Plan Review Details - Permit 07020441
Plan Review Stops For Permit 07020441
Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2009-08-05 Cont ID  
Sent By jwitmer Date 2009-08-05 Time 07:48 Rev Time 0.55
Received By jwitmer Date 2009-08-05 Time 07:48 Sent To  
Notes
2009-08-05 07:48:41 
 BUILDING PLAN REVIEW
 PERMIT: 07020441
 ADD: 6600S DIXIE HWY
 CONT: S. E. C. CONSTRUCTION & DEV
 TEL: (561)797-6007
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: BUILDING PROVISO:
 AUGUST 5/ 2009
 1) SHEETS A-102 &A-105.1 REVISION# 4 PLANS HAVE DELETED
 THE REQUIRED 34" SINK HEIGTH FOR SINKS. DOUG WISE B.O.
 VISITED THE JOBSITE AND DERTERMINED THE ROOM IN
 QUESTION , ROOM# 129 APPEARS TO BE A BREAK ROOM AND THE
 SINK AND COUNTERTOP TO BE AT 34" PER:
 11-4-24.2 HEIGTH. SINKS SHALL BE MOUNTED WITH COUNTER
 OR RIM NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.1.1(3) AREAS USED ONLY BY EMPLOYEES AS WORK AREAS.
 AREAS THAT ARE USED ONLY AS WORK AREAS SHALL BE
 DESIGNED AND CONSTRUCTED SO THAT INDIVIDUALS WITH
 DISABILITIES CAN APPROACH, ENTER, AND EXIT THE AREAS.
 THIS CODE DOES NOT REQUIRE THAT ANY AREAS USED ONLY AS
 WORK AREAS BE CONSTRUCTED TO PERMIT MANEUVERING WITHIN
 THE WORK AREA OR BE CONSTRUCTED OR EQUIPPED (I.E., WITH
 RACKS OR SHELVES) TO BE ACCESSIBLE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2009-08-03 Cont ID  
Sent By jwitmer Date 2009-08-03 Time 15:57 Rev Time 0.55
Received By jwitmer Date 2009-08-03 Time 14:37 Sent To  
Notes
2009-08-03 16:15:15BUILDING PLAN REVIEW
 PERMIT: 07020441
 ADD: 6600S DIXIE HWY
 CONT: S. E. C. CONSTRUCTION & DEV
 TEL: (561)797-6007
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
 1) SHEETS A-102 &A-105.1 REVISION# 4 PLANS HAVE DELETED
 THE REQUIRED 34" SINK HEIGTH FOR SINKS.
 11-4-24.2 HEIGTH. SINKS SHALL BE MOUNTED WITH COUNTER
 OR RIM NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.1.1(3) AREAS USED ONLY BY EMPLOYEES AS WORK AREAS.
 AREAS THAT ARE USED ONLY AS WORK AREAS SHALL BE
 DESIGNED AND CONSTRUCTED SO THAT INDIVIDUALS WITH
 DISABILITIES CAN APPROACH, ENTER, AND EXIT THE AREAS.
 THIS CODE DOES NOT REQUIRE THAT ANY AREAS USED ONLY AS
 WORK AREAS BE CONSTRUCTED TO PERMIT MANEUVERING WITHIN
 THE WORK AREA OR BE CONSTRUCTED OR EQUIPPED (I.E., WITH
 RACKS OR SHELVES) TO BE ACCESSIBLE.
  
 I HAVE REVIEWED THIS REVISION WITH THE BUILDING
 OFFICIAL DOUGWISE AND THE CONCLUSION IS THESE AREAS ARE
 NOT A WORK AREA THAT RESULTS IN SUCH AS A LAB OR
 DOCTORS OFFICE.
 THE OWNERS HAVE THREE OPTIONS;
 A) WRITING A LETTER TO THE BUILDING OFFICAL INDICATING
 THES AREAS ARE GOING TO BE WORK AREAS EXEMPTING THEM
 FROM THE REQUIRMENTS OF 11-4.1.1(3). IN DOING SUCH IT
 WILL CREATE A BUILDING
 STIPULATION THAT WILL PRINT ON THE C.O AS WELL AS TIE
 TO THE LAND FILE, WHEN TENANTS APPLY FOR THEIR
 OCCUPATIONAL LICENSE IT WILL LIMIT TTHE USAGE OF THE
 BUILDING.
  
 B) APPLY TO THE STATE FOR A WAIVER OF THE ACCESSIBILITY
 CODE.
  
 C) REMOVE THE REVISION AND LET THE PLANS STAND AS A 34"
 HEIGTH SINK AS THE PLANS WERE PERMITTED.
  
 I TRIED TO CONTACT TTHE DESIGNER OF RECORD FRIDAY JULY
 31,2009, AND SPOKE WITH SECRETARY, HE WOULD CALL BACK
 IN THE AFTERNOON, TO DATE NO TELEPHONE CALL
 ARCHITECT JOSE PEROTTI (305)442-1262
  
 DENIED SETS OF PLANS ARE NOW KEPT BY CITY.
 .
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2009-08-03 Cont ID  
Sent By jwitmer Date 2009-08-03 Time 15:56 Rev Time 0.50
Received By jwitmer Date 2009-07-31 Time 11:21 Sent To  
Notes
2009-08-03 15:56:51REVISIUON# 4 SHEET A-601

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2009-07-16 Cont ID  
Sent By jwitmer Date 2009-07-16 Time 11:08 Rev Time 3.33
Received By jwitmer Date 2009-07-16 Time 11:08 Sent To PC
Notes
2009-07-16 11:10:10REVISIONS:
 A-101
 A-102
 A-103
 A-201
 A-202
 A-601
 A-602

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-05-29 Cont ID  
Sent By jwitmer Date 2009-05-29 Time 10:57 Rev Time 0.33
Received By jwitmer Date 2009-05-29 Time 10:57 Sent To PC
Notes
2009-05-29 10:58:40REVISION: ENTRY DOORS NOA 04-0427.05 INDUSTRIAL
 MILLWORK CORP TENER SERIES WOOD ENTRY DOORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-02-19 Cont ID  
Sent By jwitmer Date 2009-02-19 Time 11:24 Rev Time 1.11
Received By jwitmer Date 2009-02-19 Time 11:24 Sent To  
Notes
2009-02-19 11:31:02REVISIONS;
 REVIEWED
 ENGINEERS' LETTER ALLOWING 1X BUCKS INSTEAD OF 2X BUCKS
 AS ILLUSTRATED ON SHEET S3 DETAIL# 2.
 A-601 NEW WALL DETAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-02-19 Cont ID  
Sent By jwitmer Date 2009-02-19 Time 11:22 Rev Time 0.77
Received By jwitmer Date 2009-02-19 Time 11:22 Sent To PC
Notes
2009-02-19 11:24:24REVISION DATED 1-19-09
 REVIEWED:
 A-201
 A-202
 A-602

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2009-02-19 Cont ID  
Sent By jwitmer Date 2009-02-19 Time 08:48 Rev Time 3.33
Received By jwitmer Date 2009-02-19 Time 08:48 Sent To  
Notes
2009-02-19 09:10:18BUILDING PLAN REVIEW
 PERMIT: 07020441
 ADD: 6600S DIXIE HWY
 CONT: S. E. C. CONSTRUCTION & DEV
 TEL: (561)797-6007
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
  
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW # 1 DATED 01-19-09
 ACTION: DENIED
  
 1) PLEASE CORRECT REVISION NUMBERS TO CORRESPOND WITH
 DATE SEQUENCE. FOR INSTANCE YOU HAVE A REVISION# 1
 DATED 6-28-07 WHICH WAS THE RESPONCE TO THE BUILDING
 DEPARTMENT COMMENTS. IT IS VERY CONFUSING TO FIND A NEW
 SET OF REVISIONS AND STILL BE REVISION # 1 WHEN THE
 FIRST SET OF REVISIONS OCCURRED 6-28-09. 106.1.1*
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION NATURE AND EXTENT OF WORK
 PROPOSED UNDER THIS REVISION.
  
 2) SHEET A-102:
 2A) THE FRONT ENTRY DOORS ARE NOT INDICATED AS A
 REVISION. 106.1.1*.
  
 2B) THERE ARE FOUR AREAS ON THE PLAN HIGH LIGHTED IN
 RED WHERE THE 18" MANEUVERING CLEARENCES AT DOORS IS
 MISSING 11-4.13.6. ALSO SEE 11-4.1.1(3) ACCESSIBILITY
 FOR WORKERS, AREAS USED ONLY BY EMPLOYEES AS WORK
 AREAS. AREAS THAT ARE USED ONLY AS WORK AREAS SHALL BE
 DESIGNED AND CONSTRUCTED SO THAT INDIVIDUALS WITH
 DISABILITIES CAN APPROACH, ENTER, AND EXIT THE AREAS.
 DOOR 105
 DOOR 107
 DOOR 109
 DOOR 135
  
 3) SHEET A103 MAY OR MAY NOT NEED REVISITED DEPENDING
 ON THE REVISIONS TO BE MADE ON SHEET A-102.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-10-17 Cont ID  
Sent By jwitmer Date 2008-10-17 Time 14:59 Rev Time 0.55
Received By jwitmer Date 2008-10-17 Time 14:59 Sent To PC
Notes
2008-10-17 14:59:43S1,S2 & S4 REVISION# 1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-29 Cont ID  
Sent By jwitmer Date 2007-08-29 Time 14:26 Rev Time 1.55
Received By jwitmer Date 2007-08-29 Time 11:53 Sent To  
Notes
2007-08-29 14:31:20BUILDING PROVISOS:
 07020441
 6600 S DIXIE HWY.
  
 1) THE NEW CUSTOM FRONT ENTRY DOOR TO BE UNDERA
 SEPERATE PERMIT WITH ASSOCIATED FEES AND REVIEW.
  
 2)109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERMORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A PROFESSIONALLY
 PREPARED DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE
 WITH THIS PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO THE INSPECTOR
 IN ORDER TO RECEIVE APPROVAL OF THE FINAL INSPECTION.
  
 3) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS.ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-27 Cont ID  
Sent By jwitmer Date 2007-06-27 Time 14:24 Rev Time 2.22
Received By jwitmer Date 2007-06-27 Time 14:24 Sent To  
Notes
2007-06-27 14:27:00BUILDING PLAN REVIEW
 PERMIT: 07020441
 ADD: 6600S DIXIE HWY
 CONT: S. E. C. CONSTRUCTION & DEV
 TEL: (561)797-6007
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
  
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED, HOWEVER THE 90 WITHOUT ACTIVITY MAY RUN
 OUT ON THE NOC REQUIRING IT TO BE REVISED.
  
 3) PARTIALLY COMPLETE, PLANS SUBMITTED AFTER DEC.8,
 2006 ARE TO BE DESIGNED UNDER THE 2004 FBC WITH 2006
 REVISIONS, PLEASE CORRECT.
  
 4-5) COMPLIED.
  
 6) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) 2ND REQUEST, WE NEED AGREEMEENT FROM THE DESIGN
 PROFESSIONAL THAT THEY ARE GOING TO COMPLETE THE THIRD
 PARTY QUALITY ASSURANCE FOR THE FRONT DOOR VERIFYING
 THE ASSEMBLY PROCESS AND WE NEED FROM THE DESIGN
 PROFESSIONAL THE REQUIREMENTS FOR THE INSTALLATION OF
 THE DOOR JAMB. IF THE CUSTOM FRONT DOOR DOES HAVE GLASS
 UNITS IT IT OR THE SIDELIGHTS EITHER LARGE MISSLE
 TESTING HAS TO OCCUR OR A PROTECTIVE SHUTTER SYSTEM
 WILL HAVE TO BE ADDED TO THIS PERMIT WITH THE REQUIRED
 PRODUCT APPROVALS AND INFORMATION TO SECURE THE STORM
 SHUTTERS OR PANELS.
 FRONT DOOR TO BE BUILT AS A ONE TIME APPROVAL , THE
 DESIGNER OF RECORD WILL NEED TO SUPERVISE THE ASSEMBLY
 OF THE DOOR AND THE INSTALATION OF DOOR AND FRAME, AND
 SIGN AND SEAL AFFADAVIT TO THE EFFECT. THIS WILL BE A
 PROVISO REQUIRED BEFORE A CERTIFICATE OF COMPLETION CAN
 BE ISSUED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By jwitmer Date 2007-03-15 Time 15:44 Rev Time 2.22
Received By jwitmer Date 2007-03-15 Time 15:44 Sent To  
Notes
2007-03-15 16:21:46BUILDING PLAN REVIEW
 PERMIT: 07020441
 ADD: 6600S DIXIE HWY
 CONT: S. E. C. CONSTRUCTION & DEV
 TEL: (561)797-6007
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
  
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH
 NOTICE IS NULL & VOID. NOTE: 713.13(6) THE POSTING OF
 THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) COVER SHEET A-1 DESIGN DATA INDICATES THE DESIGN TO
 ASCE 7-98, THE CURRENT STANDARD UNDER THE 2006 FBC IS
 ASCE 7-02.
  
 4) PLANS ALSO INDICATE THERE ARE NO OPENINGS IN END
 ZONES, 10% OF 55'-2"OR 5'-2" OR 40% OF BUILDING MEAN
 ROOF HEIGTH13'-0"= 5'-21/2", PLEASE CORRECT THE WINDOWS
 PRESSURES IN THE END ZONES. TABLE 1609.6B.
  
 5) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7) FRONT DOOR TO BE BUILT AS A ONE TIME APPROVAL , THE
 DESIGNER OF RECORD WILL NEED TO SUPERVISE
 THE ASSEMBLY OF THE DOOR AND THE INSTALATION OF DOOR
 AND FRAME, AND SIGN AND SEAL AFFADAVIT TO THE EFFECT.
 THIS WILL BE A PROVISO REQUIRED BEFORE A CERTIFICATE OF
 COMPLETION CAN BE ISSUED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-08-02 Cont ID  
Sent By dpalmer Date 2007-08-02 Time 18:40 Rev Time 0.00
Received By dpalmer Date 2007-08-02 Time 18:00 Sent To  
Notes
2007-08-02 18:40:36STAMPED PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-05 Cont ID  
Sent By dpalmer Date 2007-06-05 Time 20:53 Rev Time 0.00
Received By dpalmer Date 2007-06-05 Time 19:08 Sent To  
Notes
2007-06-05 20:55:08** UNSAT **
  
 *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR
 CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT
 YET ABLE TO BE MADE.
  
 ** PLEASE ALSO SEE THERE ARE SEVERAL ITEMS FROM
 PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING AND NEW
 COMMENTS BASED ON REVISED SHEETS OR SUBMITTED DOCUMENTS
 WHICH WERE NOT THE SAME AS PREVIOUS SUBMITTED PLANS.
 PLANS HAVE CHANGED DESIGNERS OF RECORD.
  
  
 1) NOTE:PLEASE SEE THIS COMMENT REMAINS THE SAME AS
 ONLY THE CODES ON THE ELECTRICAL PLANS WERE CORRECTED.
 THE CODES ON THE ARCHITECTURAL COVER SHEETS WHICH WERE
 OK ON PREVIOUS PLANS ARE NOT THE SAME ON THE NEW
 ARCHITECTURAL SHEETS?
 ELECTRICAL CODE NOT STATED, WRONG LIFE SAFETY CODE, NOT
 THE LATEST CORRECT FBC.
 PLEASE ADJUST.
 PREVIOUS REVIEW NOTE:
 PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN SUBMITTED
 AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECTS UNDER
 THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE THAT
 THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC FOR
 ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE ARE
 CHANGES IN THE FBC WHICH WILL AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE NOW SEE MISSING TITLE BLOCK INFORMATION
 FORLANDSCAPE ARCHITECT AND FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004. PLEASE ALSO
 SEE FLORIDA STATUTES AND 481.219.
 PLEASE SEE MISSING THE REQUIRED PRINTED NAME AND
 PRINTED LICENSE NUMBER OF DESIGNER AND MISSING FIRM
 LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
  
 3) NOTE: PLEASE SEE THE NEW LANDSCAPE SHEETS NOW
 CONTAIN A *RUBBERSTAMP* FOR THE REQUIRED *ORIGINAL*
 SIGNATURE FROM THE ARCHITECT OF RECORD. PLEASE SEE FS
 481.221. THIS IS REQUIRED WHETHER OR NOT COMMENT IS
 MADE BY ANY OTHER TRADE.
  
 4) NOTE: PLEASE SE THE ENERGY CALCULATIONS SUBMITTED IN
 FACT CONTAINS A *RAISED SEAL* OVER *PHOTO-COPIED*
 SIGNATURES AND DATED SHEETS. THIS IS THE SAME ON ALL
 LOCATIONS ON BOTH SETS OF ENERGY CALCULATIONS
 SUBMITTED.
 PLEASE SEE FBC 13-103.1.1.1, FLORIDA STATUTES, 471.025
 AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002 WHICH
 REQUIRES AN *ORIGINAL SIGNATURE* FOR ALL PLANS AND
 DOCUMENTS SIGNED, DATED AND SEALED BY THE ENGINEER.
  
 4) NOTE:PLEASE SUBMIT ENERGY/PERFORMANCE CALCULATIONS
 FOR NEW LIGHTING WHICH CORRELATES WITH THE ELECTRICAL
 PLANS AND LIGHTING LEGEND SHOWN. PLEASE SEE LIGHTING AS
 SHOWN ON CALCULATIONS DOES NOT CORRELATE. MANY ARE OK,
 HOWEVER NOT ALL.
 PLEASE GO OVER EACH AND COORDINATE PLANS WITH
 CALCULATIONS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.AB.1.1, 13-415.2.
  
 5) NOTE: PLEASE SEE THAT PLANSNOW INDICATE SOME KIND
 OF *FUTURE* GENERATOR ON SOME SHEETS BUT NOT ON SITE
 PLANS, LANDSCAPE, BUILDING ELECTRICAL ETC.
 PLEASE SEE SPECS/CUT SHEETS ARE BEING SUBMITTED FOR
 THIS UNIT, BUT NO PROVISIONS ON ELECTRICAL PLANS ARE
 BEING GIVEN OR INFORMATION?
 PLEASE KNOW IF ONE IS TO BE INSTALLED BASED ON THE
 PROPOSED LOCATION AT THE REAR OF BUILDING IT DOES NOT
 MEET THE MINIMUM CLEARANCES FOR UNIT FROM BUILDING.
 PLEASE SEE POSSIBLE COMMENTS FROM ZONING FOR PLACING IN
 PARKING AREA.
 PLEASE SEE 90.7, 110.3
 PLEASE KNOW THE GENERATOR WILL NO BE INCLUDED UNDER
 THIS PERMITTED SET OF PLANS IF NOT INFORMATION IS
 SUBMITTED OR SHOWN. THIS IS A NOTE FOR INFORMATIONAL
 PURPOSE THAT THE UNIT AT LOCATION SHOWN DOES NOT MEET
 CODE.
 FBC 106.1.2
  
 6) NOTE:PLEASE COMPLETE CIRCUIT FOR ROOF TOP GFI ON
 PLANS. PLEASE COMPLETE WHAT APPEARS TO BE A DEDICATE
 CIRCUIT IN CONFERENCE ROOM #1. THE SYMBOL IS NOT ON
 LEGEND AND THE CLOSET ONE MENTIONS DEDICATED CIRCUIT??
 PLEASE CLARIFY.
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE SEE AS THE PLANS HAVE BEEN REVISED FOR
 MECHANICAL EQUIPMENT; PLEASE SEE 424.3B FOR THE MINIMUM
 OCP REQUIRED FOR HEAT FOR A/C UNITS. (MIN 125%) PLEASE
 ALSO CORRELATE THE OCP SHOWN ON PANEL SCHEDULE *A* WITH
 THE OCP SHOWN IN LOAD CALCULATIONS.
 THIS WILL CHANGE THE BREAKER SIZE, AND CONDUCTORS.
 240.4,310.16.
  
 8) NOTE: PLEASE INDICATE THE SIZE AND TYPE OF GROUNDING
 ELECTRODES IN THE NEW REVISED SYSTEM AS SHOWN. LENGTH,
 TYPE OF GROUND RODS ETC.
 250.50, 250.53
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE PANEL *C* ON RISER WHICH DOES NOT
 CORRELATE WITH THE NUMERICAL ELECTRICAL RISER NOTE.
 PLEASE SEE NOTE MENTIONS 100AMP PANEL WITH A 200AMP
 MAIN BREAKER YET PANEL SCHEDULE SHOWS THIS PANEL AS
 150AMPS?
 THIS IS THE SAME AS PREVIOUS PLANS.
  
 10) NOTE: PLEASE SEE PANEL *B* AND NOTE ABOVE FOR PANEL
 *C*. PLEASE CORRELATE WITH ELECTRICAL NOTES ALSO AND
 THE RISER WHICH SHOWS NOTE #10. NOTE #10 IS ALSO USED
 FOR PANEL *D*.
 PLEASE CORRELATE. PANEL *B* IS SHOWN AS 150AMP ON
 SCHEDULE AND 200AMPS ON NOTES.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 11) NOTE: PLEASE SEE PANEL *A* IS STILL SHOWN AS 200A
 MCB ON PANEL SCHEDULE AND YET NOTES FOR PANEL *A*
 INDICATES THIS TO BE A 225AMP PANEL?
  
 12) NOTE: AS NOTED ABOVE IN NOTE 10 FOR PANEL *C*,
 PLEASE SEE PANEL *D* NOTE WHICH MENTIONS THIS AS A
 200AMP MCB PANEL YET, PANEL IS SHOWN AS MLO. FBC
 106.3.5.1.2, 106.1.2 FOR COORDINATION.
  
 ** PLEASE SEE THE SPECS SUBMITTED FOR THE LIGHTING
 SWITCHES SUBMITTED ARE NOT NEEDED AS A LIGHTING CONTROL
 *SYSTEM* IS NO LONGER INDICATED.
 ** PLEASE SEE THE CLOCK SPEC SHEETS ARE NOT NEEDED FOR
 SETS. THANK YOU FOR SUBMITTING TO SHOW UNIT AND
 LISTING.
  
 ** PLEASE KNOW AS SOME OF THE INFORMATION ON WHETHER OR
 NOT A GENERATOR IS GOING TO BE INSTALLED IT IS NOT
 POSSIBLE TO REVIEW FOR THESE ITEMS.
  
 ** PLEASE SEE ONE SET OF PLANS IS REDLINED FOR MANY OF
 THESE ITEMS WHICH MAY HELP TO LOCATE ITEMS AS NOTED.
  
 ** PLEASE KNOW AS STATED ON PREVIOUS REVIEW: PLEASE BE
 SURE TO CALL IF THERE ARE ANY QUESTIONS OR COMMENTS
 WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF THERE ARE
 ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, NOT
 UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE AND THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 17:07 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 15:44 Sent To  
Notes
2007-03-04 17:09:14** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWINGON ELECTRICAL SHEETS FOR
 THIS REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.(ALREADY ON MAIN
 ARCHITECTURAL SHEETS)
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR
 ARCHITECT AND FIRM AS REQUIRED UNDER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004. PLEASE ALSO SEE
 FLORIDA STATUTES AND 481.219.
 PLEASE SEE MISSING THE REQUIRED PRINTED NAME AND
 PRINTED LICENSE NUMBER OF DESIGNER AND MISSING FIRM
 LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
  
 3) NOTE:PLEASE SUBMIT ENERGY/PERFORMANCE CALCULATIONS
 FOR NEW LIGHTING WHICH CORRELATES WITH THE ELECTRICAL
 PLANS AND LIGHTING SHOWN. PLEASE SEE LIGHTING AS SHOWN
 ON CALCULATIONS DOES NOT CORRELATE.
 PLEASE ALSO BE SURE THESE ARE SIGNED, DATED AND SEALED
 BY THE DESIGNER OF RECORD AND THE PERSON RESPONSIBLE
 FOR ENERGY CALCULATIONS.
 PLEASE SEE THAT AN AUTOMATED METHOD OF LIGHTING
 CONTROLS IS BEING NOTED ON SYMBOL LEGEND HOWEVER THE
 ENERGY CALCULATIONS DO NOT CORRELATE WITH THIS AS THEY
 SHOW *MANUAL ON/OFF* FOR THIS?
 PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED
 FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS
 ON THE ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.AB.1.1, 13-415.2,AND 13-415.2.ABC.1.2 (3)
 FOR TRACK LIGHTING (WHERE APPLICABLE)
  
 4) NOTE: PLEASE SEE THAT PLANS DO INDICATE SOME
 CONTROLS FOR LIGHTING HOWEVER PLEASE SUBMIT MORE
 INFORMATION FOR SYSTEM BEING PROPOSED.
 FBC 106.1.2 ADMIN SECTION
 110.3, 90.7 NEC.
  
 5) NOTE: PLEASE SEE THE ACCESS TO THE ELECTRICAL ROOM
 WILL NOT BE PERMITTED THROUGH A STORAGE ROOM. 240.24.
 PLEASE KNOW THAT ALL ACCESS TO OVER CURRENT PROTECTION
 DEVICES SHALL BE ACCESSIBLE ON A CONTINUING BASIS.
 PLEASE KNOW THIS IS REQUIRED BY THIS OFFICE AND THE
 OFFICE OF THE FIRE MARSHAL.
 PLEASE SEE THE LOCATION OF THE PANEL *D* IS BEING NOTED
 AND SHOWN IN A STORAGE ROOM WHICH IS NOT PERMITTED.
 PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE
 ELECTRICAL PANEL(S) NEED TO MEET 110.26.
 PLEASE ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY
 IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES
 WITH OVER CURRENT PROTECTION DEVICES.
 PLEASE ADJUST PLANS.
  
 6) NOTE:PLEASE SEE PLANS ON ARCHITECTURAL SHEETS
 NOTES SERVICE AS EXISTING HOWEVER THE ELECTRICAL PLANS
 AND RISER SEEM TO NOTE AND INDICATE ALL OF THIS
 EQUIPMENT AS NEW. PLEASE CLARIFY AND ADJUST NOTE ON
 ARCHITECTURAL PLANS IF ALL NEW AS SHOWN.
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE KNOW THAT THE PLANS NEED TO CORRELATE
 WITH ALL CIRCUIT DESIGNATIONS ON PLANS FOR ROOMS AND
 AREAS. PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY
 IN THE CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT
 ACCEPTABLE.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS THE
 M-SHEETS DO NOT SEEM TO INDICATE ANY MECHANICAL
 EQUIPMENT. PLEASE KNOW THAT REVIEW OF EQUIPMENT FOR
 ELECTRICAL COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 PLEASE COMPLETE.
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE PANEL SCHEDULE *A* IS NOT COMPLETE
 FOR CONDUCTOR SIZES REQUIRED FOR AC EQUIPMENT. PLEASE
 ALSO SEE MISSING LOAD FOR THE RTU.
 PLEASE COMPLETE FOR REVIEW OF CODE COMPLIANCE. 310.16,
 240.4, 220, 408.4
  
 10) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF
 EMERGENCY AND EXIT LIGHTS. PLEASE SEE MOST ARE
 CIRCUITED CORRECTLY AND ONLY ONE OR SO IS CIRCUITED TO
 OTHER THAN THE LOCAL LIGHTING BRANCH CIRCUIT.
  
 11) NOTE: PLEASE CLARIFY MEZZANINE LEVEL FOR LIGHTING
 AND CONTROL.
 PLEASE KNOW LIGHTING CONTROL WILL ALSO BE REQUIRED AT
 THE MEZZ LEVEL AND RECEPTACLE FOR SERVICE PER 210.63,
 210.70.
  
 12) NOTE: PLEASE SEE PANEL *C* ON RISER WHICH DOES NOT
 CORRELATE WITH THE NUMERICAL ELECTRICAL RISER NOTE.
 PLEASE SEE NOTE MENTIONS 100AMP PANEL WITH A 200AMP
 MAIN BREAKER YET PANEL SCHEDULE SHOWS THIS PANEL AS
 150AMPS?
  
 13) NOTE: PLEASE SEE PANEL *B* AND NOTE ABOVE FOR PANEL
 *C*. PLEASE CORRELATE WITH ELECTRICAL NOTES ALSO AND
 THE RISER WHICH SHOWS NOTE #10. NOTE #10 IS ALSO USED
 FOR PANEL *D*.
 PLEASE CORRELATE.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 14) NOTE: PLEASE SEE NOTE FOR GROUNDING ELECTRODE
 SYSTEM MENTIONS NEW *BLDG STEEL* YET THIS BEING AN
 EXISTING BUILDING IT IS UNCLEAR WHERE THE NEW BUILDING
 STEEL IS BEING SHOWN. REVIEW OF ARCHITECTURAL AND
 STRUCTURAL PLANS DOES NOT REVEAL THIS.
 PLEASE KNOW AS AN EXISTING BUILDING THE FOOTER STEEL IS
 NOT A REQUIRED ATTACHMENT UNLESS NEW.OPENING OF THE
 OLDER EXISTING FOOTER TO MAKE AN ATTACHMENT COULD
 CREATE ISSUES FOR THE STRUCTURAL INTEGRITY OF THE
 EXISTING FOOTER DEPENDING ON THE AGE ETC.
 250.50
  
 15) NOTE: PLEASE CORRELATE THE CIRCUITING FOR CLOCK
 FEED AS THE LOAD AND AMPERAGE ON THE PANEL SCHEDULE,
 PLANSAND LOAD CALCULATIONS LEND THIS TO BE A 20AMP
 AND SINGLE POLE CIRCUIT, HOWEVER THE PANEL SCHEDULE
 SHOWS THIS FEED AS A 2-POLE 30AMP CIRCUIT WITH #10
 AWG?
 PLEASE CORRELATE.
 FBC 106.3.5.1.2
  
 16) NOTE: PLEASE SEE PANEL *D* NOTE WHICH MENTIONS THIS
 AS A 200AMP MCB PANEL YET, PANEL IS SHOWN AS MLO. FBC
 106.3.5.1.2, 106.1.2 FOR COORDINATION.
  
 ** PLEASE KNOW AS SOME INFORMATION IS NOT SUBMITTED AT
 THIS TIME FOR REVIEW THER MAY BE COMMENTS ON ANY
 FOLLOWING REVIEWS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2007-10-03 Cont ID  
Sent By rchokshi Date 2007-10-03 Time 15:44 Rev Time 0.00
Received By rchokshi Date 2007-10-03 Time 15:44 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-08-24 Cont ID  
Sent By rchokshi Date 2007-08-24 Time 11:18 Rev Time 0.00
Received By rchokshi Date 2007-08-24 Time 10:42 Sent To  
Notes
2007-08-24 11:18:07**** FAILED ****
  
 1. WHAT CHANGES YOU MADE FROM LAST TIME WE APPROVED FOR
 ENG REVIEWIN JUNE1,2007, REV 2.?? DID YOU MAKE
 ANY CHANGES IN STORM WATER CALS., PERVIOUS/IMPERVIOUS
 AREA ETC ? PLEASE EXPLAIN.
 2. YOU HAVE NOT SEALED& SIGNEDP.E. SEAL. IN ALL 3
 CIVIL DRAWINGS. NEED TO SEAL & SIGN
 3.YOU HAVE POLLUTION PREVENTION SILT FENCEONLY ON
 EAST & SOUTH SIDE,NEED SOME SILT FENCE ON NORTH &
 WEST SIDE ALSO, PLEASE EXPLAIN.
 4. AFTER CONTROL STRUCTURE BLEEDING, WHERE STORM WATER
 GOES, EITHER SFWMD OR IN CITY CANAL, PLEASE EXPLAIN
  
 RASIK CHOKSHI805-6723
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2007-06-01 Cont ID  
Sent By rchokshi Date 2007-06-01 Time 13:24 Rev Time 0.00
Received By rchokshi Date 2007-06-01 Time 12:47 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By rchokshi Date 2007-03-09 Time 08:09 Rev Time 0.00
Received By rchokshi Date 2007-03-09 Time 08:10 Sent To M
Notes
2007-03-09 08:09:19PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,ALL THESE STANDARDS & NOTES OF
 CITY OF WPB CAN BE OBTAINED FROM 1000 45TH STREET, ENG
 DEPT.
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION,MUST MEET FL BLDG CODE, FLOOD
 ZONE, CENTER LINE OF ROAD , SIDEWALK ELEVATION. PLEASE
 SHOW ALL THESE ELEVATIONS ON THE DRAWINGS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT, GEO-TECH
 REPORT.
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ? PRE & POSTPERVIOUS AREA,
 IMPERVIOUS AREA & TOTAL SITE AREA.
 6. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 7. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 8. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 10. ANY ASBESTOS FOUND OR LEAD IN OLD PAINT MUST BE
 HANDLED BY HEALTH DEPT & FDEP.
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-30 Cont ID  
Sent By mawillia Date 2007-08-30 Time 18:39 Rev Time 0.00
Received By mawillia Date 2007-08-30 Time 18:04 Sent To  
Notes
2007-08-30 18:35:43*****APPROVED****
  
  
 ALL THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS
 HAVE BEEN ADDRESSED;PLAN SHEETS A-106, A-201, AND E-2
 WERE STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-06-29 Cont ID  
Sent By mawillia Date 2007-06-29 Time 10:58 Rev Time 0.00
Received By mawillia Date 2007-06-28 Time 16:53 Sent To  
Notes
2007-06-28 17:27:29*****UNSAT****
 PLEASE NOTE THAT SINCE A NEW SHEET (A-106) HAS BEEN
 ADDED, IT MUST ALSO BE REFLECTED IN THE INDEX OF
 DRAWINGS ON A-001.TO MAINTAIN UNIFORMITY ON THE PLAN
 SHEETS, FOLLOW THE CAPITALIZED GUIDELINES TO THE
 COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW:
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 ITEM TO D-101
  
 2.NFPA 101- 2003 EDITION SHALL BE REFERENCED. ON
 A-001 RECTIFY #6 UNDER CODES & STANDARDS AND ADD 2004
 EDITION TO THE FLORIDA FIRE PREVENTION CODE
  
 3.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR CLASS B IN EXITS AND EXIT CORRIDORS, CLASS
 A, CLASS B, OR CLASS C IN ALL OTHER AREAS.PLEASE
 SPECIFY.YOUR RESPONSE (ON A-106) INDICATES THAT
 CHAPTER 38/39 SHALL COMPLY.BASED UPON AN EXISTING OR
 A NEW OCCUPANCY,REFER TO THE APPROPIATE CHAPTER. ALSO
 SPECIFY WHAT THE INTERIOR CLASSIFICATION ARE GOING TO
 BE, NOT JUST QUOTING THE CODE.
  
 NEW COMMENT
  
 A.ON SHEET A-106 NOTE #1 REFERS TO NFPA 241 AS LIFE
 SAFETY.PLEASE BE ADVISED THAT NFPA 101 IS THE LIFE
 SAFETY CODE, WHEREAS NFPA 241 IS THE STANDARD FOR
 SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS.
  
  
  
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-29 Cont ID  
Sent By mawillia Date 2007-03-29 Time 14:09 Rev Time 0.00
Received By mawillia Date 2007-03-29 Time 13:10 Sent To  
Notes
2007-03-29 14:08:42*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.NFPA 101- 2003 EDITION SHALL BE REFERENCED.
  
 3.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR CLASS B IN EXITS AND EXIT CORRIDORS, CLASS
 A, CLASS B, OR CLASS C IN ALL OTHER AREAS.PLEASE
 SPECIFY.
  
 4.SHOW LOCATION OF THE 2A10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 5.IF THE BUILDING IS EQUIPPED WITH A FIRE ALARM AND
 (OR) FIRE SPRINKLER SYSTEM, WILL THE SCOPE OF WORK
 CAUSE THE SYSTEM(S) TO BE MODIFIED?IF SO, SEPARATE
 PLANS AND PERMIT WILL BE REQUIRED FOR THE REMODEL.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-10-05 Cont ID  
Sent By mperson Date 2007-10-05 Time 14:19 Rev Time 0.00
Received By mperson Date 2007-10-05 Time 14:19 Sent To  
Notes
2007-10-05 14:27:41****************PROVISO****************
 SEPERATE GAS PERMIT REQUIRED.
 FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/COM PERMIT REQUIRED WITH ZONING, ELECTRICAL AND
 MECHANICAL APPROVAL OF GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE VALVED AND CAPPED GAS TIGHT.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-06-16 Cont ID  
Sent By kstevens Date 2007-06-16 Time 16:54 Rev Time 0.00
Received By kstevens Date 2007-06-16 Time 16:54 Sent To  
Notes
2007-06-16 16:56:15SEPARATE GAS PERMIT REQUIRED.--GAS TO THE FUTURE
 GENERATOR IS AT CONTRACTORS OWN RISK. THERE IS NO
 GUARANTEE THAT THE LOCATION OF THE FUTURE GENERATOR
 WILL BE APPROVED. THERE MAY BE ZONING OR MECHANICAL
 ISSUES THAT MAY PREVENT THE GENERATOR FROM BEING
 LOCATED WHERE SHOWN.--A SHUT OFF VALVE AND A HARD
 CAP ARE REQUIRED ON THE LINE TO THE FUTURE GENERATOR.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By kstevens Date 2007-03-14 Time 11:04 Rev Time 0.00
Received By kstevens Date 2007-03-14 Time 11:04 Sent To  
Notes
2007-03-14 11:07:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SUBMIT THE FOLLOWING INFORMATION FOR THE REQUIRED
 GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (SHOW THE LENGTH FROM THE METER TO THE
 FIRST RISER),
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2009-07-29 Cont ID  
Sent By lmartine Date 2009-07-29 Time 10:47 Rev Time 0.00
Received By lmartine Date 2009-07-29 Time 10:47 Sent To  
Notes
2009-07-29 10:48:33GAVE TO WITMER

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2009-07-08 Cont ID  
Sent By rregueir Date 2009-07-08 Time 16:55 Rev Time 0.00
Received By rregueir Date 2009-07-08 Time 16:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2009-07-07 Cont ID  
Sent By dpalmer Date 2009-07-07 Time 17:00 Rev Time 0.00
Received By dpalmer Date 2009-07-07 Time 17:00 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-05-21 Cont ID  
Sent By lmartine Date 2009-05-21 Time 10:43 Rev Time 0.00
Received By lmartine Date 2009-05-19 Time 10:42 Sent To  
Notes
2009-05-21 10:43:34SENT TO JIM WITMER

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-02-10 Cont ID  
Sent By adarroug Date 2009-02-10 Time 08:35 Rev Time 0.00
Received By adarroug Date 2009-02-10 Time 08:35 Sent To B
Notes
2009-02-10 08:35:51TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 10:05 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 10:05 Sent To B
Notes
2009-02-09 10:05:39TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-02-04 Cont ID  
Sent By adarroug Date 2009-02-04 Time 09:35 Rev Time 0.00
Received By adarroug Date 2009-02-04 Time 09:35 Sent To  
Notes
2009-02-04 09:37:19TO "COMM" BD#11

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-01-26 Cont ID  
Sent By adarroug Date 2009-01-26 Time 11:03 Rev Time 0.00
Received By adarroug Date 2009-01-26 Time 11:03 Sent To M
Notes
2009-01-26 11:03:58TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-10-06 Cont ID  
Sent By adarroug Date 2008-10-06 Time 08:33 Rev Time 0.00
Received By adarroug Date 2008-10-06 Time 08:33 Sent To B
Notes
2008-10-06 08:33:29TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-10 Cont ID  
Sent By adarroug Date 2007-09-10 Time 14:26 Rev Time 0.00
Received By adarroug Date 2007-09-10 Time 14:26 Sent To  
Notes
2007-10-01 15:11:31TO "COMM" BD#8
2007-09-10 14:27:03WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-20 Cont ID  
Sent By adarroug Date 2007-07-20 Time 10:19 Rev Time 0.00
Received By adarroug Date 2007-07-20 Time 10:19 Sent To  
Notes
2007-08-01 13:30:53TO "COMM" BD#13
2007-07-20 10:20:45WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 11:09 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 11:09 Sent To  
Notes
2007-05-31 14:29:35TO "COMM" BD#30
2007-05-15 11:09:50WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-29 Cont ID  
Sent By mawillia Date 2007-03-29 Time 14:10 Rev Time 0.00
Received By mawillia Date 2007-02-20 Time 16:19 Sent To  
Notes
2007-02-26 13:34:48TO "COMM" BD#57
2007-02-20 16:25:25WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-07-10 Cont ID  
Sent By rkussner Date 2009-07-10 Time 12:34 Rev Time 0.00
Received By rkussner Date 2009-07-10 Time 12:33 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-07-08 Cont ID  
Sent By rkussner Date 2009-07-08 Time 15:58 Rev Time 0.00
Received By rkussner Date 2009-07-08 Time 15:58 Sent To  
Notes
2009-07-08 16:03:22***LANDSCAPE REVIEW FAILED***
  
 1, THE FICUS TREES ALONG THE EAST PERIMETER SHALL BE
 CHANGED TO ANOTHER SPECIES.
  
 2. ALL NEW LANDSCAPING IN THE LANDSCAPE NODE ADJACENT
 TO DIXIE HIGHWAY SHALL BE REMOVED. PLEASE CONTACT LABAN
 REEVES AT 822-2160 TO DISCUSS THE LANDSCAPE OPTIONS FOR
 THAT PLANTING AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-01-29 Cont ID  
Sent By rregueir Date 2009-01-29 Time 20:59 Rev Time 0.00
Received By rregueir Date 2009-01-29 Time 20:59 Sent To PC
Notes
2009-01-29 20:59:48REVISION #3: PAGES M.1, M.2, M.3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-08 Cont ID  
Sent By rregueir Date 2007-08-08 Time 19:51 Rev Time 0.00
Received By rregueir Date 2007-08-08 Time 19:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-05 Cont ID  
Sent By rregueir Date 2007-06-05 Time 17:18 Rev Time 0.00
Received By rregueir Date 2007-06-05 Time 14:23 Sent To  
Notes
2007-06-05 17:18:25--------------DENIED------------------
  
 1. M.4: FIRE DAMPERS LOCATED WITHIN AIR DISTRIBUTION
 AND SMOKE CONTROL SYSTEMS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE REQUIREMENTS OF THIS SECTION, AND
 THE MANUFACTURER?S INSTALLATION INSTRUCTIONS AND
 LISTING. FBC,M 607.2
  
 2. M.4: PLEASE SHOW MEANS OF AUXILIARY DRAIN PROTECTION
 FOR ROOFTOP PACKAGE UNITS PER FBC,M 307.2.3.
  
 3. M.4: DUCT DETECTOR INSTALLATION DETAIL SHOWS
 DETECTOR IN RETURN DUCT. SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM IN THE SUPPLY AIR DUCT. FBC,M
 606.2.1.
  
 4. M.4: WALL CAP DETAIL SHOWS WALL CAP W/ BUILT-IN
 DAMPER. THIS WALL CAP WILL NOT WORK FOR INTAKE IF IT
 HAS A BACKDRAFT DAMPER. ALSO, INTAKE OPENINGS ARE TO BE
 PROTECTED IN ACCORDANCE WITH FBC,M TABLE 401.6.
  
 5. PLEASE PROVIDE ROOF CURB TO STRUCTURE ATTACHMENT AND
 EQUIPMENT TO CURB ATTACHMENT DETAILS, SHOWING THE
 DESIGN TO MEET 140 MPH WIND LOAD REQUIREMENTS OF FBC CH
 16.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-17 Cont ID  
Sent By rregueir Date 2007-03-17 Time 16:53 Rev Time 0.00
Received By rregueir Date 2007-03-17 Time 14:27 Sent To  
Notes
2007-03-17 16:53:40------------------DENIED-------------------
  
 1. PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON PLANS. FBC
 106.3.5.1.4
  
 2. PLEASE PROVIDE SUBMITTAL DATA FOR THE FIREPLACE
 INCLUDING MANUFACTURER'S INSTRUCTIONS RELATED TO
 VENTING REQUIREMENTS.
  
 3. DUCT SMOKE DETECTORS SHALL BE INSTALLED TO MONITOR
 THE ENTIRE AIRFLOW OF THE SYSTEM PER FBC,M 606.3. TO
 ACCOMPLISH THIS, THE DETECTOR NEEDS TO BE LOCATED IN
 THE SUPPLY TRUNK BEFORE FIRST TAP OR BRANCH DUCT.
 CONSULT THE MANUFACTURER'S INSTALLATION INSTRUCTIONS
 FOR MINIMUM REQUIRED DISTANCE FROM BLOWER. AN
 AUDIBLE/VISIBLE NOTIFICATION (HORN/STROBE) IN AN
 APPROVED LOCATION IS REQUIRED UPON ACTIVATION OF THE
 SMOKE DETECTOR PER FBC,M 606.4.1(2)
  
 4. SOME TRANSFER DUCTS (JUMPERS) ARE NOT SIZED TO MEET
 THE BALANCED RETURN AIR EXCEPTIONS AS LISTED IN FBC,M
 601.4. IF THESE EXCEPTIONS ARE NOT MET, A FIELD TEST
 WILL BE REQUIRED AT FINAL INSPECTION TO SHOW THAT THE
 REQUIREMENT FOR A MAXIMUM PRESSURE DIFFERENTIAL OF
 0.01" WC HAS BEEN ACHIEVED.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-10-05 Cont ID  
Sent By mperson Date 2007-10-05 Time 14:12 Rev Time 0.00
Received By mperson Date 2007-10-05 Time 14:12 Sent To G
Notes
2007-10-05 14:18:46****************PROVISO****************
 PER FBC-2004 W/06 REV. CHAPTER 11 SECTION 11-4.24.6
 EXPOSED PIPES AND SURFACES. HOT WATER AND DRAIN PIPES
 EXPOSED UNDER SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST CONTACT. THERE
 SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER SINK.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-08-30 Cont ID  
Sent By kstevens Date 2007-08-30 Time 15:07 Rev Time 0.00
Received By kstevens Date 2007-08-30 Time 15:07 Sent To  
Notes
2007-08-30 15:19:03DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ******FROM PREVIOUS REVIEW:
 ***FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
  
 4. SUBMIT THE FOLLOWING INFORMATION FOR THE REQUIRED
 GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
 H. N/A
 I. N/A
  
 5. SHT A-8 SHOW COMPLIANCE FOR THE FOLLOWING:
 FOR THE LAVS:
 A. OK
 B. OK
 C. OK
  
 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15AND ALL SUBSECTIONS, AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING. SECTION
 106.1.1.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PLEASE
 INDICATE WHERE THE RESPONSE HAS BEEN ADDRESSED.
 ***RESPONSE NOTED, BUT THE REQUIREMENT FOR SECTION
 11-4.1.3(10(A) HAS NOT BEEN ADDRESSED. THE FLOOR PLAN
 SHOWS A SINGLE DRINKING FOUNTAIN, BUT SHT A-105.1 SHOWS
 A HI/LOW. PLEASE CLARIFY. IF A SINGLE DRINKING
 FOUNTAIN, SHOW COMPLIANCE FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
  
 7. SUBMIT A DETAIL FOR THE KITCHEN SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT AN ELEVATION VIEW. CABINET DOORS ARE NOT
 APPROVED FOR THE SINK AREA. SECTION 106.1.1.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PLEASE
 INDICATE WHERE THE RESPONSE HAS BEEN ADDRESSED.
 ***RESPONSE NOTED, BUT SHT A-107 HAS NOT BEEN
 SUBMITTED, NOR IS SHT A-107 INDICATED ON THE SHEET
 INDEX SHT A-001.
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. SHT A-105 THE FIXTURES SHALL BE ACCESSIBLE. PLEASE
 SHOW COMPLIANCE FOR THE FOLLOWING:
 ___FOR THE W/C'S:
 A. OK
 B. OK
 ___FOR THE LAV'S:
 A. OK
  
 3B. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUBSECTIONS FOR THE SINKS IN ROOMS 129
 & IN THE ROOM LEFT OF ROOM 115.
 ***RESPONSE NOTED, BUT SHT A-107 HAS NOT BEEN
 SUBMITTED, NOR IS SHT A-107 INDICATED ON THE SHEET
 INDEX SHT A-001.
  
 4B. GAS TO THE FUTURE GENERATOR IS AT CONTRACTORS OWN
 RISK. THERE IS NO GUARANTEE THAT THE LOCATION OF THE
 FUTURE GENERATOR WILL BE APPROVED. THERE MAY BE ZONING
 OR MECHANICAL ISSUES THAT MAY PREVENT THE GENERATOR
 FROM BEING LOCATED WHERE SHOWN.
 ***RESPONSE "COMMENT NOTED FOR FUTURE REFERENCE" WILL
 BE INDICATED ON PLANS WHEN APPROVED.
  
 5B. SHTS L1 & L2 THE LANDSCAPE FIRM LICENSE NUMBER IS
 REQUIRED IN THE TITLE BLOCK ON ALL SHEETS PER FAC
 61G1-16.004(2) & FS 481.219, 481.2055. -- STAMPED
 SIGNATURES ARE NOT APPROVED. THE SIGNATURE OF THE
 LANDSCAPE ARCHITECT IS REQUIRED.--THE PRINTED NAME
 OF THE PERSON SEALING THE DOCUMENT SHALL BE INDICATED
 IN THE TITLE BLOCK ON EACH SHEET.
 ***RESPONSE NOTED, SHEETS DELETED.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-16 Cont ID  
Sent By kstevens Date 2007-06-16 Time 16:34 Rev Time 0.00
Received By kstevens Date 2007-06-16 Time 16:34 Sent To  
Notes
2007-06-16 16:54:27DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ******FROM PREVIOUS REVIEW:
  
 1. SHT A-3 SHOW THE CLEAR FLOOR SPACE FOR THE W/C'S PER
 SECTION 11-4.16.2, THE DRINKING FOUNTAIN PER SECTION
 11-4.15.5, AND THE KITCHEN SINK PER SECTION 11-4.24.5,
 (FORWARD APPROACH REQUIRED).
 ******RESPONSE NOTED, BUT NO CLEAR FLOOR SPACE FOR THE
 DRINKING FOUNTAINS OR SINKS INDICATED. PLEASE INDICATE
 WHICH SHEET THE COMMENT RESPONSE HAS BEEN ADDRESSED
  
 2. OK
 3. OK
  
 4. SUBMIT THE FOLLOWING INFORMATION FOR THE REQUIRED
 GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
 H. N/A
 I. N/A
  
 5. SHT A-8 SHOW COMPLIANCE FOR THE FOLLOWING:
 FOR THE LAVS:
 A. 11-4.19.2 CLEARANCE (29")
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PLEASE
 INDICATE WHERE THE RESPONSE HAS BEEN ADDRESSED.B.
 11-4.19.4 EXPOSED PIPES & SURFACES ******RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED. PLEASE INDICATE WHERE
 THE RESPONSE HAS BEEN ADDRESSED.C. 11-4.91.5 FAUCETS
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PLEASE
 INDICATE WHERE THE RESPONSE HAS BEEN ADDRESSED.
  
 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15AND ALL SUBSECTIONS, AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING. SECTION
 106.1.1.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PLEASE
 INDICATE WHERE THE RESPONSE HAS BEEN ADDRESSED.
  
 7. SUBMIT A DETAIL FOR THE KITCHEN SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT AN ELEVATION VIEW. CABINET DOORS ARE NOT
 APPROVED FOR THE SINK AREA. SECTION 106.1.1.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PLEASE
 INDICATE WHERE THE RESPONSE HAS BEEN ADDRESSED.
  
 **********NEW COMMENTS**********
  
 1B. SHT A-102 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. PLEASE INDICATE THE LOCATION ON THE FLOOR PLAN.
 SECTION 106.1.1.
  
 2B. SHT A-105 THE FIXTURES SHALL BE ACCESSIBLE. PLEASE
 SHOW COMPLIANCE FOR THE FOLLOWING:
 ___FOR THE W/C'S:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.5 FLUSH CONTROLS
 ___FOR THE LAV'S:
 A. SEE PREVIOUS COMMENT #5.
  
 3B. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUBSECTIONS FOR THE SINKS IN ROOMS 129
 & IN THE ROOM LEFT OF ROOM 115.
  
 4B. GAS TO THE FUTURE GENERATOR IS AT CONTRACTORS OWN
 RISK. THERE IS NO GUARANTEE THAT THE LOCATION OF THE
 FUTURE GENERATOR WILL BE APPROVED. THERE MAY BE ZONING
 OR MECHANICAL ISSUES THAT MAY PREVENT THE GENERATOR
 FROM BEING LOCATED WHERE SHOWN.
  
 5B. SHTS L1 & L2 THE LANDSCAPE FIRM LICENSE NUMBER IS
 REQUIRED IN THE TITLE BLOCK ON ALL SHEETS PER FAC
 61G1-16.004(2) & FS 481.219, 481.2055. -- STAMPED
 SIGNATURES ARE NOT APPROVED. THE SIGNATURE OF THE
 LANDSCAPE ARCHITECT IS REQUIRED.--THE PRINTED NAME
 OF THE PERSON SEALING THE DOCUMENT SHALL BE INDICATED
 IN THE TITLE BLOCK ON EACH SHEET.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-13 Cont ID  
Sent By kstevens Date 2007-03-13 Time 11:48 Rev Time 0.00
Received By kstevens Date 2007-03-13 Time 11:48 Sent To  
Notes
2007-03-13 13:55:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-3 SHOW THE CLEAR FLOOR SPACE FOR THE W/C'S PER
 SECTION 11-4.16.2, THE DRINKING FOUNTAIN PER SECTION
 11-4.15.5, AND THE KITCHEN SINK PER SECTION 11-4.24.5,
 (FORWARD APPROACH REQUIRED).
  
 2. SHT A-8 PLUMBING SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. TOILET ROOMS #2 SHOW A W/C & A LAV IN
 EACH ROOM ON THE FLOOR PLAN, BUT ON THE RISER DIAGRAM
 AS DRAWN IT INDICATES BOTH W/C'S IN ONE ROOM AND BOTH
 LAVS IN ANOTHER. ALSO THE W/C'S ARE SHOWN CONNECTING TO
 THE BRANCH LINE & TO THE BUILDING DRAIN LINE. W/C'S
 SHALL BE CONNECTED TO THE BRANCH LINE ONLY.--ONLY
 THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT. SECTION 909.1. ALL OTHER FIXTURES BESIDES THE
 FIXTURES IN TOILET ROOMS #2 SHALL CONNECT DOWNSTREAM OF
 THE FIXTURES ON TOILET ROOMS #2.--TOILET ROOMS #1
 ARE SHOWN ON THE LEFT OF TOILET ROOMS #2 ON THE FLOOR
 PLAN, BUT ARE SHOWN ON THE RIGHT SIDE OF TOILET ROOMS
 #2 ON THE RISER DIGARAM.--THE DRINKING FOUNTAIN IS
 NOT SHOWN ON THE RISER DIAGRAM. CORRELATE FLOOR PLAN
 AND RISER. SECTION 106.1.1.--THE LAVS AND W/C'S IN
 TOILET ROOMS #1 ARE NOT VENTED AS SHOWN. SECTION
 901.2.1.--TRAPS ARE NOT ALLOWED FOR THE W/C'S AS
 THEY HAVE INTEGRAL TRAPS BUILT IN THEM. SECTION 1002.1.
 (SEE ONE SET OF PLANS SHT A-8 FOR AN EXAMPLE OF A RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN AND MEETS CODE
 REQUIREMENTS).
  
 3. SUBMIT A WATER RISER DIAGRAM THAT REFLECT THE FLOOR
 PLAN. SHOW ALL PIPE SIZES, VALVES ECT. SECTION
 106.3.5.1.3(3)(10)(13).
  
 4. SUBMIT THE FOLLOWING INFORMATION FOR THE REQUIRED
 GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (SHOW THE LENGTH FROM THE METER TO THE
 FIRST RISER),
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 5. SHT A-8 SHOW COMPLIANCE FOR THE FOLLOWING:
 FOR THE LAVS:
 A. 11-4.19.2 CLEARANCE (29")
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.91.5 FAUCETS
  
 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15AND ALL SUBSECTIONS, AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING. SECTION
 106.1.1.
  
 7. SUBMIT A DETAIL FOR THE KITCHEN SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT AN ELEVATION VIEW. CABINET DOORS ARE NOT
 APPROVED FOR THE SINK AREA. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status F Date 2009-02-09 Cont ID  
Sent By kdfreema Date 2009-02-09 Time 08:46 Rev Time 0.00
Received By kdfreema Date 2009-02-09 Time 08:46 Sent To  
Notes
2009-02-09 08:52:37***FAILED***
  
 PLEASE PROVIDE A WRITTEN NOTATION ON THE PLANS STATING
 THE SPECIFIC NATURE OF THE REVISIONS REQUESTED. NOTE
 THAT IN THE PROPOSED LOCATIONS, THE HEIGHT OF BOTH
 GATES MAY NOT EXCEED FOUR (4) FEET.
  
 ON THE SITE PLAN, THERE IS A DUPLICATE BUILDING
 FOOTPRINT IN THE MIDDLE OF SOUTH DIXIE HIGHWAY. PLEASE
 REMOVE IT AND ENSURE THAT RESUBMITTED PLANS ARE FREE OF
 UNNECESSARY MARKS AND LAYERS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-08-08 Cont ID  
Sent By kdfreema Date 2007-08-08 Time 17:07 Rev Time 0.00
Received By kdfreema Date 2007-08-08 Time 17:07 Sent To  
Notes
2007-08-08 17:09:56NOTE THAT THE GENERATOR SHOWN ON THE GAS/PLUMBING PLANS
 CANNOT BE APPROVED BY ZONING IN THAT LOCATION.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-06-06 Cont ID  
Sent By kdfreema Date 2007-06-06 Time 14:24 Rev Time 0.00
Received By kdfreema Date 2007-06-06 Time 14:24 Sent To  
Notes
2007-06-06 14:46:43***FAILED***
  
 DUMPSTER MUST BE A MINIMUM OF 5 FEET FROM PROPERTY
 LINES. AS SHOWN, THE DUMPSTER IS TOO CLOSE TO THE SOUTH
 PROPERTY LINE.
  
 THERE IS A FUTURE GENERATOR SHOWN ON THE PLUMBING
 PLANS. BE AWARE THAT A GENERATOR MAY NOT BE PLACED IN
 THIS LOCATION AS IT BLOCKS ACCESS TO THE PARKING AND
 DRIVE AISLE. IT WOULD APPEAR THE ONLY VIABLE ON-GROUND
 LOCATION WOULD BE IN THE PARKING ROW ALONG THE EAST
 SIDE OF THE PROPERTY. THE BUILDING REQUIRES 14 PARKING
 SPACES AND 16 ARE PROVIDED. TWO SPACES COULD BE REMOVED
 TO ACCOMMODATE THE GENERATOR. PLEASE NOTE THAT
 GENERATORS SHALL BE SCREENED TO THE SAME STANDARDS AS
 DUMPSTER ENCLOSURES. DEPENDING ON YOUR FUTURE PLANS, IT
 MAY BE PRUDENT TO CONSTRUCT A COMBINATION
 DUMPSTER/GENERATOR ENCLOSURE SO THAT A FUTURE GENERATOR
 MAY BE ACCOMMODATED PER CODE REQUIREMENTS.
  
 PLEASE SHOW CODE COMPLIANT STRIPING ON ALL PARKING
 SPACES.
  
 PLEASE CALL KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-02 Cont ID  
Sent By kdfreema Date 2007-03-02 Time 14:17 Rev Time 0.00
Received By kdfreema Date 2007-03-02 Time 14:17 Sent To  
Notes
2007-03-02 14:17:44**FAILED**
  
 1) A LANDSCAPE PLAN SIGNED AND SEALED BY A REGISTERED
 LANDSCAPE ARCHITECT SHALL BE PROVIDED. PLEASE SEE
 ARTICLE XIV OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR SPECIFIC REQUIREMENTS.
  
 2) PLEASE INCLUDE A PARKING SPACE STRIPING DETAIL THAT
 CONFORMS TO THE REQUIREMENTS OF SECTION 94-485 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 3) PLEASE PROVIDE A DETAIL AND ELEVATIONS FOR YOUR
 DUMPSTER ENCLOSURE. YOU MAY WANT TO CONSIDER ENLARGING
 THE ENCLOSURE TO THE NORTH TO ACCOMMODATE A RECYCLING
 CENTER.
  
 4) ALL PARKING SPACES WILL BE REQUIRED TO HAVE WHEEL
 STOPS LOCATED 2 FEET FROM THE FRONT OF THE SPACES.
  
 5) THE SECTIONS OF THE BUILDING IN THE SETBACKS (NORTH
 AND WEST ELEVATIONS) MAY NOT BE EXTENDED ABOVE THEIR
 EXISTING HEIGHTS. THIS APPLIES TO THE CLOCK TOWER
 ELEMENT AND THE PARAPET WALLS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS AND SPECIFIC INFORMATION ABOUT
 LANDSCAPING REQUIREMENTS.