Plan Review Details - Permit 07020456
Plan Review Stops For Permit 07020456
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-09-22 Cont ID  
Sent By amorse Date 2007-09-22 Time 09:24 Rev Time 0.00
Received By amorse Date 2007-09-22 Time 09:24 Sent To PC
Notes
2007-09-22 09:25:18 
  
 PASSED
  
 REVISION FOR 1X HEAVY DUTY MULLIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-18 Cont ID  
Sent By amorse Date 2007-08-18 Time 12:49 Rev Time 0.00
Received By amorse Date 2007-08-18 Time 12:49 Sent To PC
Notes
2007-08-18 13:11:47 
  
 PASSED
  
 1)TRUSS ENGINEERING PACKAGE REVIEWED AND APPROVED
  
 2)WINDOW SHOP DRAWINGS WILL REQUIRE REVISION TO
 DRAWINGS ON SHEET A-2.0 AND CORRECTIONS TO NOA NUMBERS
 TO THOSE THAT WERE REVIEWEDAND APPROVED AT TIME OF
 PERMITTING.
  
 3)DRAWINGS SHOW 2 X HEAVY DUTY MULLIONS AND THE
 PRODUCT APPROVALS THAT WERE SUBMITTED ARE 2 X HD BUT
 SHOP DRAWINGS ARE USING 1 X HD. IF THE 1 X HD ARE TO BE
 USED SUBMIT NEW PRODUCT APPROVALS AND REVISED DRAWINGS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-23 Cont ID  
Sent By amorse Date 2007-06-23 Time 07:01 Rev Time 0.00
Received By amorse Date 2007-06-23 Time 07:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-16 Cont ID  
Sent By amorse Date 2007-06-16 Time 13:38 Rev Time 0.00
Received By amorse Date 2007-06-16 Time 13:38 Sent To PC
Notes
2007-06-16 13:40:15 
  
 DENIED
  
 1)ALL NEW PAGES ARE REQUIRED TO BE DATED BY THE
 DESIGN PROFESSIONAL OF RECORD
  
 2)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-14 Cont ID  
Sent By amorse Date 2007-04-14 Time 13:36 Rev Time 0.00
Received By amorse Date 2007-04-14 Time 13:36 Sent To PC
Notes
2007-04-14 13:47:08 
  
 DENIED
  
 1)DRAWINGS TO COMPLY WITH THE LATEST CODE, PLACE NOTE
 ON PLANS THAT THEY CONFORM TO THE 2004 FLORIDA BUILDING
 CODE WITH 2006 REVISIONS
  
 2)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO
 BUILDING PER 1603.1.4 FBC
  
 3)PROVIDE TYPE OF CONSTRUCTION AND OCCUPANCY GROUP ON
 PLANS
  
 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*.VALUE ADJUSTED TO $307,520 WHICH
 INCREASES THE PERMIT FEE. BALANCE DUE IS $105.43
  
 5)PLAN, ELEVATION AND DOOR, WINDOW SCHEDULE DO NOT
 MATCH. WINDOW 1,HAS QUANTITY OF ONE, SHOULD BE THREE.
 IS THERE A PICTURE WINDOW ABOVE THE SGD "A"
 IF SO IS LINTEL BETWEEN OR MULLION AND WHAT IS THE
 DESIGN PRESSURE.
  
 6)BUILDING ELEVATION TO INCLUDE MEAN ROOF HEIGHT
  
 7)SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 8)PROVIDE NOTE FOR SHOWER DOORS TO BE SAFETY GLAZING
 PER R308.4 FBC RES.
  
 9)IF WOOD BUCKS ARE TO BE USED AN ATTACHMENT DETAIL
 IS REQUIRED FOR THE TRANSFER OF APPLICABLE LOADS TO THE
 BUILDING PER R613.6.1.1 FBC RES.
 AS THE PRODUCT APPROVALS DO NOT SPECIFY ANY ATTACHMENT
 METHOD
  
 10)NOA FOR PRE-CAST LINTELS IS INCORRECT SUBMITTED
 NOA IS FOR 4,6 AND 12" WIDE BLOCK APPLICATIONS PROVIDE
 MIAMI-DADE NOA # 03-0605.05 FOR 8" LINTELS
  
 11)SEVERAL LINTEL LENGTHS ARE TO SHORT TO MEET THE
 MINIMUM END BEARING OF 4" PER 2104.1.5 FBC. THE
 FOLLOWING NEED CORRECTION
 A) LINTEL #7 FOR SGD "A"
 B) LINTEL #3 FOR GARAGE DOOR "F AND SGD "C"
 C) LINTEL #6 FOR WINDOW #7
  
 12)GLASS BLOCK MEETS THE DESIGN PRESSURES REQUIRED
 BUT IS ONLY SMALL MISSILE IMPACT RATED. PER 1609.1.4
 FBC GLAZING WITHIN THE FIRST 30 FEET FROM GRADE ARE
 REQUIRED TO MEET LARGE MISSILE IMPACT TEST REQUIREMENTS
 THEREFORE THESE OPENINGS WILL REQUIRE AN IMPACT
 PROTECTION SYSTEM.
  
 13)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-29 Cont ID  
Sent By dpalmer Date 2007-08-29 Time 18:09 Rev Time 0.00
Received By dpalmer Date 2007-08-29 Time 18:02 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-03 Cont ID  
Sent By dpalmer Date 2007-06-03 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2007-06-03 Time 10:55 Sent To P
Notes
2007-06-03 11:03:34PLANS REDLINED.
  
  
 * PLEASE SEE PREVIOUS REQUESTED CODES AND NOTES WERE
 PLACED ON D-1 AND NOT ON ELECTRICAL SHEETS. THIS
 INLCUDES THE NOTES FOR RECESSED LIGHTING REQUIREMENTS
 AND CORRECT ADOPTED CODES FOR DESIGN.( PLEASE PLACE ON
 ELECTRICAL SHEETS).
 * NOTES ON ELECTRICAL SHEETS IN LEGEND STILL INDICATE
 THE 2002 NEC.
 * PLEASE SEE GFI PROTECTION IS REQUIRED FOR "ALL"
 RECEPTS WITHIN 6FT OF LAUNDRY ROOM SINK WHICH ARE 125V
 15 OR 20 AMP. (INCLUDING DEDICATED USE RECEPTS, THIS
 WAS CHANGED IN THE 2005 NEC )
  
 ** PLEASE CORRECT THE ABOVE ALONG WHEN ANY OTHER
 REVISIONS ARE MADE TO PLANS.
  
  
 SOME SHEETS STILL NOT DATED BY THE ARCHITECT.(
 ELECTRICAL SHEETS OK).

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-23 Cont ID  
Sent By dpalmer Date 2007-02-23 Time 10:24 Rev Time 0.00
Received By dpalmer Date 2007-02-23 Time 10:02 Sent To M
Notes
2007-03-20 20:02:30RECEPTS W/IN 6FT OF LUNDRY SINKS. GFI 210.8A7 INCLUDING
 WASHING MACHINES
2007-02-23 10:28:37*** UNSAT ***
  
 6700 FOX HOLLOW
  
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISION. (THIS WILL AFFECT PLANS
 SUBMITTED).
 2005 NFPA-70 (NEC).
 2002 NFPA-72
 2003 NFPA-101
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 2) NOTE: PLEASE SEE 2004 FBC W/2006 FOR NOTE REQUIRED
 FOR TYPE OF RECESSED LIGHTING FIXTURES PER
 13-606.1.ABC.1.2.4
  
 3) NOTE: PLEASE SEE REAR THAT THE REAR PORCH WILL
 REQUIRE A LIGHT W/ A SWITCH FROM THE MASTER BEDROOM OR
 A 3-WAY FOR THE FLOOD LIGHTS WHICH ARE BEING SHOWN FOR
 EGRESS LIGHTING FROM FAMILY ROOM. OTHER OPTIONS MAY
 ALSO BE DONE, HOWEVER PLEASE SHOW MINIMUM LIGHT(S) FOR
 EGRESS. A LIGHT FIXTURE OF SOME TYPE WILL BE REQUIRED
 FOR ILLUMINATION OF THE REAR AREA. (FLOODS AS SHOWN ARE
 OK)
 210.70, LS 101 7.8
  
 4) NOTE: PLEASE SEE THE COMPRESSOR FOR THE A/C CU IS
 BEING SHOWN WITH A LOAD OF 9.8KW; PLEASE VERIFY THIS AS
 THIS LOAD EXCEED THAT OF THE RATING OF THE CIRCUIT
 BREAKER.
 THIS WAS REDLINED ON PREVIOUS PLANS ON MANY OCCASIONS
 BUT TO DATE NO CHANGES HAVE BEEN MADE.
  
 5) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 10:08 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 10:08 Sent To B
Notes
2007-09-20 10:09:05TO "AMORSE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-12 Time 16:39 Rev Time 0.00
Received By adarroug Date 2007-09-12 Time 16:39 Sent To M
Notes
2007-09-12 16:39:59TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 10:13 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 10:13 Sent To E
Notes
2007-08-29 10:14:04TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-08 Cont ID  
Sent By mmiller Date 2007-08-08 Time 18:04 Rev Time 0.00
Received By mmiller Date 2007-08-08 Time 18:03 Sent To B
Notes
2007-08-08 18:04:15SENT TO "AM" DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-22 Cont ID  
Sent By adarroug Date 2007-06-22 Time 16:04 Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 16:04 Sent To B
Notes
2007-06-22 16:04:34TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-24 Cont ID  
Sent By adarroug Date 2007-05-24 Time 11:07 Rev Time 0.00
Received By adarroug Date 2007-05-24 Time 11:07 Sent To E
Notes
2007-05-24 11:08:06TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-04-14 Time   Rev Time 0.00
Received By adarroug Date 2007-02-21 Time 11:13 Sent To  
Notes
2007-02-21 11:13:50TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-09-14 Cont ID  
Sent By tgordon Date 2007-09-14 Time 09:00 Rev Time 0.25
Received By tgordon Date 2007-09-14 Time 08:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-02-23 Cont ID  
Sent By tgordon Date 2007-02-23 Time 12:07 Rev Time 0.30
Received By tgordon Date 2007-02-23 Time 12:07 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-14 Cont ID  
Sent By jleech Date 2007-06-14 Time 09:37 Rev Time 0.00
Received By jleech Date 2007-06-14 Time 09:37 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-02-26 Cont ID  
Sent By dpalmer Date 2007-06-03 Time 11:48 Rev Time 0.00
Received By jleech Date 2007-02-26 Time 08:30 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-02-22 Cont ID  
Sent By ajones Date 2007-02-22 Time 10:16 Rev Time 0.00
Received By ajones Date 2007-02-22 Time 10:16 Sent To  
Notes
***NONE***