2007-02-20 10:28:45 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2001 | | | | 1.)SELECT THE APPROVED ASSEMBLY YOU ARE USING FOR THE | | METAL ROOF.NOTE THAT ONLY ONE IS COMPLIANT FOR THE | | DESIGN PRESSURE OF ZONE 3, -89 PSF (SHEET S3). | | | | 2.)THE ASSEMBLY YOU HAVE SELECTED FOR THE FLAT DECK | | REFERS TO GENERAL LIMITATION #9 WHICH DOES NOT ALLOW | | ENHANCED FASTENING.THE ASSEMBLY MAXIMUM DESIGN | | PRESSURE OF -45 IS NOT COMPLIANT FOR ZONES 2 (-59.2) | | AND 3 (-89). | | |
|
|