Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-02-06 Cont ID  
Sent By rmcdouga Date 2008-02-06 Time 12:51 Rev Time 0.00
Received By rmcdouga Date 2008-02-06 Time 10:31 Sent To  
Notes
2008-02-06 10:35:102004 FBC W/2006 REVISIONS
 LEVEL 2 ALTERATION AND ADDITION
  
 REVISION TO ENCLOSE CARPORT INTO A GARAGE IS DENIED BY
 BUILDING
  
 1) THE VALUE OF THE REVISED WORK ($ 15,000.00) HAS BEEN
 ADDED TO THE PREVIOUS VALUE OF WORK. ADDITIONAL FEES OF
 $4
  
 2) WHEN MAKING REVISIONS TO APPROVED PLANS, THE NEW
 PLANS ARE REQUIRED TO CONTAIN THE INFORMATION ON THE
 OLD DRAWINGS THAT IS NOT BEING CHANGED, AS WELL AS, THE
 NEW INFORMATION. THE REVISED/NEW INFORMATION SHOULD BE
 CLOUDED AND LABELED WITH THE REVISION NUMBER. SEE FBC
 106.1.3* AND 106.1.1* CITY AMENDMENTS. NOTE: THESE
 PLANS NEED TO SHOW THE SCOPE OF WORK FOR THE ENTIRE
 PROJECT IN ADDITION TO THE REVISION TO ENCLOSE THE
 GARAGE. SOME OF THE INFORMATION FROM THE APPROVED PLANS
 WAS NOT SHOWN ON THE REVISED SHEET A-1.
  
 3) COMPLIED.
  
 4) THE WEST ELEVATION WAS ADDED TO PLANS. HOWEVER, THE
 EAST ELEVATION WAS ELIMINATED. PLEASE SHOW BOTH
 ELEVATIONS ON THE DRAWINGS. FBC 106.1.1* CITY
 AMENDMENTS.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE
 DOOR, THE SIDE SWING GARAGE DOOR, THE ROOF COVERING.
 SEE FAC RULE 9B-72. THE PRODUCT APPROVALS THAT WERE
 SUBMITTED ARE FOR GAF RIDGE CAP SHINGLES AND THEY WERE
 NOT APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 9)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) COMPLIED.
  
 11) SHOW COMPLIANCE WITHR302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL. PROJECTIONS EXTENDING
 INTO THE 6-FOOT (1829 MM) SEPARATION DISTANCE SHALL
 HAVE NOT LESS THAN 1-HOUR FIRE-RESISTIVE CONSTRUCTION
 ON THE UNDERSIDE.
 R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE.
 THE NEW GARAGE WALLS APPEAR TO BE LESS THAN 6 FEET FROM
 THE PROPERTY LINE. PROVIDE A SURVEY/SITE PLAN THAT
 INDICATES THAT THE DISTANCE TO STRUCTURES ON THE
 ADJACENT PROPERTY WILL COMPLY WITH THE REQUIRED
 DISTANCES OR COMPLY WITH THE CODE SECTIONS LISTED
 ABOVE.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-01-10 Cont ID  
Sent By rmcdouga Date 2008-01-10 Time 09:58 Rev Time 0.00
Received By rmcdouga Date 2008-01-10 Time 07:04 Sent To Z
Notes
2008-01-10 10:50:462004 FBC W/2006 REVISIONS
 LEVEL 2 ALTERATION AND ADDITION
  
 REVISION TO ENCLOSE CARPORT INTO A GARAGE IS DENIED BY
 BUILDING
  
 1) SPECIFY THE VALUE OF THE ADDITIONAL WORK (CURRENTLY
 $21,013.00) AND PAY ADDITIONAL PERMIT FEES. SEE FBC
 108.1* AND 108.2* CITY AMENDMENTS.
  
 2) WHEN MAKING REVISIONS TO APPROVED PLANS, THE NEW
 PLANS ARE REQUIRED TO CONTAIN THE INFORMATION ON THE
 OLD DRAWINGS THAT IS NOT BEING CHANGED, AS WELL AS, THE
 NEW INFORMATION. THE REVISED/NEW INFORMATION SHOULD BE
 CLOUDED AND LABELED WITH THE REVISION NUMBER. SEE FBC
 106.1.3* AND 106.1.1* CITY AMENDMENTS. NOTE: THESE
 PLANS NEED TO SHOW THE SCOPE OF WORK FOR THE ENTIRE
 PROJECT IN ADDITION TO THE REVISION TO ENCLOSE THE
 GARAGE. SOME OF THE INFORMATION FROM THE APPROVED PLANS
 WAS NOT SHOWN ON THE REVISED SHEET A-1.
  
 3) COMPLIED.
  
 4) THE WEST ELEVATION WAS ADDED TO PLANS. HOWEVER, THE
 EAST ELEVATION WAS ELIMINATED. PLEASE SHOW BOTH
 ELEVATIONS ON THE DRAWINGS. FBC 106.1.1* CITY
 AMENDMENTS.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE
 DOOR, THE SIDE SWING GARAGE DOOR, THE ROOF COVERING.
 SEE FAC RULE 9B-72. THE PRODUCT APPROVALS THAT WERE
 SUBMITTED ARE FOR GAF RIDGE CAP SHINGLES AND THEY WERE
 NOT APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 9)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) COMPLIED.
  
 11) SHOW COMPLIANCE WITHR302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL. PROJECTIONS EXTENDING
 INTO THE 6-FOOT (1829 MM) SEPARATION DISTANCE SHALL
 HAVE NOT LESS THAN 1-HOUR FIRE-RESISTIVE CONSTRUCTION
 ON THE UNDERSIDE.
 R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE.
 THE NEW GARAGE WALLS APPEAR TO BE LESS THAN 6 FEET FROM
 THE PROPERTY LINE. PROVIDE A SURVEY/SITE PLAN THAT
 INDICATES THAT THE DISTANCE TO STRUCTURES ON THE
 ADJACENT PROPERTY WILL COMPLY WITH THE REQUIRED
 DISTANCES OR COMPLY WITH THE CODE SECTIONS LISTED
 ABOVE.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-11-26 Cont ID  
Sent By rmcdouga Date 2007-11-26 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2007-11-26 Time 07:22 Sent To Z
Notes
2007-11-26 10:40:112004 FBC W/2006 REVISIONS
 LEVEL 2 ALTERATION AND ADDITION
  
 REVISION TO ENCLOSE CARPORT INTO A GARAGE IS DENIED BY
 BUILDING
  
 1) SPECIFY THE VALUE OF THE ADDITIONAL WORK (CURRENTLY
 $21,013.00) AND PAY ADDITIONAL PERMIT FEES. SEE FBC
 108.1* AND 108.2* CITY AMENDMENTS.
  
 2) WHEN MAKING REVISIONS TO APPROVED PLANS, THE NEW
 PLANS ARE REQUIRED TO CONTAIN THE INFORMATION ON THE
 OLD DRAWINGS THAT IS NOT BEING CHANGED, AS WELL AS, THE
 NEW INFORMATION. THE REVISED/NEW INFORMATION SHOULD BE
 CLOUDED AND LABELED WITH THE REVISION NUMBER. SEE FBC
 106.1.3* AND 106.1.1* CITY AMENDMENTS.
  
 3) THE DETAILS ON SHEET D-1 DO NOT CORRESPOND WITH THE
 FRONT ELEVATION SHOWN ON A-1. THE ELEVATION SHOWS A
 GABLE AT THE RIGHT SIDE. PLEASE CLARIFY. FBC 106.1.1*
 CITY AMENDMENTS
  
 4) THE RIGHT SIDE ELEVATION IS NOT LABELED ON SHEET
 A-1. FBC 106.1.1* CITY AMENDMENTS
  
 5) SPECIFY THE SIZE AND SPACING OF THE ROOF RAFTERS.
 FBC 106.1.1* CITY AMENDMENTS
  
 6) SPECIFY THE SPACING OF THE 2 X 6 WALL FRAMING. FBC
 106.1.1* CITY AMENDMENTS
  
 7) SPECIFY THE WALL COVERING FOR THE GABLE END ON THE
 RIGHT ELEVATION. FBC 106.1.1* CITY AMENDMENTS
  
 8) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE
 DOOR, THE SIDE SWING GARAGE DOOR, THE ROOF COVERING.
 SEE FAC RULE 9B-72.
  
 9)106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) THE ROOF SHEATHING NAILING INFORMATION ON SHEET D-1
 IS INCORRECT. PLEASE REVISE. ROOF SHEATHING IS REQUIRED
 TO BE IN ACCORDANCE WITH SECTION R803.2.3.1 OF 2006
 REVISIONS TO 2004 FBC RESIDENTIAL CODE. WOOD STRUCTURAL
 PANEL SHEATHING SHALL BE FASTENED TO ROOF FRAMING WITH
 8D RING-SHANK NAILS AT 6 INCHES ON CENTER AT EDGES AND
 6 INCHES ON CENTER AT INTERMEDIATE FRAMING. SPACING OF
 RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN
 NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND
 SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-07-11 Cont ID  
Sent By rmcdouga Date 2007-07-11 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2007-07-11 Time 07:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-07-06 Cont ID  
Sent By rmcdouga Date 2007-07-06 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2007-07-06 Time 09:18 Sent To  
Notes
2007-07-06 10:44:39DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE SYSTEM THAT WAS SELECTED FOR THE FIRESTONE
 MODIFIED ROOF SYSTEM ON PAGE 31 OF NOA 05-0830.10, DOES
 NOT ALLOW ENHANCED FASTENING TO INCREASE THE DESIGN
 PRESSURE. THEREFORE, THE CALCULATIONS FROM THE ENGINEER
 FOR ENHANCED FASTENING ARE NOT ALLOWED. SEE LIMITATION
 #9 ON PAGE 34 OF THE NOA. ONE SET OF THE ENGINEER'S
 CALCULATIONS HAVE BEEN RETAINED.
  
 3) THE ENERGY CALCULATION FORM THAT WAS SUBMITTTED IS
 OUTDATED. SUBMIT THE CURRENT ONE, WHICH IS FORM
 600C-04.
  
 4) THE OWNER/ AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-26 Cont ID  
Sent By rmcdouga Date 2007-04-26 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2007-04-26 Time 06:52 Sent To  
Notes
2007-04-26 10:17:44DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO CLEAR AND LEGIBLE COPIES OF ALL PRODUCT
 APPROVALS. NOTE: THESE WILL BE COPIED INTO FILES FOR
 RECORD RETENTION. THEREFORE, THEY MUST BE CLEAR AND
 READABLE.
  
 4)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. SEE THE FL. COVERSHEET FOR THE FIRESTONE ROOFING
 MATERIAL ATTACHED TO THIS REVIEW.
  
 5)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE LETTER FROM THE
 DESIGNER OF RECORD DOES NOT INCLUDE ALL OF THE ITEMS
 REQUIRED TO HAVE PRODUCT APPROVALS SUBMITTED BY RULE
 9B-72.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK, THE
 OUTSWING EXTERIOR GARAGE DOOR, THE 8' X 7' OVERHEAD
 GARAGE DOOR, THE SIMPSON AND USP CONNECTORS AND THE
 SINGLE HUNG WINDOWS.
  
 7) THE PRODUCT APPROVAL NOA SUBMITTED FOR THE PGT
 SGD-70, SLIDING GLASS DOOR, HAS PAGES OF THE NOA THAT
 ARE ILLEGIBLE. THE ENTIRE REPORT MUST BE LEGIBLE.
  
 8)SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE NOA FOR THE FIRESTONE MODIFIED ROOF SYSTEM WILL
 BE INSTALLED. INDICATE THE FASTENING OPTION THAT WILL
 BE USED AND DESIGN PRESSURE FOR THE SELECTED ASSEMBLY.
 CIRCLE THE APPROPRIATE ITEMS ON THE NOA. THE REQUIRED
 UPLIFT PRESSURES ARE -59.2 FOR ROOF ZONE 2 AND -89.0
 FOR ROOF ZONE 3. IF THE DESIGN PRESSURES ARE TOO LOW
 FOR THESE AREAS, SUBMIT RAS 117 CALCULATIONS PER
 GENERAL LIMITATION #7. SEE PAGE 34 OF THE NOA.
  
 9) NO ENERGY CALCULATIONS WERE SUBMITTED. PLEASE SUBMIT
 THE 2004 FORMS # 600C-04 . THE OWNER/AGENT IS REQUIRED
 TO SIGN THE ENERGY CALC. FORM. SEE FBC CHAPTER 13.
  
 10) AN EMERGENCY ESCAPE AND RESCUE OPENING TO THE
 EXTERIOR REQUIRED BY FBC R310 MUST BE PROVIDED AT THE
 EXISTING BEDROOM ADJACENT TO THE ADDITION WHICH HAS THE
 REAR WINDOWSTHAT ARE BEING ENCLOSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-29 Cont ID  
Sent By rmcdouga Date 2007-03-29 Time 07:27 Rev Time 0.00
Received By rmcdouga Date 2007-03-29 Time 07:27 Sent To  
Notes
2007-03-29 09:30:00DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO LEGIBLE COPIES OF THE PRODUCT APPROVALS.
  
 4)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 5)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK AND
 SINGLE HUNG WINDOW.
  
 7) THE PRODUCT APPROVAL NOA SUBMITTED FOR THE PGT
 SGD-70, SLIDING GLASS DOOR, HAS BEEN REVISED BY NOA #
 06-0523.03. SUBMIT CURRENT NOA.
  
 8)SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE NOA FOR THE FIRESTONE MODIFIED ROOF SYSTEM WILL
 BE INSTALLED. INDICATE THE FASTENING OPTION THAT WILL
 BE USED AND DESIGN PRESSURE FOR THE SELECTED ASSEMBLY
 BY CIRCLING THE APPROPRIATE ITEMS ON THE NOA. THE
 REQUIRED UPLIFT PRESSURES ARE -59.2 FOR ROOF ZONE 2 NAD
 -89.0 FOR ROOF ZONE 3. IF THE DESIGN PRESSURES ARE TOO
 LOW FOR THESE AREAS, SUBMIT RAS 117 CALCULATIONS IF
 ALLOWED BY GENERAL LIMITATION #7 ON PAGE 34 OF THE
 NOA.
  
  
 9) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 10) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS:
 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS
 THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE
 INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH
 RAMPS ONLY.
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES,
 THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR
 FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5.MASONRY VENEERS.
  
 11) DETAIL F1 ON S1 SHOWS A 1-1/2" X 8" RECESS AT THE
 EXTERIOR OF THE MONOLITHIC FOUNDATION AND THE WALL
 SECTION ON D1 DOES NOT. PLEASE CLARIFY.
  
 12) SHOW COMPLIANCE WITH R301.2.1.2 INTERNAL PRESSURE.
  
 WINDOWS IN BUILDINGS LOCATED IN WIND-BORNE DEBRIS
 REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM
 WIND-BORNE DEBRIS OR THE BUILDING SHALL BE DESIGNED AS
 A PARTIALLY ENCLOSED BUILDING IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING . GLAZED OPENING
 PROTECTION FOR WIND-BORNE DEBRIS SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM E 1996
 AND OF ASTM E 1886, SSTD 12, ,OR TAS 201, 202 AND 203
 REFERENCED THEREIN.
  
 13) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1 / 8
 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 14) SPECIFY THE LENGTH OF THE ROOF OVERHANG. SEE R320.7
 PROTECTION AGAINST TERMITES AND DECAY. CONDENSATE LINES
 AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT
 AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY
 UNDERGROUND PIPING, TAIL EXTENSIONS OR SPLASH BLOCKS.
 GUTTERS WITH DOWN SPOUTS ARE REQUIRED ON ALL BUILDINGS
 WITH EAVES OF LESS THAN 6 INCHES HORIZONTAL PROJECTION
 EXCEPT FOR GABLE END RAKES OR ON A ROOF ABOVE ANOTHER
 ROOF.
  
 15) PROVIDE STRUCTURAL DETAILS OF THE EXISTING PORCH,
 PART OF WHICH IS BEING ENCLOSED.
  
 16) THE WRONG ENERGY CALC. FORMS WERE SUBMITTED. PLEASE
 SUBMIT THE 2004 FORMS # 600C-04 . THE OWNER/AGENT IS
 REQUIRED TO SIGN THE ENERGY CALC. FORM. SEE FBC CHAPTER
 13.
  
 17) SPECIFY THE ROOF SHEATHING FASTENER SPACING.ROOF
 SHEATHING IS REQUIRED TO BE IN ACCORDANCE WITH SECTION
 R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC RESIDENTIAL
 CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED
 TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. SPACING OF RING-SHANK FASTENERS SHALL BE 4
 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR
 GREATER DESIGNWIND SPEEDS IN ACCORDANCE WITH FIGURE
 R803.2.3.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-07 Cont ID  
Sent By btrobaug Date 2008-01-07 Time 14:01 Rev Time 0.00
Received By btrobaug Date 2008-01-07 Time 12:49 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-11-21 Cont ID  
Sent By btrobaug Date 2007-11-21 Time 07:32 Rev Time 0.00
Received By btrobaug Date 2007-11-21 Time 06:47 Sent To B
Notes
2007-11-21 07:32:21 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET E-1 IS INCOMPLETE. THE WORK ORIGINALLY
 PERMITTED IS NOT SHOWN. THIS SHEET CANNOT BE REPLACED
 WITH A PARTIAL. 106.1.1 FBC AS AMENDED. INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS ARE PERMITTED TO BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL (SEE ALSO SECTION 106.3.5).
  
 2} THE VALUE OF THE ADDITIONAL WORK MUST BE ADDED TO
 THE ORIGINAL FEES. ADJUST THE VALUE AT THE PERMIT
 CLERK?S DESK, AND PAY THE DIFFERENCE IN FEES PRIOR TO
 RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-04 Cont ID  
Sent By btrobaug Date 2007-06-04 Time 13:32 Rev Time 0.33
Received By btrobaug Date 2007-06-04 Time 12:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-25 Cont ID  
Sent By btrobaug Date 2007-04-25 Time 12:40 Rev Time 0.00
Received By btrobaug Date 2007-04-25 Time 12:30 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-03-06 Cont ID  
Sent By btrobaug Date 2007-03-06 Time 16:23 Rev Time 0.50
Received By btrobaug Date 2007-03-06 Time 16:12 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-01-30 Cont ID  
Sent By adarroug Date 2008-01-30 Time 12:33 Rev Time 0.00
Received By adarroug Date 2008-01-30 Time 12:33 Sent To Z
Notes
2008-01-30 12:33:42TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 16:43 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 16:43 Sent To E
Notes
2008-01-04 16:43:25TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 09:10 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 09:10 Sent To E
Notes
2007-11-15 09:11:16TO "BTROBAUGH" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-07-10 Cont ID  
Sent By adarroug Date 2007-07-10 Time 10:36 Rev Time 0.00
Received By adarroug Date 2007-07-10 Time 10:36 Sent To B
Notes
2007-07-10 10:36:44TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 08:17 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 08:17 Sent To E
Notes
2007-06-01 08:17:54TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 16:23 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 16:23 Sent To  
Notes
2007-05-22 16:24:59TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 14:29 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 14:29 Sent To E
Notes
2007-04-20 14:29:39TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 16:15 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 16:15 Sent To Z
Notes
2007-04-16 16:15:25TO "Z" BOX/RESUB--NEW SHEETS FOR "E"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 13:56 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 13:56 Sent To E
Notes
2007-02-22 13:57:52TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-29 Cont ID  
Sent By rmcdouga Date 2007-03-29 Time 07:28 Rev Time 0.00
Received By rmcdouga Date 2007-02-14 Time 15:19 Sent To  
Notes
2007-02-14 15:27:24TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-03-07 Cont ID  
Sent By tgordon Date 2007-03-07 Time 13:41 Rev Time 0.15
Received By tgordon Date 2007-03-07 Time 13:41 Sent To P
Notes
2007-03-07 13:42:06NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-01-08 Cont ID  
Sent By mperson Date 2008-01-08 Time 14:35 Rev Time 0.00
Received By mperson Date 2008-01-08 Time 14:35 Sent To B
Notes
2008-01-08 14:37:00REVISION: SHEET E-1, SANITARY ISOMETRIC RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-06-14 Cont ID  
Sent By mperson Date 2007-06-14 Time 11:35 Rev Time 0.20
Received By mperson Date 2007-06-14 Time 11:35 Sent To B
Notes
2007-06-14 11:36:35NOTE: NEW SHEET.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-25 Cont ID  
Sent By mperson Date 2007-04-25 Time 14:26 Rev Time 0.33
Received By mperson Date 2007-04-25 Time 14:26 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By mperson Date 2007-03-09 Time 10:06 Rev Time 0.45
Received By mperson Date 2007-03-09 Time 10:06 Sent To B
Notes
2007-03-09 11:16:14DENIED
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: SHEET E-1 ISOMETRIC SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN ON SHEET A-1. SHEET A-1
 INDICATES A NEW KITCHEN WITH A DOUBLE BOWL KITCHEN SINK
 WITH DISHWASHER BUT ON SHEET E-1 ISOMETRIC SANITARY
 RISER DIAGRAM THE WASTE PIPING TO THE NEW KITCHEN IS
 NOT INDICATED. PLEASE REFERENCE THE ATTACHED CORRECTED
 ISOMETRIC SANITARY RISER DIAGRAM TO THE PLUMBING
 COMMENTS THAT REFLECTS THE FLOOR PLAN AND IS CODE
 COMPLIANT FOR THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 6 Status F Date 2008-02-01 Cont ID  
Sent By adavila Date 2008-02-01 Time 13:15 Rev Time 0.00
Received By adavila Date 2008-01-30 Time 17:13 Sent To B
Notes
2008-02-01 13:15:56PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. THE DIMENSIONS SHOWN ON THE SURVEY SUBMITTED WITH
 THIS REVISION DO NOT MATCH THE DIMENSIONS SHOWN ON THE
 PREVIOUSLY SUBMITTED SURVEY.PLEASE CLARIFY.
  
 2. REPEAT COMMENT - SETBACK DIMENSIONS SHOWN ON THE
 SITE PLAN DO NOT MATCH THE SETBACK DIMENSIONS SHOWN ON
 THE SURVEY.SETBACK DIMENSIONS WERE REDLINED ON THE
 SITE PLAN OF THE APPROVED PERMIT.
  
 3. THERE IS A DISCREPANCY BETWEEN THE ROOF OVERHANG
 DIMENSION SHOWN ON THE SURVEY AND THE OVERHANG
 DIMENSION SHOWN ON THE PLANS.PLEASE CLARIFY.PROVIDE
 THE ROOF OVERHANG DIMENSION OF THE EXISTING CARPORT.
  
 4. ACCORDING TO THE RESUBMITTED PACKET, THE WORK VALUE
 INCREASED BY $15,000.PER SECTION 94-441(C)(2),
 ALTERATIONS WHICH EXCEED 50% OF THE VALUE OF THE
 STRUCTURE SHALL COMPLY WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS.PLEASE NOTE IN THE
 EVENT THAT THE WORK VALUE INCREASES AGAIN.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 5 Status F Date 2008-01-15 Cont ID  
Sent By adavila Date 2008-01-15 Time 10:55 Rev Time 0.00
Received By adavila Date 2008-01-11 Time 17:06 Sent To I
Notes
2008-01-15 10:55:48PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. REPEAT COMMENT - PROVIDE 2 COPIES OF A CURRENT
 SURVEY.SURVEY SHALL SHOW WIDTH, DEPTH AND SETBACK
 DIMENSIONS OF THE EXISTING CARPORT, AS WELL AS SETBACK
 DIMENSIONS OF THE EXISTING STRUCTURE.
 A. SURVEY DOES NOT SHOW DIMENSIONS OF THE EXISTING
 CARPORT, INCLUDING ROOF OVERHAND PROJECTIONS.
 B. ONLY 1 COPY OF THE SURVEY WAS SUBMITTED WITH THIS
 APPLICATION.
  
 2. REPEAT COMMENT - PROVIDE 2 COPIES OF A SITE PLAN
 SHOWING ALL SETBACK DIMENSIONS OF THE EXISTING
 STRUCTURE AND THE PROPOSED GARAGE.
 A. SETBACK DIMENSIONS DO NOT MATCH THE SETBACK
 DIMENSIONS SHOWN ON THE SURVEY.
 B. SETBACK DIMENSIONS TO THE PROPOSED GARAGE ARE NOT
 SHOWN ON THE SITE PLAN.
  
 3. PROVIDE ROOF OVERHAND DIMENSION ALONG THE NORTH AND
 WEST BUILDING FA?ADES OF THE GARAGE.PLEASE NOTE THAT
 ROOF OVERHANGS MAY NOT PROJECT FURTHER THAN 3 FEET INTO
 A SETBACK, OR FURTHER THAN THE EXISTING ROOF OVERHANG
 PROJECTION.
  
 4. REAR ELEVATION DOES NOT MATCH PROPOSED PLANS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 4 Status F Date 2007-11-28 Cont ID  
Sent By adavila Date 2007-11-28 Time 14:18 Rev Time 0.00
Received By adavila Date 2007-11-28 Time 13:41 Sent To I
Notes
2007-11-28 14:22:00PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.PROVIDE 2 COPIES OF A CURRENT SURVEY.SURVEY SHALL
 SHOW WIDTH, DEPTH AND SETBACK DIMENSIONS OF THE
 EXISTING CARPORT, AS WELL AS SETBACK DIMENSIONS OF THE
 EXISTING STRUCTURE.
  
 2.PROVIDE 2 COPIES OF A SITE PLAN SHOWING ALL SETBACK
 DIMENSIONS OF THE EXISTING STRUCTURE AND THE PROPOSED
 GARAGE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-05-30 Cont ID  
Sent By adavila Date 2007-05-30 Time 13:04 Rev Time 0.00
Received By adavila Date 2007-05-23 Time 15:41 Sent To I
Notes
2007-05-30 13:04:30PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-04-18 Cont ID  
Sent By adavila Date 2007-04-18 Time 18:27 Rev Time 0.00
Received By adavila Date 2007-04-17 Time 08:55 Sent To Z
Notes
2007-04-18 18:27:29PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE ALL SETBACK DIMENSIONS FROM PROPERTY LINE ON
 SITE PLAN (REPEAT COMMENT).
 A. SETBACK DIMENSIONS TO THE WEST PROPERTY LINE ARE NOT
 SHOWN ON SITE PLAN.
  
 2. SETBACK DIMENSIONS ON SITE PLAN DO NOT MATCH THOSE
 INDICATED ON THE SURVEY.
 A. ACCORDING TO THE SURVEY THE EXISTING STRUCTURE HAS A
 7.15 FOOT SETBACK TO THE EAST PROPERTY LINE AT THE
 FRONT OF THE HOUSE.SITE PLAN SHOWS A 6.5 FOOT
 SETBACK.
  
 3. PURSUANT TO SECTION 94-72 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, MINIMUM SIDE SETBACK IS 5
 FEET, 15 FEET TOTAL.NEW GARAGE ADDITION SHALL MEET
 THIS REQUIREMENT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-22 Cont ID  
Sent By adavila Date 2007-02-22 Time 08:43 Rev Time 0.00
Received By adavila Date 2007-02-22 Time 08:43 Sent To I
Notes
2007-02-22 08:43:57PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PLEASE PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) SIGNED AND SEALED SURVEYS.THE
 SURVEY SHALL BE LESS THAN A YEAR OLD.
  
 3. PROVIDE DIMENSION BETWEEN PROPOSED ADDITION AND
 EXISTING ACCESSORY STRUCTURE.
  
 4. PROVIDE ALL SETBACK DIMENSIONS FROM PROPERTY LINE ON
 SURVEY AND SITE PLAN.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.