Plan Review Details - Permit 07020425
Plan Review Stops For Permit 07020425
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-26 Cont ID  
Sent By shill Date 2007-02-26 Time 17:08 Rev Time 0.00
Received By shill Date 2007-02-26 Time 17:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-20 Cont ID  
Sent By shill Date 2007-02-20 Time 10:26 Rev Time 0.00
Received By shill Date 2007-02-20 Time 10:26 Sent To  
Notes
2007-02-20 10:28:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2001
  
 1.)SELECT THE APPROVED ASSEMBLY YOU ARE USING FOR THE
 METAL ROOF.NOTE THAT ONLY ONE IS COMPLIANT FOR THE
 DESIGN PRESSURE OF ZONE 3, -89 PSF (SHEET S3).
  
 2.)THE ASSEMBLY YOU HAVE SELECTED FOR THE FLAT DECK
 REFERS TO GENERAL LIMITATION #9 WHICH DOES NOT ALLOW
 ENHANCED FASTENING.THE ASSEMBLY MAXIMUM DESIGN
 PRESSURE OF -45 IS NOT COMPLIANT FOR ZONES 2 (-59.2)
 AND 3 (-89).
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-23 Cont ID  
Sent By adarroug Date 2007-02-23 Time 09:40 Rev Time 0.00
Received By adarroug Date 2007-02-23 Time 09:40 Sent To B
Notes
2007-02-23 09:40:26TO "SHILL' DESK/RESUB