SECTION 404.8 PROTECTION | | AGAINST CORROSION: METALLIC PIPE EXPOSED TO CORROSIVE | | ACTION, SUCH AS SOIL CONDITION OR MOISTURE SHALL BE | | PROTECTED IN AN APPROVED MANNER. | | B} PER FBC-2004 FUEL GAS, SECTION 404.8.2 PROTECTIVE | | COATINGS AND WRAPPING: PIPE PROTECTIVE COATINGS AND | | WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND | | SHALL BE FACTORY APPLIED. | | C} PER FBC-2004 FUEL GAS, SECTION 404.11 PIPING | | UNDERGROUND BENEATH BUILDINGS: PIPING INSTALLED | | UNDERGROUND BENEATH BUILDINGS IS PROHIBITED EXCEPT | | WHERE THE PIPING IS SLEEVED IN ACCORDANCE WITH THIS | | SECTION. | | | | IF DRYER ROOM IS A CONFINED SPACE, OPENINGSREQUIRED | | PER SECTION 304.5 OR | | SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | IF WATER HEATER ROOM IS A CONFINED | | SPACE, OPENINGS REQUIRED PER SECTION | | 304.5 OR SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,900 CUBIC FEET REQUIRED. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2007-10-19 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-10-19 |
Time |
11:58 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-10-19 |
Time |
11:58 |
Sent To |
PC |
|
Notes |
2007-10-19 13:08:25 | REVISION DENIED | | REFERENCE: | | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | REQUIREMENTS. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | ** FLORIDA ADMINISTRATIVE CODE (FAC). | | ** FLORIDA STATUTES (FS). | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | 1. THE GAS REVISION WITH THE ADDED GENERATOR IS | | DENIED. THE REFERENCED MASTER PERMIT #06020782 DOES NOT | | HAVE AN APPROVED GENERATOR. A SEPERATE GEN/RES PERMIT | | IS REQUIRED FOR THE PROPOSED GENERATOR. PLEASE | | REFERENCE THE ATTACHED "CITY OF WEST PALM BEACH | | RESIDENTIAL GENERATOR PLAN REVIEW" REQUIREMENTS TO THE | | DENIED GAS COMMENTS FOR THE RESUBMITTAL. | | | | ******IMPORTANT INFORMATION****** | | AS OF 8/25/06 GENERATOR (GEN/RES AND | | GEN/COM) PERMIT APPLICATIONS SHALL NOT | | BE ACCEPTED UNLESS THE ELECTRICAL INFOR- | | MATION AND GAS (OR DIESEL) INFORMATION | | IS ALL SUBMITTED AT THE SAME TIME. THE | | GENERATOR, ELECTRICAL AND GAS/DIESEL IN- | | FORMATION WILL BE ROUTED TOGETHER. THIS | | WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY | | THE MANUFACTURER'S SPECI- | | FICATIONS AND INSTALLATION INSTRUCTIONS) | | ARE AVAILABLE TO ALL PLAN REVIEWERS. | | | | 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | THE REVISED DRAWING SHALL CLEARLY PRINT AND SIGN | | NAME, AND ALSO DATE DRAWING. PLEASE DO | | THIS PRIOR TO RESUBMITTING. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2007-03-06 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-03-06 |
Time |
11:18 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2007-03-06 |
Time |
11:18 |
Sent To |
PC |
|
Notes |
2007-03-06 11:29:48 | ****************PROVISO**************** | | A} PER FBC-2004 FUEL GAS, SECTION 404.8 PROTECTION | | AGAINST CORROSION: METALLIC PIPE EXPOSED TO CORROSIVE | | ACTION, SUCH AS SOIL CONDITION OR MOISTURE SHALL BE | | PROTECTED IN AN APPROVED MANNER. | | B} PER FBC-2004 FUEL GAS, SECTION 404.8.2 PROTECTIVE | | COATINGS AND WRAPPING: PIPE PROTECTIVE COATINGS AND | | WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND | | SHALL BE FACTORY APPLIED. | | C} PER FBC-2004 FUEL GAS, SECTION 404.11 PIPING | | UNDERGROUND BENEATH BUILDINGS: PIPING INSTALLED | | UNDERGROUND BENEATH BUILDINGS IS PROHIBITED EXCEPT | | WHERE THE PIPING IS SLEEVED IN ACCORDANCE WITH THIS | | SECTION. | | | | IF DRYER ROOM IS A CONFINED SPACE, OPENINGSREQUIRED | | PER SECTION 304.5 OR | | SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | IF WATER HEATER ROOM IS A CONFINED | | SPACE, OPENINGS REQUIRED PER SECTION | | 304.5 OR SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,900 CUBIC FEET REQUIRED. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2007-02-26 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-02-26 |
Time |
14:32 |
Rev Time |
0.45 |
Received By |
mperson |
Date |
2007-02-26 |
Time |
14:32 |
Sent To |
PC |
|
Notes |
2007-02-26 14:58:26 | DENIED | | REFERENCE: FBC-2004 FUEL GAS; CITY OF WEST PALM BEACH | | GAS PERMIT APPLICATION REQUIREMENTS; | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN | | REVIEW TO MEET CODE COMPLIANCE: | | | | 1. PLEASE INDICATE THE BTU LOAD OF EACH APPLIANCE AND | | THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | NOTE: PLEASE INDICATE THE BTU LOADS OF THE APPLIANCES | | ON THE RESUBMITTAL. | | | | 2. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | NOTE: CLEARLY INDICATE THE DELIVERY PRESSURE ON THE | | RESUBMITTAL. THERE ARE TWO DELIVERY PRESSURES INDICATED | | ON THE SUBMITTED DRAWINGS, ONE IS 21 LB AND THE OTHER | | IS O.5 PSI, PLEASE CLARIFY ON THE RESUBMITTAL WITH ONLY | | INDICATING ONE DELVERY PRESSURE. | | | | 3. PLEASE CLEARLY INDICATE ON THE RESUBMITTAL IF THE | | GAS PIPING IS ABOVE GROUND OR UNDERGROUND, AND WHAT GAS | | PIPING IS EXISTING OR NEW. | | | | ******IMPORTANT INFORMATION | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | PLEASE REPLACE ONLY SHEETS | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | IN RED INK FOR REFERENCE FOR | | RESUBMITTAL. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-10-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-09 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-09 |
Time |
16:53 |
Sent To |
G |
|
Notes |
2007-10-09 16:53:57 | TO "G" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-03-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-01 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-01 |
Time |
13:33 |
Sent To |
G |
|
Notes |
2007-03-01 13:34:20 | TO "G" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-02-26 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-02-26 |
Time |
14:58 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-02-21 |
Time |
10:16 |
Sent To |
|
|
Notes |
2007-02-21 10:16:44 | TO "G" BOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |