Plan Review Details - Permit 07020389
Plan Review Stops For Permit 07020389
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-20 Cont ID  
Sent By tgordon Date 2007-02-20 Time 14:33 Rev Time 0.00
Received By tgordon Date 2007-02-16 Time 14:22 Sent To  
Notes
2007-02-16 14:22:26TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-21 Cont ID  
Sent By tgordon Date 2007-02-21 Time 12:09 Rev Time 0.25
Received By tgordon Date 2007-02-21 Time 12:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-20 Cont ID  
Sent By tgordon Date 2007-02-20 Time 14:33 Rev Time 30.00
Received By tgordon Date 2007-02-20 Time 14:33 Sent To  
Notes
2007-02-20 14:40:09*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) PLEASE PROVIDE RETURN AIR TO BEDROOMS, BALANCED
 RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.