Plan Review Details - Permit 07020467
Plan Review Stops For Permit 07020467
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-11-14 Cont ID  
Sent By amorse Date 2007-11-14 Time 18:49 Rev Time 0.00
Received By amorse Date 2007-11-14 Time 18:49 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2007-10-11 Cont ID  
Sent By amorse Date 2007-10-11 Time 18:42 Rev Time 0.00
Received By amorse Date 2007-10-11 Time 18:42 Sent To PC
Notes
2007-10-11 18:54:39 
  
 DENIED
  
 1)SUBMIT TWO COPIES OF CORRECTED ENERGY CALC'S PER
 13-101.2.2 FBC. BE SURE THAT THEY ARE SIGNED AND DATED
 BY PREPARER AND OWNER/AGENT PRIOR TO SUBMITTAL. PLEASE
 NOTE THAT WALL ASSEMBLY FOR COMBINED VALUE IS NOT
 PERMITTED SEE 13-602.1.ABC.I WALL INSULATION AND
 13-C1.2 BUILDING ENVELOPE INSULATION FOR RESIDENTIAL
 COMPLIANCE METHODS (R-VALUES OF STRUCTURAL BUILDING
 COMPONENTS SHALL NOT BE INCLUDED)
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-21 Cont ID  
Sent By amorse Date 2007-08-21 Time 18:52 Rev Time 0.00
Received By amorse Date 2007-08-21 Time 18:52 Sent To PC
Notes
2007-08-21 19:01:58 
  
 DENIED
  
 1)PLEASE HAVE RAR SIGN AND SEAL THE ROOFING
 CALCULATIONS THAT WERE PROVIDED. ALSO HAVE THE NOA #
 CHANGED TO MATCH THE NEW PRODUCT APPROVAL REQUIRED IN
 COMMENT #2.
  
 2)THE STATE HAS NOT UPDATED THE PRODUCT APPROVAL FOR
 TAMKO MODIFIED ROOFING SYSTEMS AND THE NOA HAS EXPIRED,
 PLEASE PROVIDE 2 COPIES OF THE REVISED MIAMI-DADE
 REPORT # 07-0111.03 THE PAGES 6 & 7 OF 19 ARE THE SAME
 SYSTEM THAT WAS SUBMITTED ON THE OLD PRODUCT APPROVALS.
 THE MIAMI-DADE REPORT WILL THEN BE GIVEN LOCAL PRODUCT
 APPROVAL FOR USE.
  
 3)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN
 THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING,
 THE NOTICE IS VOID
  
 4)THE COPIES OF THE TRUSS ENGINEERING WERE NOT
 RESUBMITTED, THEY ARE NOT REQUIRED BEFORE A PERMIT IS
 ISSUED BUT ARE REQUIRED BEFORE TRUSSES ARE SET.
  
 5)OLD DRAWINGS CAN BE REMOVED FOR RESUBMITTAL BUT BE
 SURE TO INSERT PAGES WITH THE IMPACT FEE STAMP ON THEM
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-23 Cont ID  
Sent By amorse Date 2007-06-23 Time 14:13 Rev Time 0.00
Received By amorse Date 2007-06-23 Time 14:13 Sent To PC
Notes
2007-06-23 14:14:40 
  
 DENIED
  
 THE FOLLOWING REVIEW COMMENTS WERE NOT COMPLETELY
 ADDRESSED:
  
 5)PROVIDE 2 COPIES OF CURRENT SURVEY SHOWING PROPOSED
 WORK AND ALL REQUIRED SETBACKS. ****NOTE SURVEY AND
 SITE PLAN DO NOT MATCH SEE ZONING REVIEW COMMENTS****
  
 6)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. ****REQUIRES CORRECTIONS SEE MECHANICAL
 REVIEW COMMENTS, ALSO CLARIFY R11 ON ENERGY CALC'S AND
 R4.7 ON DRAWINGS****
  
 9)THE FOLLOWING STRUCTURAL DETAILS REQUIRE
 CORRECTION;
 B) PLAN S-2 THE SECTIONS LABELED A/S7 SHOULD BE THE
 TYPICAL TRUSS BEARING DETAIL A/S6. ****NOT
 CORRECTED****
 E) PROVIDE SCHEDULE FOR PRE CAST LINTEL THAT WILL BE
 USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC.
 ****NOA # ON SCHEDULE IS OLD PLEASE USE THE REVISED #
 FROM PRODUCT APPROVALS****
  
 15)THE FOLLOWING CORRECTION ARE REQUIRED FOR THE
 PRODUCT APPROVALS:
 B) PROVIDE THE ROOF SYSTEM FROM THE MODIFIED PRODUCT
 APPROVAL THAT WILL BE USED. *****PROVIDE CALCULATIONS
 FROM RAS 117 PER LIMITATION #7 OF THE NOA, PLEASE NOTE
 THAT NOA USES 12" O/C AT THE 4" LAP AND 2 ROWS AT 12"
 O/C IN MIDDLE. SEEMS EXTREME AT 4" O/C EACH WAY WITH 3"
 PLATES****
  
 NEW
  
 1)TRUSS ENGINEERING IS INCOMPLETE, PROVIDE INDIVIDUAL
 TRUSSES WITH UPLIFT VALUES AT CONNECTION POINTS, THESE
 DO NOT REQUIRE INDIVIDUAL SIGN AND SEAL AS LONG AS
 THERE IS A SIGNED AND SEALED COVER PAGE THAT LISTS THE
 PAGES. ALSO THE WIND DESIGN IS INCORRECT AND DOES NOT
 MATCH THE ARCHITECTURAL AND STRUCTURAL DRAWINGS AND TOP
 AND BOTTOM DEAD LOADS SHALL ALSO MATCH STRUCTURAL
 DRAWINGS.
  
 2)REMOVE MULLION PRODUCT APPROVALS AS NONE ARE SHOWN
 ON THE DRAWINGS. WINDOWS 2A & 2B AND 2L & 2M SHOW
 STRUCTURAL STEEL BETWEEN AND DO NOT REQUIRE MULLIONS.
  
 3)PROVIDE INDIVIDUAL WINDOW DESIGN PRESSURES, IF WE
 USE THE CHART FOR THIS ON S/8, PLAN REVIEW DOES NOT
 INTERPOLATE THEREFORE THE CASEMENT WINDOWS 5050 THAT
 ARE IN THE END ZONE WILL NOT MEET THE DESIGN PRESSURE
 OR A STRONGER GLAZING TYPE MUST BE USED FROM THE
 CHOICES IN THE PRODUCT APPROVAL.
  
 4)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID, PLEASE RE-RECORD THIS CAN BE DONE AT TIME OF
 FINAL PERMIT PICKUP
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-14 Cont ID  
Sent By amorse Date 2007-04-14 Time 06:06 Rev Time 0.00
Received By amorse Date 2007-04-14 Time 06:06 Sent To PC
Notes
2007-04-14 07:36:04 
  
 DENIED
  
  
 1)BEFORE FURTHER PLAN REVIEW ALL FEES DUE ARE
 REQUIRED TO BE PAID IN FULL.
  
 2)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE
 OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2
 COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER
 R401.4 BC RES.
  
 3)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R401.3 BC RES. BE
 SURE TO CREATE SWALES SO NOT TO DRAIN ON TO ADJACENT
 PROPERTY
  
 4)PROVIDE NOTE ON DRAWINGS THAT TERMITE TREATMENT IS
 REQUIRED ON ALL EXTERIOR CONCRETE WITHIN 1 FOOT OF
 PRIMARY STRUCTURE PER 1816.1.6 OR R320.1.6 FBC
  
 5)PROVIDE 2 COPIES OF CURRENT SURVEY SHOWING PROPOSED
 WORK AND ALL REQUIRED SETBACKS
  
 6)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PRUEPARER AND OWNER/AGENT PRIOR
 TO SUBMITTABLE
  
 7)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES.
  
 8)ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME,
 ADDRESS, AND LICENSE NUMBER ON EACH SHEET THAT BEARS
 THEIR SEAL PER
 61G15-23.002(2)PLEASE NOTE ENGINEER IS REQUIRED TO
 SIGN NOT USE STAMP PER FBPE
  
 9)THE FOLLOWING STRUCTURAL DETAILS REQUIRE
 CORRECTION;
  
 A) THE TIE BEAM AND CB 16 BEAMS ON SECTION 07/S7 ARE
 NOT DESIGNATED ON PLAN S-2
 B) PLAN S-2 THE SECTIONS LABELED A/S7 SHOULD BE THE
 TYPICAL TRUSS BEARING DETAIL A/S6
 C) PROVIDE DETAIL OF KNEE WALL ATTACHMENT TO ROOF
 TRUSSES
 D) MAKE CORRECTIONS FOR SECTIONS ON S-3
 E) PROVIDE SCHEDULE FOR PRE CAST LINTEL THAT WILL BE
 USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC
  
 10)PLEASE NOTE THAT ROUGH OPENING SIZES IN THE DOOR
 AND WINDOW SCHEDULES DO NOT ACCOUNT FOR THE ARCHED
 TRANSOMS
  
 11)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA
 STATE APPROVAL COVER PAGES, AND THE PRODUCT NOAH THAT
 LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE
 PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND
 THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG
  
 12)THOSE PRODUCTS WHICH ARE REGULATED BY DC RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 13 )THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 14)THE FOLLOWING PRODUCT APPROVALS WERE NOT
 SUBMITTED, PRECAST LINTELS, ENTRY DOORS, CASEMENT
 WINDOWS AND MULLIONS
  
 15)THE FOLLOWING CORRECTION ARE REQUIRED FOR THE
 PRODUCT APPROVALS:
 A) PROVIDE THE MODEL FOR THE GARAGE DOOR (NOT ALL
 MODELS MEET THE DESIGN PRESSURE)
 B) PROVIDE THE ROOF SYSTEM FROM THE MODIFIED PRODUCT
 APPROVAL THAT WILL BE USED
 C) PLEASE NOTE THE ATTACHMENT METHODS IN THE ROOF TILE
 PRODUCT APPROVAL ONLY SEVERAL WILL WORK IF YOU ARE
 USING POLYFOAM A PRODUCT APPROVAL IS REQUIRED
 D) FOR YOUR INFORMATION I HAVE ATTACHED THE FLORIDA
 COVER SHEETS TO THE PRODUCT APPROVAL FOR THE PGT FRENCH
 DOORS (THESE ARE REQUIRED FOR ALL PRODUCT APPROVALS)
  
  
  
  
  
 16)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-04 Cont ID  
Sent By dpalmer Date 2007-06-04 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2007-06-03 Time 16:30 Sent To M
Notes
2007-06-04 07:48:18** PROVISO **
  
 ** REVISION REQUIRED WITHIN30 DAYS OF ISSUANCE OF
 PERMIT.
  
 1) NOTE: PLEASE SEE AS STATED ON THE PREVIOUS REVIEW,
 WHEN THE AMOUNT OF DECORATIVE AND/OR RECESSED LIGHTING
 EXCEEDS THAT OF THE NORMAL 3VA PER SQ FT, THEN THE
 HIGHER AMOUNT SHALL BE FIGURED. PLEASE SEE THAT THE
 WATTAGE BASED ON THE AMOUNT OF EACH OF THESE TYPES OF
 FIXTURES DO EXCEED THE 3VA PER SQ FT.THIS WAS
 CONFIRMED BY THE CODE PANELIST AND THE AHJ IS THE
 DETERMINING AUTHORITY.PLEASE SEE THE FOLLOWING TEXT
 WHICH IS TAKEN DIRECTLY FROM THE 2005 NEC.
  
 *D) LUMINAIRES (LIGHTING FIXTURES) AN OUTLET SUPPLYING
 LUMINAIRE(S) [LIGHTING FIXTURE(S)] SHALL BE CALCULATED
 BASED ON THE MAXIMUM VOLT-AMPERE RATING OF THE
 EQUIPMENT AND LAMPS FOR WHICH THE LUMINAIRE(S)
 [FIXTURE(S)] IS RATED.
 IN GENERAL, NO ADDITIONAL CALCULATION IS REQUIRED FOR
 LUMINAIRES (RECESSED AND SURFACE MOUNTED) INSTALLED IN
 OR ON A DWELLING UNIT, BECAUSE THE LOAD OF SUCH
 LUMINAIRES IS COVERED IN THE 3 VOLT-AMPERES PER SQUARE
 FOOT CALCULATION SPECIFIED BY TABLE 220.12. WHERE THE
 RATING OF THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING
 EXCEEDS THE MINIMUM LOAD PROVIDED FOR IN TABLE 220.12,
 THE MINIMUM GENERAL LIGHTING LOAD FOR THAT PREMISES IS
 TO BE BASED ON THE INSTALLED LUMINAIRES. DISTINGUISHING
 BETWEEN THE LUMINAIRES INSTALLED FOR GENERAL LIGHTING
 VERSUS THOSE INSTALLED FOR ACCENT, SPECIALTY OR DISPLAY
 LIGHTING IS MUCH EASIER TO DELINEATE IN COMMERCIAL
 (PARTICULARLY MERCANTILE) OCCUPANCIES.
  
 AS STATED, *IN GENERAL* AN ADDITIONAL AMOUNT IS NOT
 NEEDED ONLY WHEN THE FIXTURES ARE USED FOR NORMAL
 GENERAL LIGHTING. WHEN THE FIXTURES EXCEED THE GENERAL
 LIGHTING USE AS THIS IS DONE ON THIS PLAN, THEN THE
 ADDITIONAL SHALL BE FIGURED.
 THIS REVIEW IS BEING PASSED AS THE SERVICE IS KNOWN TO
 BE OF SUFFICIENT SIZE HOWEVER RECORD PLANS ARE TO BE
 CORRECTED FOR CODE COMPLIANCE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-03 16:31:11IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 17:58 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 17:14 Sent To M
Notes
2007-03-04 17:58:43 
 ** UNSAT **
  
 1) NOTE: 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION
 HAS BEEN SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH
 PLACES PROJECTS UNDER THE NEW CODES ADOPTED BY THE
 STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72 (DONE)
 2003 NFPA-101(DONE)
  
 2) NOTE: PLEASE SEE LOAD CALCULATIONS AS THERE ARE
 SEVERAL CODE SECTIONS REFLECTED FROM THE 2002 CODE
 WHICH ARE NO LONGER ACCURATE.
  
 3) NOTE: PLEASE CORRELATE ALL OF THE SMALL APPLIANCE
 CIRCUITS AND THE CIRCUITS OF THE LIKE WHICH ARE
 REQUIRED TO BE FIGURED INTO THE LOAD CALCULATIONS.
 PLEASE SEE 210.52B1, 210.11C1, AND 220.52A.
 PLEASE SEE PLANS INDICATE MORE THAN THE FOUR FIGURED
 AND SHOWN.
  
 4) NOTE: PLEASE CORRELATE RISER AND PLANS. PLEASE SEE
 PLANS INDICATE PANEL *B* AS BEING ON THE GROUND FLOOR,
 YET THE RISER SHOWS PANEL *B* UPSTAIRS AND COORDINATE
 WITH PANEL *C*.
  
 5) NOTE: PLEASE CORRELATE THE FOLLOWING.
 PLEASE CORRELATE PANEL *B* AS PANEL *B* ON RISER SHOWS
 THIS AS 100AMPS AND PANEL *B* SCHEDULE SHOWS THIS AS
 150AMPS.
 PLEASE SEE RISER AND PANEL SCHEDULE FOR THE SAME FOR
 PANEL *C*.
 PLEASE SEE RISER AND PANEL SCHEDULE FOR PANEL *A* WHICH
 SHOWS ONE AS 400A MLO AND THE OTHER AS 300A MLO. PLEASE
 CORRELATE ALL OF THE ABOVE.
 FBC 106.1.2 , 106.3.5.4
  
 6) NOTE: PLEASE CORRELATE LOAD FOR DISHWASHER(S) ON
 LOAD CALCULATIONS AND THE LOAD AS SHOWN ON PANEL
 SCHEDULE. PLEASE SEE THE AMPERAGE AS SHOWN ON PANEL
 DOES NOT FIGURE FOR THE LOAD IN KVA AS SHOWN IN
 CALCULATIONS.
 220.
 FBC 106.3.5.4
  
 7) NOTE: PLEASE SEE THE LOAD FOR THE DISPOSAL WHICH
 ALSO DOES NOT CORRELATE WITH THE VA ON LOAD
 CALCULATIONS AS LOAD ON PANEL SCHEDULE ONLY SHOWS 1AMP
 LOAD?
 220.
 FBC 106.3.5.4
  
 8) NOTE: PLEASE SEE RISER FOR GROUNDING ELECTRODE
 SYSTEM SHOWS ATTACHMENT TO *BLDG STEEL* WHICH IS OK AND
 REQUIRED IF * BLDG STEEL* IS PRESENT. PLEASE INCLUDE
 *FOOTER STEEL* AS REQUIRED PER 250.50.
  
 9) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE
 SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS
 SMOKE DETECTORS.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY
 THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 10) NOTE: PLEASE KNOW THAT IN NO CASE MAY *STICKERS* OF
 ANY KIND BE PLACED ON PLANS.
 PLEASE REVISE PLANS TO CORRECT THE ISSUE AS TO WHY THE
 LABELS WERE PLACED ON SHEETS.
 106.3.1 ADMIN SECTION.
 FS 471.025
  
 11) NOTE: PLEASE SEE THAT THE RECESSED LIGHTING IN THE
 NUMBER AS SHOWN ON PLANS MUST BE BASED ON THE NUMBER OF
 FIXTURES AND MAXIMUM WATTAGE PER FIXTURE. PLEASE SEE
 THE PREVIOUS CODE 2002 WHICH IS SECTION 220.3B4. PLEASE
 SEE 220.14/220.12.
 PLEASE KNOW THIS WAS CONFIRMED AT THE SOUTHERN SECTION
 MEETING AND BROUGHT FORTH TO THE CODE PANELIST. WHEN A
 CONSIDERABLE NUMBER OF RECESSED FIXTURES OR OTHER
 FIXTURES ARE SHOWN THEN THE LOADS NEED TO BE SHOWN IN
 ADDITION TO THE GENERAL LIGHTING LOADS FIGURED.
  
 12) NOTE: PLEASE BE SURE TO STATE THE TYPE OF RECESSED
 LIGHTING FIXTURE TO BE USED FBC 13-606.1.ABC.1.2.4.
 THIS IS TO ALLEVIATE THE AIR MOVEMENT FROM CONDITIONED
 SPACE ETC.
  
 13 NOTE: PLEASE SEE THAT THE TRUSS PLANS AND
 ENGINEERINF CONTAINS A *RUBBER STAMP* INSTEAD OF THE
 REQUIRED ORIGINAL SIGNATURE FROM THE ENGINEER OF RECORD
 AS SHOWN. THIS IS REQUIRED PER FAC 61G15-23.002 AND FS
 471.025
 THIS IS ALSO REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
 THIS COMMENT IS NOT FOR THE DEISGNER OF THE ELECTRICAL
 PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-06-20 Cont ID  
Sent By mperson Date 2007-06-20 Time 10:54 Rev Time 0.45
Received By mperson Date 2007-06-20 Time 10:54 Sent To B
Notes
2007-06-20 11:02:40****************PROVISO****************
 GAS SYSTEM PER FBC-2004 FUEL GAS
 TABLES: 402.4(2) AND 402.4(20).
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGS
 REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 4,000 CUBIC FEET REQUIRED.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By mperson Date 2007-03-12 Time 09:19 Rev Time 0.45
Received By mperson Date 2007-03-12 Time 09:19 Sent To B
Notes
2007-03-12 09:52:54DENIED
 REFERENCE: FBC-2004 FUEL GAS; THE CITY OF WEST PALM
 BEACH GAS PERMIT APPLICATION REQUIREMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: NOT ALL
 CORRESPONDING LENGTHS ARE INDICATED. THE LONGEST LENGTH
 IS BEING INDICATED IS 88' BUT THE ADDED SUM OF THE
 INDICATED CORRESPONDING LENGTHS EQUALS 77'-6". PLEASE
 CORRECT AND CORRELATE ON THE RESUBMITTAL.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: THE ONLY
 INDICATED PIPING MATERIAL BEING USED IS PE FOR THE
 UNDERGROUND. ALL PIPING MATERIALS MUST BE INDICATED ON
 THE RESUBMITTAL. IF THE GAS TYPE IS NATURAL GAS WITH A
 DELIVERY PRESSURE OF 0.5 PSI PLEASE NOTE THE RED LINE
 CORRECTIONS TO THE GAS PIPE SIZES. PLEASE REFERENCE THE
 ATTACHED GAS SIZING TABLES TO THE GAS COMMENTS
 INDICATING THIS. PLEASE CORRECT AND RESUBMIT.
  
 3. SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: THE TYPE OF
 GAS BEING USED SHALL BE CLEARLY INDICATED AS, (LP) OR
 (NATURAL). PLEASE CORRECT ON THE RESUBMITTAL.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: THE TOTAL
 BTU'S ARE NOT CLEARLY INDICATED AND ARE BEING INDICATED
 WRONG AS 3?0,000. THE TOTAL SUM OF THE BTU'S SHOULD BE
 410,000. PLEASE CORRECT ON THE RESUBMITTAL.
 ********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-02-16 Cont ID  
Sent By ssherman Date 2007-02-16 Time 10:51 Rev Time 0.00
Received By ssherman Date 2007-02-16 Time 10:51 Sent To  
Notes
2007-02-16 10:51:21HISTORICAL APPROVAL PER FRIEDERIKE MITTNER

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 14:29 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 14:29 Sent To M
Notes
2007-11-08 14:29:41TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-04 Cont ID  
Sent By adarroug Date 2007-10-04 Time 14:53 Rev Time 0.00
Received By adarroug Date 2007-10-04 Time 14:53 Sent To Z
Notes
2007-10-04 14:53:50TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-08 Cont ID  
Sent By dpalmer Date 2007-08-08 Time 18:48 Rev Time 0.00
Received By dpalmer Date 2007-08-08 Time 18:46 Sent To Z
Notes
2007-08-08 18:48:36TO ZONING INBOX.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-31 Cont ID  
Sent By adarroug Date 2007-05-31 Time 16:42 Rev Time 0.00
Received By adarroug Date 2007-05-31 Time 16:42 Sent To E
Notes
2007-05-31 16:42:34TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 11:14 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 11:14 Sent To Z
Notes
2007-05-29 11:14:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-03 Cont ID  
Sent By adarroug Date 2007-03-03 Time 15:17 Rev Time 0.00
Received By adarroug Date 2007-03-03 Time 15:17 Sent To E
Notes
2007-03-03 15:17:43TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-04-14 Time   Rev Time 0.00
Received By adarroug Date 2007-02-19 Time 14:36 Sent To  
Notes
2007-02-27 14:36:47TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-11-13 Cont ID  
Sent By tgordon Date 2007-11-13 Time 13:40 Rev Time 0.30
Received By tgordon Date 2007-11-13 Time 13:40 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-10-10 Cont ID  
Sent By tgordon Date 2007-10-10 Time 13:51 Rev Time 0.35
Received By tgordon Date 2007-10-10 Time 13:51 Sent To B
Notes
2007-10-10 14:00:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
  
 1) SEE ATTACHED PRINTED ARI LISTING FOR ARI REFERENCE
 #1106086 AND #1106536 DO NOT MATCH THE MODEL NUMBERS ON
 THE A.C. SCHEDULE ON PLAN M-3.AS NOTED IN LAST TWO
 REVIEWS 6/8/07 AND 8/13/07 PLEASE CORRECT EQUIPMENT
 MODEL NUMBERS ON PLAN PAGE M-3 A/C SCHEDULE. SEE 2004
 FBC 13-607.1.ABC.3.1.
  
 2) SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-08-13 Cont ID  
Sent By tgordon Date 2007-08-13 Time 09:23 Rev Time 0.30
Received By tgordon Date 2007-08-13 Time 09:23 Sent To B
Notes
2007-08-13 09:55:56PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
  
 1) PLEASE CORRECT EQUIPMENT MODEL NUMBERS ON PLAN PAGE
 M-3 A/C SCHEDULE, SEE ARI CERTICATE (MODEL #2TWB3060A1,
 2TEC3F60B1 AND 2TWX4048B1, 2TEC3F48B1) DO NOT USE WHITE
 OUT, PEN, OR PENCIL.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-08 Cont ID  
Sent By tgordon Date 2007-06-08 Time 16:06 Rev Time 0.45
Received By tgordon Date 2007-06-08 Time 16:06 Sent To P
Notes
2007-06-08 16:15:40*** DENIED ***
 1) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S FOR A/C SYSTEMS, EQUIPMENT LISTED ON
 MECHANICAL PLANS COULD NOT BE FOUND ON THE ARI
 DIRECTORY. PLEASE BE AWARE THE ENERGY CALCULATIONS ARE
 CALLING FOR HEAT PUMP UNITS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-05 Cont ID  
Sent By tgordon Date 2007-03-05 Time 10:42 Rev Time 0.45
Received By tgordon Date 2007-03-05 Time 10:42 Sent To P
Notes
2007-03-05 10:57:12*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, PER 2004 FBC
 13-101.2.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR
 FIREPLACES AND GAS LOGS.
  
 3) PLEASE PROVIDE COMBUSTION AIR CALCULATIONS AND OR
 COMBUSTION AIR FOR GAS CLOTHS DRYER, SEE 2004 FBC/R
 M1701.1.
  
 4) THE LICENSE FOR RAR ARCHITECT INC. EXPIRED ON
 2-28-07, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-20 Cont ID  
Sent By mperson Date 2007-06-20 Time 10:46 Rev Time 0.45
Received By mperson Date 2007-06-20 Time 10:46 Sent To G
Notes
2007-06-20 10:54:26****************PROVISO****************
 PER FBC-2004 PLUMBING, SECTION 504.6.1, THE RELIEF
 VALVE DISCHARGE SHALL NOT HAVE ANY TRAPPED SECTIONS.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By mperson Date 2007-03-12 Time 08:38 Rev Time 1.25
Received By mperson Date 2007-03-12 Time 08:38 Sent To G
Notes
2007-03-12 09:19:03DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. A} SHEET P-1 KEY NOTE #6 INDICATES A 3" SANITARY
 RISER.
 B} SHEET P-2 KEY NOTE #1 INDICATES A 4" SANITARY
 DOWN.
 C} SHEET P-3 UNDERGROUND TO 2ND FLOOR RISER BEHIND
 1ST FLOOR LAUNDRY INDICATES A 3" SANITARY RISER. PLEASE
 CORRELATE SHEETS FOR RESUBMITTAL.
  
 2. SHEET P-4 ISOMETRIC WATER RISER DIAGRAM PLEASE ADD
 WATER HAMMER ARRESTORS AT THE TWO DISHWASHERS HOT WATER
 SUPPLY PIPES PER FBC-2004 PLUMBING, SECTION 604.9,
 WATER HAMMER ARRESTORS REQUIRED ON QUICK CLOSING
 VALVES. PLEASE ADJUST PLUMBING GENERAL NOTES #16 TO
 REFLECT THIS ON THE RESUBMITTAL.
  
 3. SHEET P-1 KEY NOTE #2 INDICATES UNDERGROUND WATER
 SUPPLY PIPE TO BE 1" GALVANIZED BUT SHEET P-5 PLUMBING
 GENERAL NOTES #11 INDICATES ALL UNDERGROUND WATER TO BE
 TYPE K COPPER. IS IT THE INTENT TO HAVE KEY NOTES OVER
 RIDE GENERAL NOTES. PLEASE CLARIFY OR CORRELATE ON THE
 RESUBMITTAL.
  
 4. SHEET P-3 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE
 INDICATE THE CLEANOUT FOR THE WASHING MACHINE AT FOUR
 FEET ABOVE FINNISH FLOOR (4' A.F.F.) PER FBC-2004
 PLUMBING SECTION, 708.7 MINIMUM SIZE AND 708.9 ACCESS.
  
 5. SHEET P-3 SANITARY ISOMETRIC RISER DIAGRAM: CLEARLY
 INDICATE THE CLEANOUT AT THE JUNCTION OF THE BUILDING
 DRAIN AND BUILDING SEWER AS BEING A TWO-WAY CLEANOUT
 PER FBC-2004 PLUMBING, SECTION 708.3.5 ON THE
 RESUBMITTAL.
  
 ********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 4 Status N Date 2007-10-04 Cont ID  
Sent By adavila Date 2007-10-04 Time 16:58 Rev Time 0.00
Received By adavila Date 2007-10-04 Time 16:58 Sent To I
Notes
2007-10-04 16:59:19USE SHEET SP-1 STAMPED BY ZONING.ES.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-08-10 Cont ID  
Sent By adavila Date 2007-08-10 Time 15:01 Rev Time 0.00
Received By adavila Date 2007-08-09 Time 08:39 Sent To M
Notes
2007-08-10 15:01:51PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-05-30 Cont ID  
Sent By adavila Date 2007-05-30 Time 15:33 Rev Time 0.00
Received By adavila Date 2007-05-29 Time 14:26 Sent To I
Notes
2007-05-30 15:39:29PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. SURVEY AND SITE PLAN SHALL REFLECT SAME ACTUAL
 CONDITIONS:
  
 A. ACCORDING TO THE SURVEY, THE DEPTH OF THE PROPERTY
 IS 119.97 FEET.HOWEVER, THE SITE PLAN SHOWS A LOT
 DEPTH OF 119.42 FEET.
  
 B. ACCORDING TO THE SURVEY, 3 FEET OF THE 6 FOOT
 UTILITY EASEMENT IS WITHIN THE PROPERTY ALONG THE NORTH
 PROPERTY LINE.HOWEVER, THE SITE PLAN SHOWS THE 6 FOOT
 UTILITY EASEMENT OUTSIDE THE SUBJECT PROPERTY.
  
 C. SURVEY SHOWS A SHED AT THE NORTH PROPERTY LINE.IN
 THE EVENT THAT THE SHED IS NO LONGER EXISTING, IT SHALL
 BE INDICATED ON BOTH COPIES OF THE SURVEY.IF THE SHED
 WILL BE DEMOLISHED, THAN A DEMOLITION PERMIT FOR THE
 SHED SHALL BE SUBMITTED TO THE CONSTRUCTION SERVICES
 DEPARTMENT PRIOR TO BUILDING PERMIT APPROVAL.IF THE
 SHED IS TO REMAIN, THAN SETBACK DIMENSIONS FROM THE
 SHED TO THE PROPOSED PRIMARY STRUCTURE SHALL BE
 PROVIDED.PLEASE NOTE THAT PER SECTION 94-304(B)(3) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS, ACCESSORY
 STRUCTURES SHALL BE LOCATED NO LONGER THAN 6 FEET FROM
 THE PRIMARY STRUCTURE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-01 Cont ID  
Sent By adavila Date 2007-03-01 Time 11:54 Rev Time 0.00
Received By adavila Date 2007-03-01 Time 11:54 Sent To I
Notes
2007-03-01 12:52:14PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PLEASE PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) SIGNED AND SEALED SURVEYS.THE
 SURVEY SHALL BE LESS THAN A YEAR OLD.
  
 3. PROVIDE HEIGHT DIMENSION FROM GRADE TO THE TOP OF
 THE CHIMNEY.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.