Plan Review Details - Permit 07020383
Plan Review Stops For Permit 07020383
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-17 Cont ID  
Sent By shill Date 2007-03-17 Time 13:20 Rev Time 0.00
Received By shill Date 2007-03-17 Time 13:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-07 Cont ID  
Sent By shill Date 2007-03-07 Time 11:35 Rev Time 0.00
Received By shill Date 2007-03-07 Time 11:35 Sent To  
Notes
2007-03-07 11:36:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)SEE ANCHOR SPACING LEGEND ON SHEET 8.NOTE 3
 SHOULD BE USED FOR SPANS GREATER THAN 8'6, REQUIRES 6"
 SPACING FOR DP LESS THAN 61.8, YOU HAVE SPECIFIED 8" ON
 THE INSTALLATION SCHEDULE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-13 Cont ID  
Sent By adarroug Date 2007-03-13 Time 15:07 Rev Time 0.00
Received By adarroug Date 2007-03-13 Time 15:07 Sent To B
Notes
2007-03-13 15:07:46TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-07 Cont ID  
Sent By shill Date 2007-03-07 Time 11:36 Rev Time 0.00
Received By shill Date 2007-02-15 Time 15:05 Sent To  
Notes
2007-02-15 15:05:31TO "MISC" BOX#1