Plan Review Details - Permit 07020464
Plan Review Stops For Permit 07020464
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 09:07 Rev Time 0.00
Received By shill Date 2007-06-13 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-04 Cont ID  
Sent By shill Date 2007-05-04 Time 11:32 Rev Time 0.00
Received By shill Date 2007-05-04 Time 11:32 Sent To  
Notes
2007-05-04 11:36:05****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)I THINK THAT THE COMMENT WAS ADDRESSED BUT IT IS
 DIFFICULT TO DETERMINE AS I CANNOT READ THE ADDED TEXT
 REGARDING POOL SAFETY.PLEASE SUBMIT LEGIBLE PLANS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-04 Cont ID  
Sent By shill Date 2007-04-04 Time 12:24 Rev Time 0.00
Received By shill Date 2007-04-04 Time 12:24 Sent To  
Notes
2007-04-04 12:26:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)POOL SAFETY REQUIREMENTS OF FBC R 4101 IS TO BE
 INCORPORATED INTO THE PLAN.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-18 Cont ID  
Sent By btrobaug Date 2007-05-18 Time 13:36 Rev Time 0.33
Received By btrobaug Date 2007-05-18 Time 13:30 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-03-21 Cont ID  
Sent By btrobaug Date 2007-03-21 Time 07:05 Rev Time 0.50
Received By btrobaug Date 2007-03-21 Time 06:31 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-05-29 Cont ID  
Sent By mperson Date 2007-05-29 Time 14:40 Rev Time 0.00
Received By mperson Date 2007-05-29 Time 14:39 Sent To B
Notes
2007-05-29 14:41:38CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-04-04 Cont ID  
Sent By mperson Date 2007-04-04 Time 09:59 Rev Time 0.00
Received By mperson Date 2007-04-04 Time 09:59 Sent To B
Notes
2007-04-04 10:01:20CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 14:40 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 14:40 Sent To E
Notes
2007-05-15 14:40:42TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-01 Cont ID  
Sent By adarroug Date 2007-05-01 Time 10:12 Rev Time 0.00
Received By adarroug Date 2007-05-01 Time 10:12 Sent To P
Notes
2007-05-01 10:12:53TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-25 Cont ID  
Sent By adarroug Date 2007-04-25 Time 16:14 Rev Time 0.00
Received By adarroug Date 2007-04-25 Time 16:14 Sent To Z
Notes
2007-04-25 16:14:30TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-20 Cont ID  
Sent By adarroug Date 2007-03-20 Time 09:02 Rev Time 0.00
Received By adarroug Date 2007-03-20 Time 09:02 Sent To E
Notes
2007-03-20 09:02:48TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-04 Cont ID  
Sent By shill Date 2007-04-04 Time 12:26 Rev Time 0.00
Received By shill Date 2007-03-14 Time 09:21 Sent To  
Notes
2007-03-14 09:22:25TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-05-29 Cont ID  
Sent By mperson Date 2007-05-29 Time 14:38 Rev Time 0.33
Received By mperson Date 2007-05-29 Time 14:38 Sent To G
Notes
2007-05-29 14:43:20****************PROVISO****************
 A) FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES)

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-05-03 Cont ID  
Sent By mperson Date 2007-05-03 Time 11:27 Rev Time 0.33
Received By mperson Date 2007-05-03 Time 11:27 Sent To B
Notes
2007-05-03 13:44:41DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS.
 ** FBC-2004 CHAPTER 1, THE CITY OF WEST PALM BEACH
 AMENDMENTS.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO/OK** PER FBC-2004, CHAPTER 1, SECTION
 106.1.3, QUALITY OF BUILDING PLANS: THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 NOTE: THE RESUBMITTED PLANS ARE STILL HARD TO READ. THE
 WORDING IS NOT LEGIBLE DUE TO THE INK RUNNING TOGETHER.
 PLEASE SUBMIT NEW SHEETS THAT ARE LEGIBLE. PLEASE
 REFERENCE ALL CIRCLED AREAS IN RED INK THAT ARE NOT
 LEGIBLE AND PLEASE CORRECT AND RESUBMIT.
  
 2. **NO** PER R4101.6.6.4 THE HAND WRITTEN CHANGES
 MADE FOR THE TWO SUCTION INLETS ON THE PIPING DIAGRAM
 ARE WRONG. THE HAND WRITTEN CHANGES ARE INDICATING A
 THREE FEET CENTER TO CENTER SEPERATION OF THE MAIN
 DRAINS, WHICH IS WRONG. THE CORRECT INDICATION SHOULD
 BE THAT THE TWO SUCTION INLETS PER PUMP SHOULD BE
 SEPERATED A MINIMUM OF THREE FEET. PLEASE CORRECT AND
 RESUBMIT.
  
 3. **OK**
  
 4. **OK**
  
 5. **OK**
  
 6. **OK**
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-04 Cont ID  
Sent By mperson Date 2007-04-04 Time 09:31 Rev Time 0.45
Received By mperson Date 2007-04-04 Time 09:31 Sent To G
Notes
2007-04-04 09:58:50DENIED
 REFERENCE:
 ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004, CHAPTER 1, SECTION
 106.1.3, QUALITY OF BUILDING PLANS: THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 NOTE: PLANS ARE HARD TO READ AND THE PIPING SCHEMATIC
 DOES NOT REFLECT THE POOL LAYOUT. PLEASE DELETE THE
 SPA, AND CLEANING LINE FROM THE SCHEMATIC ON THE
 RESUBMITTAL AND CLEARLY INDICATE THAT THESE ITEMS ARE
 NOT BEING USED IN THE "POOL DATA & EQUIPMENT &
 CRITERIA" ON THE RESUBMITTAL.
  
 2. PER R4101.6.6.4 SUCTION INLETS PER PUMP THE TWO
 SUCTION INLETS ON THE PIPING DIAGRAM ARE INDICATED IN
 THE WRONG PLACE. IF IT IS THE INTENT TO LOCATE THE TWO
 SUCTION INLETS IN THE SIDE WALL THEY MUST BE ONE EACH
 ON TWO SEPERATE VERTICAL WALLS. PLEASE REFLECT THIS ON
 THE RESUBMITTAL.
  
 3.FBC-2004 SEC. 424.2.7.2, OR
 FBCR-2004 SEC. R4101.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK.
 NOTE: PLEASE INDICATE ON THE RESUBMITTED POOL EQUIPMENT
 ANCHOR DETAIL THAT THE SLAB IS A NOMINAL 4 INCH THICK
 (4")
  
 4. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
  
 5.FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES)
  
 6.FBC-2004 SEC. 424.2.14, OR FBCR-2004
 SEC. R4101.15 GAS PIPING SHALL COMPLY
 WITH FBC FUEL GAS.SEPARATE PLANS AND
 PERMIT REQUIRED.
 (ADD TO NOTES)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status P Date 2007-04-30 Cont ID  
Sent By jroach Date 2007-04-30 Time 22:28 Rev Time 0.00
Received By jroach Date 2007-04-30 Time 22:28 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By jroach Date 2007-03-19 Time 16:02 Rev Time 0.00
Received By jroach Date 2007-03-19 Time 16:02 Sent To I
Notes
2007-03-19 16:04:04***FAILED***
  
 1) TWO (2) COPIES OF A RECENT SURVEY SHALL BE SUBMITTED
 SHOWING THE LOCATION OF THE PROPOSED STRUCTURE AS WELL
 AS THE LOCATION OF ANY AND ALL MECHANICAL EQUIPMENT
 (I.E. POOL EQUIPMENT).DIMENSIONS TO ALL STRUCTURES
 AND EQUIPMENT SHALL BE SHOWN FROM THE PROPERTY LINE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.