Plan Review Details - Permit 07020459
Plan Review Stops For Permit 07020459
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-12 Cont ID  
Sent By rmcdouga Date 2007-10-12 Time 10:27 Rev Time 0.00
Received By rmcdouga Date 2007-10-12 Time 10:27 Sent To  
Notes
2007-10-12 10:29:45REVISED SHEET A2.0 AND PRODUCT APPROVAL FOR 1X HEAVY
 MULLIONS HAS BEEN REVIEWED FOR CODE COMPLIANCE.
  
 TRUSSES DENIED
  
 1) THE TRUSS LAYOUT AND TRUSS DRAWING DESIGN DATA DOES
 NOT CONCUR WITH THE APPROVED PLANS. THE TOP AND BOTTOM
 CORD DEAD LOADS ARE DIFFERENT.
  
 2) THE TRUSS LAYOUT IS REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-25 Cont ID  
Sent By rmcdouga Date 2007-07-25 Time 13:32 Rev Time 0.00
Received By rmcdouga Date 2007-07-25 Time 13:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-29 Cont ID  
Sent By rmcdouga Date 2007-06-29 Time 13:19 Rev Time 0.00
Received By rmcdouga Date 2007-06-29 Time 13:19 Sent To Z
Notes
2007-06-29 13:46:04DENIED BY BUILDING
  
 1)) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
 THE NOC THAT WAS SUBMITTED HAS EXPIRED.
  
 2) THE FASTENERS SPECIFIED FOR THE SIMPSON MBHA 3
 CONNECTOR ON SHEET A5.0 ARE INCORRECT. THE CATALOG
 SPECIFIES 2 ALL THREAD RODS EPOXIED WITH MINIMUM 6-3/4"
 EMBEDMENT FOR THIS HANGER.
  
 3) THE NET UPLIFT AND CAPACITY SPECIFIED FOR THE CS 16
 STRAP ON SHEET A5.0 ARE REVERSED.
  
 4) THE CONNECTORS FOR THE 2 PLY GIRDER AT THE FRONT
 PORCH ARE NOT SPECIFIED ON A5.0 OR SECTION 2 ON D1.
  
 NOTE: SEE RED MARKS ON PLAN.
  
 RESUBMIT THE OLD SHEETS WITH THE COUNTY IMPACT FEE
 STAMPS OR THE NEW PLANS WILL HAVE TO BE STAMPED BY THE
 COUNTY FOR IMPACT FEES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-04 Cont ID  
Sent By rmcdouga Date 2007-04-04 Time 11:56 Rev Time 0.00
Received By rmcdouga Date 2007-04-03 Time 17:38 Sent To  
Notes
2007-04-04 11:56:42DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT A SITE DRAINAGE PLANS SHOWING COMPLIANCE WITH
 R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE
  
 3) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR
 WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL
 HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING
 WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT
 EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN
 ADJACENT PROJECTION OR WALL.
 EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING
 LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE
 PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4
 INCHES (102 MM).
 PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM)
 SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR
 FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE
 PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND
 SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL
 PROTECTION BASED ON LOCATION ON THE LOT.
  
 4) SHOW COMPLIANCE WITH R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE.
 EXCEPTIONS:
 1.OPENINGS SHALL BE PERMITTED IN WALLS THAT ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 2.FOUNDATION VENTS INSTALLED IN COMPLIANCE WITH
 THIS CODE ARE PERMITTED.
  
 5) PLEASE CLARIFY THE SCREEN BLOCK THAT IS SPECIFIED ON
 SHEET A1.0 AT THE GARDEN WALL.
  
 6) THE SCREEN BLOCK SPECIFIED AT THE GARAGE IN THE
 GENERAL NOTES ON A2.0 CAN NOT BE LOCATED IN THE FIRE
 RATED ZERO LOT LINE WALL.
  
 7)1001.1.3/ 1005.4 ZERO LOT LINE
 EGRESS:WHEN ACCESS TO OR FROM A RE-
 QUIRED EMERGENCY ESCAPE AND RESCUE OPEN-
 ING OF A STRUCTURE TO THE PUBLIC WAY,
 REQUIRES TRANSVERSING A PROPERTY
 (ADJOINING LOT) THAT IS NOT PART OF THE
 ONE WHICH THE STRUCTURE IS LOCATED, AN
 EGRESS EASEMENT THROUGH THE ADJOINING
 PROPERTY IS REQUIRED AND SHALL BE RECORD
 ED IN THE COUNTY RECORDS. THIS EASEMENT
 SHALL BE A MINIMUM OF 3' WIDE AND NOTH-
 ING SHALL BE PLACED WITHIN THE EASEMENT
 AREA WHICH WOULD BLOCK ACCESS TO THE
 EASEMENT AND OR IMPEDE EMERGENCY EGRESS
 FROM THE RESCUE OPENING TO THE PUBLIC
 WAY. NO LANDSCAPING, FENCES OR OTHER
 IMPEDIMENTS SHALL BE INSTALLED IN THIS
 EASEMENT.
  
 8) SHOW COMPLIANCE WITH G2408.3 (305.5) PRIVATE
 GARAGES.
 APPLIANCES LOCATED IN PRIVATE GARAGES SHALL BE
 INSTALLED WITH A MINIMUM CLEARANCE OF 6 FEET (1829 MM)
 ABOVE THE FLOOR.
 EXCEPTION: THE REQUIREMENTS OF THIS SECTION SHALL NOT
 APPLY WHERE THE APPLIANCES ARE PROTECTED FROM MOTOR
 VEHICLE IMPACT AND INSTALLED IN ACCORDANCE WITH SECTION
 G2408.2.
  
 9) SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED. THE
 GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND ITS
 ATTIC AREA BY NOT LESS THAN ? -INCH (12.7 MM) GYPSUM
 BOARD APPLIED TO THE GARAGE SIDE. GARAGES BENEATH
 HABITABLE ROOMS SHALL BE SEPARATED FROM ALL HABITABLE
 ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH (15.9 MM) TYPE
 X GYPSUM BOARD OR EQUIVALENT. WHERE THE SEPARATION IS A
 FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE
 SEPARATION SHALL ALSO BE PROTECTED BY NOT LESS THAN
 ?-INCH (12.7 MM) GYPSUM BOARD OR EQUIVALENT.
  
 10) SPECIFY THE SIZE OF THE ATTIC ACCESS ON THE
 PLANS.R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 11) PLEASE CLARIFY THE COLUMN SHOWN ON A1.0 AT THE
 CORNER OF THE BREAKFAST ROOM WHICH APPEARS TO HAVE 4
 VERTICAL REBARS AND IS LABELED AS A TYPE 2 COLUMN.
  
 12) THE TAG FOR SECTION 8/A1.0 AT THE FAMILY ROOM WALL
 IS IN THE WRONG LOCATION. IT SHOULD BE AT THE DOOR
 OPENING.
  
 13) SLIDING GLASS DOOR B IS SHOWN ON THE SCHEDULE ON
 A2.0 AS TWELVE FEET WIDE AND UNDER REMARKS IN SAME
 SCHEDULE IT IS SPECIFIED AS A 16080. PLEASE CORRECT.
 ALSO THE TRANSOM ABOVE IS SPECIFIED AS TWO 96" X 24"
 WINDOWS IN THE SCHEDULE ON A2.0. PLEASE CORRECT.
  
 14) PLEASE SPECIFY THE 8 X 8 LINTEL BETWEEN THE 12'
 SLIDING GLASS DOOR AND THE FIXED GLASS TRANSOM AT THE
 BREAKFAST ROOM.THE LINTEL SCHEDULE AND ROOF/LINTEL
 PLAN ON A5.0 DOES NOT SPECIFY THIS LINTEL.
  
 15) PROVIDE A FRAMING PLAN FOR THE ARCH OPENINGS.
  
 16)ON SHEET A2.0 A 96" X 24" FIXED WINDOW IS
 SPECIFIED ABOVE THE THE 6' WIDE SLIDING GLASS DOOR AT
 THE DINING ROOM. HOWEVER, IT IS NOT SHOWN ON THE
 ELEVATION ON A4.0.
  
 17) THE WINDLOAD PRESSURES FOR THE TWO SIDE SWING DOORS
 AT THE COVERED TERRACE ARE NOT SPECIFIED ON SHEET
 A4.0.
  
 18) THE WINDLOAD PRESSURES ARE NOT SPECIFIED FOR THE
 OVAL LAUNDRY ROOM WINDOW OR THE EXTERIOR DOOR TO
 BEDROOM #3.THE PRESSURES SPECIFIED FOR THE WINDOW IN
 BEDROOM #2 ON THE RIGHT ELEVATION ARE DIFFERENT FROM
 THE ONES FOR THE SAME WINDOW ON THE FRONT ELEVATION.
 SEE SHEET A4.0.
  
 19) SUBMIT THE GLASS BLOCK MANUFACTURER'S
 SPECIFICATIONS FOR THE INSTALLATION OF THE ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 20) SUBMIT THE SIMPSON TECHNICAL BULLETINS THAT ALLOW
 THE HUS 26 AND HGUS 28-2 HANGERS TO BE FASTENED TO
 MASONRY OR CONCRETE WITH CONCRETE SCREWS.
  
 21) SUBMIT THE NOA FOR THE 8" WIDE LINTELS, WHICH ARE
 NOT INCLUDED IN THE NOA THAT WAS SUBMITTED.
  
 22) THE PRODUCT APPROVAL SUBMITTED FOR THE 12' WIDE SGD
 IS FOR 4 OR 2 PANEL DOORS, THE PLAN SHOWS A 3 PANEL
 DOOR. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-10-25 Cont ID  
Sent By dpalmer Date 2007-10-25 Time 12:38 Rev Time 0.00
Received By dpalmer Date 2007-10-25 Time 12:38 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-11 Cont ID  
Sent By dpalmer Date 2007-10-11 Time 16:55 Rev Time 0.00
Received By dpalmer Date 2007-10-11 Time 16:47 Sent To B
Notes
2007-10-11 16:55:25** DENIED REVISION**
  
 1) NOTE: ** PLEASE SEE SOME ITEMS WHICH WERE *REDLINED*
 ON ISSUE PLANS WERE NOT ADDRESSED. THERE WERE SOME
 NOTES CORRECTED.
  
 *** NOTES REDLINED***
 * PLEASE SEE PREVIOUS REQUESTED CODES AND NOTES WERE
 PLACED ON D-1 AND NOT ON ELECTRICAL SHEETS. THIS
 INCLUDES THE NOTES FOR RECESSED LIGHTING REQUIREMENTS
 PER 13-606.1.ABC.1.2.4 AND CORRECT ADOPTED CODES FOR
 DESIGN.( PLEASE PLACE ON ELECTRICAL SHEETS).
 * NOTES ON ELECTRICAL SHEETS IN LEGEND STILL INDICATE
 THE 2002 NEC.
  
 ** PLEASE CORRECT THE ABOVE ALONG WHEN ANY OTHER
 REVISIONS ARE MADE TO PLANS.
  
 2) NOTE: PLEASE SEE AFI PROTECTION IS STILL SHOWN ON
 RECEPTACLES WHEN THIS PROTECTION IS REQUIRED FOR THE
 CIRCUIT.AFCI RECEPTACLE IS NOT MADE, AND ONLY NEEDS
 TO LIST THE CIRCUIT IN THE PANEL.
 210.12
 AS STATED ON PREVIOUS REVIEW IF THERE ARE ANY QUESTIONS
 OR COMMENTS TO PLEASE CALL TO GO OVER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-03 Cont ID  
Sent By dpalmer Date 2007-06-03 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2007-06-03 Time 11:11 Sent To P
Notes
2007-06-03 11:32:45PLANS REDLINED.
  
  
 * PLEASE SEE PREVIOUS REQUESTED CODES AND NOTES WERE
 PLACED ON D-1 AND NOT ON ELECTRICAL SHEETS. THIS
 INLCUDES THE NOTES FOR RECESSED LIGHTING REQUIREMENTS
 AND CORRECT ADOPTED CODES FOR DESIGN.( PLEASE PLACE ON
 ELECTRICAL SHEETS).
 * NOTES ON ELECTRICAL SHEETS IN LEGEND STILL INDICATE
 THE 2002 NEC.
 * PLEASE SEE GFI PROTECTION IS REQUIRED FOR "ALL"
 RECEPTS WITHIN 6FT OF LAUNDRY ROOM SINK WHICH ARE 125V
 15 OR 20 AMP. (INCLUDING DEDICATED USE RECEPTS, THIS
 WAS CHANGED IN THE 2005 NEC )
  
 ** PLEASE CORRECT THE ABOVE ALONG WHEN ANY OTHER
 REVISIONS ARE MADE TO PLANS.
  
  
 SOME SHEETS STILL NOT DATED BY THE ARCHITECT.(
 ELECTRICAL SHEETS OK).

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-23 Cont ID  
Sent By dpalmer Date 2007-02-23 Time 11:43 Rev Time 0.00
Received By dpalmer Date 2007-02-23 Time 11:43 Sent To M
Notes
2007-03-20 20:02:49RECEPTS W/IN 6FT OF LUNDRY SINKS. GFI 210.8A7 INCLUDING
 WASHING MACHINES
2007-02-23 11:44:20*** UNSAT ***
  
 6610 SPARROW HAWK DR.
  
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISION. (THIS WILL AFFECT PLANS
 SUBMITTED).
 2005 NFPA-70 (NEC).
 2002 NFPA-72
 2003 NFPA-101
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 2) NOTE: PLEASE SEE 2004 FBC W/2006 FOR NOTE REQUIRED
 FOR TYPE OF RECESSED LIGHTING FIXTURES PER
 13-606.1.ABC.1.2.4
  
 3) NOTE: PLEASE SEE REAR THAT THE REAR PORCH WILL
 REQUIRE A LIGHT W/ A SWITCH FROM THE MASTER BEDROOM OR
 A 3-WAY FOR THE FLOOD LIGHTS WHICH ARE BEING SHOWN FOR
 EGRESS LIGHTING FROM FAMILY ROOM. OTHER OPTIONS MAY
 ALSO BE DONE, HOWEVER PLEASE SHOW MINIMUM LIGHT(S) FOR
 EGRESS. A LIGHT FIXTURE OF SOME TYPE WILL BE REQUIRED
 FOR ILLUMINATION OF THE REAR AREA. (FLOODS AS SHOWN ARE
 OK)
 210.70, LS 101 7.8
  
 4) NOTE: PLEASE SEE THE COMPRESSOR FOR THE A/C CU IS
 BEING SHOWN WITH A LOAD OF 9.8KW; PLEASE VERIFY THIS AS
 THIS LOAD EXCEED THAT OF THE RATING OF THE CIRCUIT
 BREAKER.
 THIS WAS REDLINED ON PREVIOUS PLANS ON MANY OCCASIONS
 BUT TO DATE NO CHANGES HAVE BEEN MADE.
  
 5) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY
 THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-01-17 Cont ID  
Sent By shill Date 2008-01-17 Time 15:23 Rev Time 0.00
Received By shill Date 2008-01-17 Time 15:23 Sent To Z
Notes
2008-01-17 15:24:23TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 10:58 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 10:58 Sent To E
Notes
2007-10-24 10:59:14TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 15:49 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 15:49 Sent To E
Notes
2007-10-10 15:50:17TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-27 Cont ID  
Sent By adarroug Date 2007-09-27 Time 10:25 Rev Time 0.00
Received By adarroug Date 2007-09-27 Time 10:25 Sent To M
Notes
2007-09-27 10:25:52TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 10:03 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 10:03 Sent To B
Notes
2007-09-20 10:04:16TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 15:31 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 15:31 Sent To M
Notes
2007-08-29 15:32:10TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-24 Cont ID  
Sent By adarroug Date 2007-07-24 Time 15:56 Rev Time 0.00
Received By adarroug Date 2007-07-24 Time 15:56 Sent To E
Notes
2007-07-24 15:56:59TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-24 Cont ID  
Sent By adarroug Date 2007-05-24 Time 16:10 Rev Time 0.00
Received By adarroug Date 2007-05-24 Time 16:10 Sent To E
Notes
2007-05-24 16:11:08TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-04 Cont ID  
Sent By rmcdouga Date 2007-04-04 Time 11:56 Rev Time 0.00
Received By rmcdouga Date 2007-02-21 Time 11:14 Sent To  
Notes
2007-02-21 11:15:14TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-05 Cont ID  
Sent By rregueir Date 2007-10-05 Time 08:14 Rev Time 0.00
Received By rregueir Date 2007-10-05 Time 07:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-10 Cont ID  
Sent By tgordon Date 2007-09-10 Time 14:37 Rev Time 0.30
Received By tgordon Date 2007-09-10 Time 14:37 Sent To  
Notes
2007-09-10 14:38:35REVISION TO MECH. PLANS, ENERGY CAL'S. AND COOLING LOAD
 CAL'S..

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-02-23 Cont ID  
Sent By tgordon Date 2007-02-23 Time 13:30 Rev Time 0.30
Received By tgordon Date 2007-02-23 Time 13:30 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-14 Cont ID  
Sent By jleech Date 2007-06-14 Time 09:51 Rev Time 0.00
Received By jleech Date 2007-06-14 Time 09:51 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-02-26 Cont ID  
Sent By jleech Date 2007-02-26 Time 08:27 Rev Time 0.00
Received By jleech Date 2007-02-26 Time 08:27 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By choops Date 2008-01-22 Time 13:58 Rev Time 0.00
Received By choops Date 2008-01-22 Time 13:58 Sent To PC
Notes
2008-01-22 13:59:05***APPROVED - REVISION - SUBMITTED LANDSCAPE PLAN***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-02-22 Cont ID  
Sent By ajones Date 2007-02-22 Time 10:17 Rev Time 0.00
Received By ajones Date 2007-02-22 Time 10:17 Sent To  
Notes
***NONE***