Plan Review Details - Permit 07020355
Plan Review Stops For Permit 07020355
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-11 Cont ID  
Sent By shill Date 2007-07-11 Time 10:07 Rev Time 0.00
Received By shill Date 2007-07-10 Time 16:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By shill Date 2007-05-07 Time 10:19 Rev Time 0.00
Received By shill Date 2007-05-07 Time 10:19 Sent To  
Notes
2007-05-07 11:23:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 ***PLAN CHECK ONLY***
  
 1-5.)ADDRESSED.
  
 6.)PLATFORM DETAIL EL X-1,2, V13, NO GUARDS SHOWN
 FBC1012.THIS COMMENT APPLIES TO OTHER SHEETS SUCH AS
 EL X-3,4.NOTE THAT THE "HANDRAIL" PLAN DOES NOT HAVE
 CROSS SECTIONS REFERRING TO THESE ELEVATIONS SO I
 CANNOT DETERMINE IF THE HANDRAIL (WHICH MAY ALSO SERVE
 AS GUARDRAILS?) IS TO BE INSTALLED IN THIS LOCATION AND
 WAS OMITTED FOR CLARITY, OR IF THE DESIGN INTENT IS FOR
 THE PLATFORM OPEN SIDES.SEE FBC1012.1, FBC1028.
  
 2ND REVIEW - A NOTE WAS ADDED STATING THAT PLATFORMS
 OVER 48" IN HEIGHT WILL HAVE HANDDRAILS.SEE
 FBC1012.1, GUARDS REQUIRED (IN ADDITION TO OTHER
 LOCATIONS WHICH MAY BE APPLICABLE) ON INDUSTRIAL
 EQUIPMENT PLATFORMS OVER 30 INCHES ABOVE THE FLOOR.
 PLEASE NOTE THAT THERE IS A DIFFERENCE BETWEEN A
 HANDRAIL AND A GUARDRAIL FBC1002. FBC1015.2
 ADDRESSES MECHANICAL EQUIPMENT PLATFORMS SPECIFICALLY.
  
 7.)SHOW ALL REQUIRED GUARDS ON THE PLAN.FOR
 INSTANCE, SEE ELEVATIONS X-3,4.SEE FBC1012, 1028.
  
 2ND REVIEW - A PLAN WAS PROVIDED BUT THE NOTE (48" HIGH
 PLATFORMS) CONFLICTS WITH CODE REQUIREMENTS OF 30".
 PLEASE REVISE THE NOTE AND REVISE HANDRAIL/GUARDRAIL
 PLAN AS REQUIRED.
  
 8.)1ST REVIEW - ARE ALL HANDRAILS SHOWN ON L1 TO ALSO
 SERVE AS GUARDRAILS?THEY APPEAR TO BE AT PLATFORM
 AREAS; HANDRAILS ARE NOT REQUIRED FOR PLATFORMS BUT
 GUARDS (GUARDRAILS) ARE.SEE OTHER COMMENTS.
  
 2ND REVIEW - THE RESPONSE, "THIS SAFETY RAIL IS FOR
 MAINTENANCE PURPOSES OF THE CONVEYOR ONLY" DOES NOT
 ADDRESS THE COMMENT.THE GUARDRAILS ARE REQUIRED,
 HANDRAIL REQUIREMENTS ARE NOT CLEAR.SEE OTHER
 COMMENTS.
  
 9.)1ST REVIEW - SEE ELEVATIONS X-1,2, SECTION DETAIL
 V7, 3.1. THIS DETAIL IS TOO SMALL TO READ.THE SHEETS
 ARE LABELED BUT NOT NUMBERED.DOES THIS REFER TO SHEET
 3.1 (NO 3.1 IN THE SET)?ARCHITECTURAL STANDARDS ARE
 FOR DETAIL AND SECTION INDICATORS TO REFER TO DETAIL
 AND PAGE, BUT THE DETAILS PROVIDED REFER TO SHEETS
 WHICH ARE NOT IN THE PACKAGE.PLEASE EITHER PROVIDE
 STANDARD DETAIL AND SECTION INDICATORS OR ADVISE AS TO
 HOW I COULD BEST UNDERSTAND THE PLAN.
  
 2ND REVIEW - THE SHEET PROVIDED DOES NOT HAVE A TITLE
 BLOCK AND IS NOT SEALED.PLEASE INCORPORATE ALL
 NECESSARY DETAILS INTO THE PLAN AND REMOVE UNNECESSARY
 DETAILS.OTHER SHEETS HAVE SMALL ILLEGIBLE DETAILS.
 EITHER REMOVE FROM THE PLAN OR ENLARGE SO THAT THEY ARE
 LEGIBLE.
  
 10.) ADDRESSED, BUT PLEASE SEE ELECTRIC COMMENTS.
  
 11.) THE PREVIOUS COMMENT REQUESTED CLARIFICATION FOR
 THE PURPOSE OF THE WALKS AND LANDINGS.THE PLAN NOW
 STATES IN GENERAL NOTES THAT "ALL PLATFORMS ARE FOR
 MAINTENANCE PURPOSES ONLY."PLEASE FURTHER DESCRIBE
 THE USE OF THE LANDINGS AND WALKS."MAINTENANCE ONLY";
 IS THIS TO OCCUR ON OCCASION SUCH AS ONCE A MONTH, OR
 SEVERAL TIMES IN THE DAY?COMPLIANCE WITH VERTICAL
 ACCESSIBILITY (EXCEPTION) APPEARS TO BE CLEAR, BUT
 EGRESS REQUIREMENTS ARE NOT CLEAR.
  
 PLEASE INCORPORATE THIS INFORMATION ON THE ISO SHEET
 WHICH MAKES IT APPEAR THAT THE LANDINGS ARE WORK
 AREAS.
  
  
 NEW COMMENTS;
  
 12.)CLEARLY INDICATE ALL CHANGES TO THE PLAN WITH
 CLOUDS AND REVISION NUMBERS. SEVERAL SHEETS CHANGED
 WITH NO REVISIONS SHOWN.
  
 13.)SHEET A, ELEVATIONS X-1, 2 HAS A DETAIL V7 3.1
 WHICH IS TOO SMALL TO BE LEGIBLE.ALL INFORMATION ON
 THE PLAN IS TO BE LEGIBLE.CHECK ALL SHEETS, ALL
 DETAILS.
  
 14.)THE GENERAL NOTES REFER TO THE CONVEYOR SAFETY
 CABLE RAIL LOCATIONS.REQUIRED GUARDS ARE TO COMPLY
 WITH FBC1012, FBC1607.7.PLEASE STATE STRUCTURAL
 DESIGN CRITERIA ON THE PLAN AND PROVIDE A DETAIL
 SHOWING COMPLIANCE WITH FBC1012.THE DETAIL AS DRAWN
 IS NOT TALL ENOUGH AND THE OPENINGS ARE TOO LARGE TO
 REJECT A 21" OBJECT.CODE COMPLIANCE IS NOT CLEAR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-03 Cont ID  
Sent By shill Date 2007-04-03 Time 08:43 Rev Time 0.00
Received By shill Date 2007-04-02 Time 17:49 Sent To  
Notes
2007-04-03 08:00:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)ALL INFORMATION REQUIRED BY FAC61G1-16-23.002, 003
 AND FAC61G15-23.002 ARE TO BE ON EACH SHEET.
  
 2.)ALL SHEETS ARE TO BE SIGNED, SEALED, DATED, FS471,
 FS481 WHEN SUBMITTED FOR PUBLIC RECORD.
  
 3.)DECLARE GOVERNING CODE.
  
 4.)INFORMATIONAL ONLY; THIS IS A PLAN CHECK.PERMIT
 APPLICATON REQUIRED.REVIEW WILL REMAIN IN "F"
 STATUS.
  
 5.)L3, SHOW TRAVEL DISTANCES AND PROVIDE A CODE
 SUMMARY (BUILDING TYPE, OCCUPANCY, TRAVEL DISTANCE,
 BUILDING AREA, OCCUPANT LOAD).
  
 6.)PLATFORM DETAIL EL X-1,2, V13, NO GUARDS SHOWN
 FBC1012.THIS COMMENT APPLIES TO OTHER SHEETS SUCH AS
 EL X-3,4.NOTE THAT THE "HANDRAIL" PLAN DOES NOT HAVE
 CROSS SECTIONS REFERRING TO THESE ELEVATIONS SO I
 CANNOT DETERMINE IF THE HANDRAIL (WHICH MAY ALSO SERVE
 AS GUARDRAILS?) IS TO BE INSTALLED IN THIS LOCATION AND
 WAS OMITTED FOR CLARITY, OR IF THE DESIGN INTENT IS FOR
 THE PLATFORM OPEN SIDES.SEE FBC1012.1, FBC1028.
  
 7.)SHOW ALL REQUIRED GUARDS ON THE PLAN.FOR
 INSTANCE, SEE ELEVATIONS X-3,4.SEE FBC1012, 1028.
  
 8.)ARE ALL HANDRAILS SHOWN ON L1 TO ALSO SERVE AS
 GUARDRAILS?THEY APPEAR TO BE AT PLATFORM AREAS;
 HANDRAILS ARE NOT REQUIRED FOR PLATFORMS BUT GUARDS
 (GUARDRAILS) ARE.SEE OTHER COMMENTS.
  
 9.)SEE ELEVATIONS X-1,2, SECTION DETAIL V7, 3.1. THIS
 DETAIL IS TOO SMALL TO READ.THE SHEETS ARE LABELED
 BUT NOT NUMBERED.DOES THIS REFER TO SHEET 3.1 (NO 3.1
 IN THE SET)?ARCHITECTURAL STANDARDS ARE FOR DETAIL
 AND SECTION INDICATORS TO REFER TO DETAIL AND PAGE, BUT
 THE DETAILS PROVIDED REFER TO SHEETS WHICH ARE NOT IN
 THE PACKAGE.PLEASE EITHER PROVIDE STANDARD DETAIL AND
 SECTION INDICATORS OR ADVISE AS TO HOW I COULD BEST
 UNDERSTAND THE PLAN.
  
 10.) CONTRACTOR HAS DECLARED VALUE OF $45,000.THIS IS
 TO INCLUDE ALL MATERIALS AND LABOR, FBC*108.3.
  
 11.)PLEASE CLARIFY THE PURPOSE OF THE WALKS AND
 LANDINGS.FROM ISO AND ELEVATIONS THIS APPEARS TO BE
 AN OCCUPIABLE WORK AREA, BUT DOES NOT MEET GENERAL
 EGRESS REQUIREMENTS OF FBC10 OR ACCESSIBILITY FBC11
 (VERTICAL ACCESSIBILITY, HANDRAILS, EGRESS, ETC.).SEE
 ALSO FBC11-4.1.3(5)(3) IF APPLICABLE.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 11:21 Rev Time 0.00
Received By dpalmer Date 2007-08-08 Time 12:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-06-23 Cont ID  
Sent By dpalmer Date 2007-06-23 Time 19:00 Rev Time 0.00
Received By dpalmer Date 2007-06-23 Time 18:36 Sent To  
Notes
2007-06-23 19:00:50*** UNSAT 3RD REVIEW ***
  
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO PLANS ONLY BEING SUBMITTED FOR *PLAN
 REVIEW*.
 PLEASE KNOW THAT PLANS ARE STILL NOT SUBMITTED FOR
 PERMIT AND WILL BE PLACED INTO A FAILED STATUS EVEN
 WHEN ALL CODE COMMENTS ARE ADDRESSED.
 VERIFICATION OF LICENSE INFORMATION, PERMIT VALUATION,
 CONTRACTING LICENSING AND CODES IN EFFECT AT THE TIME
 OF APPLICATION WILL ALL STILL NEED TO BE VERIFIED. IF
 THERE ARE ANY CODE CHANGES WHICH ARE ADOPTED BY THE
 STATE AND THE PERMIT APPLICATION HAS NOT BEEN MADE,
 THEN PLANS WILL FALL UNDER THE NEW CODES ADOPTED BY THE
 STATE WHICH MAY REQUIRE DESIGN CHANGES.
 ALL OF THESE ITEMS CAN NOT BE VERIFIED AT THIS TIME.
  
 2) NOTE:PLEASE SEE AS STATED ON PREVIOUS REVIEWS;
 PLEASE BE SURE ALL INFORMATION IN TITLE BLOCKS IS
 CORRECT.PLEASE SEE THERE IS NOW A DESIGNER OF RECORD
 CHANGE. PLEASE SEE THE ATTACHED PRINT OUT FROM THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION AS
 THE INFORMATION FOR THE ENGINEER OF RECORD ON TITLE
 BLOCKS DOES NOT MATCH THE STATE WEBSITE.
 PLEASE ADJUST AS THIS INFORMATION MUST MATCH.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-25 Cont ID  
Sent By dpalmer Date 2007-04-25 Time 14:28 Rev Time 0.00
Received By dpalmer Date 2007-04-25 Time 14:10 Sent To  
Notes
2007-04-25 14:28:32 
  
 ** UNSAT2ND REVIEW**
  
  
  
 1) NOTE: PLEASE SEE THAT PLANS ARE STILL ONLY BEING
 SUBMITTED FOR *PLAN REVIEW* ONLY AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT APPLICATION. PLEASE KNOW THAT EVEN
 IF ELECTRICAL WAS OK, THE PLANS WOULD STILL REMAIN IN A
 *F* STATUS UNTIL THE TIME THAT THE PERMIT APPLICATION,
 CONTRACTOR, VALUATION ETC CAN BE REVIEWED ALONG WITH
 FINAL DOCUMENTS.
  
 2) NOTE: PLEASE SEEINFORMATION ON TITLE BLOCKS FOR
 BOTH OF THE ENGINEER AND ARCHITECT AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODES 61G15-23.002, 61G1-16.004.
 PLEASE ALSO SEE FLORIDA STATUTES 471.023 AND 481.219
 WHERE APPLICABLE FOR REQUIRED FIRM LICENSE NUMBER(S).
 PLEASE SEE MISSING THE REQUIRED PRINTED NAME AND
 PRINTED LICENSE NUMBER OF DESIGNERS.
 PRINTED NAMES ARE REUIRED FOR ALL TITLE BLOCKS FOR
 ARCHITECT AND ENGINEER.
 ** REVIEW OF TITLE BLOCKS AND INFORMATION REQUIRED ON
 TITLE BLOCKS CAN NOT BE DONE AT THIS TIME.
 PLANS NOW CONTAIN TITLE BLOCKS, HOWEVER NOT COMPLETE
 WITH ALL INFORMATION AS REQUIRED.
  
 3) NOTE: PLEASE SEE MOST OF THE SEALS ON THE SHEETS FOR
 THE MEP ARE NOT CLEAR AND VISIBLE WITH ALL INFORMATION
 ON RAISED SEAL ESAILY READ.
 FAC 61G15-23.001.
  
 4) NOTE:THE VALUE IN RESPONSE LETTER MENTIONS WHEN
 APPLIED FOR PERMIT THE VALUE WILL BE 180K, HOWEVER
 PLEASE KNOW THAT THE VALUE SHALL INCLUDE ALL LABOR TO
 INSTALL AND VALUE FOR EQUIPMENT EVEN IF EQUIPMENT IS
 OWNER SUPPLIED. THIS VALUE SHOWN IS LOW FOR THIS
 SYSTEM.
 PLEASE KNOW THAT THE VALUE FOR THE COMPLETE SCOPE OF
 WORK FOR THE CONVEYOR SYSTEM, ELECTRICAL, ETC SHALL
 INCLUDE ALL LABOR AND MATERIALS EVEN IF EQUIPMENT,
 ELECTRICAL PANELS ETC ARE OWNER SUPPLIED. PLEASE ADJUST
 THE APPLIED VALUE FOR ALL WORK AS SHOWN. FBC 108.3
 ADMIN SECTION.
  
 5) NOTE: PLEASE PROVIDE MORE INFORMATION ON ELECTRICAL
 SYSTEM(S). PLEASE PROVIDE INFORMATION ON LISTINGS OF
 CONTROL BOARDS/PANELS FROM A NRTL.
 PLEASE KNOW THAT THE INFORMATION AS SHOWN ON BASE
 BUILDING FOR SUPPLY DOES NOT PROVIDE ENOUGH INFORMATION
 FOR THIS SYSTEM.
 110.3, 90.7.
 PLEASE LIST ON RECORD SET OF PLANS WHERE POWER ETC IS
 COMING FROM. THIS SHOULD CORRELATE WITH THE MAIN
 BUILDING PLANS SHOWING CIRCUITING ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-04 Cont ID  
Sent By dpalmer Date 2007-03-04 Time 15:38 Rev Time 0.00
Received By dpalmer Date 2007-03-04 Time 15:07 Sent To  
Notes
2007-03-04 15:40:41** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN
 SUBMITTED FOR *PLAN REVIEW* ONLY AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT APPLICATION. PLEASE KNOW THAT EVEN
 IF ELECTRICAL WAS OK, THE PLANS WOULD STILL REMAIN IN A
 *F* STATUS UNTIL THE TIME THAT THE PERMIT APPLICATION,
 CONTRACTOR, VALUATION ETC CAN BE REVIEWED ALONG WITH
 FINAL DOCUMENTS.
  
 2) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES
  
 3) NOTE: PLEASE SEE MISSING TITLE BLOCKS FOR BOTH OF
 THE ENGINEER AND ARCHITECT AS REQUIRED UNDER FLORIDA
 ADMINISTRATIVE CODES 61G15-23.002, 61G1-16.004. PLEASE
 ALSO SEE FLORIDA STATUTES 471.023 AND 481.219 WHERE
 APPLICABLE FOR REQUIRED FIRM LICENSE NUMBER(S). PLEASE
 SEE MISSING THE REQUIRED PRINTED NAME AND PRINTED
 LICENSE NUMBER OF DESIGNERS.
 ** REVIEW OF TITLE BLOCKS AND INFORMATION REQUIRED ON
 TITLE BLOCKS CAN NOT BE DONE AT THIS TIME.
  
 4) NOTE: PLEASE BE SURE ALL SEALS ARE CLEAR AND VISIBLE
 WITH ALL INFORMATION ON SAID SEAL. THE PE SEAL IS VERY
 FAINT AND INFORMATION IS NOT EASILY READ. 61G15-23.001
  
 5) NOTE: ***IMPORTANT***
 PLEASE SEE ATTACHED DOCUMENTATION FROM THE DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATION / STATE'S
 WEBSITE WHICH SHOWS THE LICENSE FOR JAMES PURDY, PE #
 14240 AS *DELINQUENT*/ EXPIRED.
 ONE SET OF PLANS TO BE RETAINED.
  
 6) NOTE: PLEASE KNOW THAT THE VALUE FOR THE COMPLETE
 SCOPE OF WORK FOR THE CONVEYOR SYSTEM, ELECTRICAL, ETC
 SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF
 EQUIPMENT, ELECTRICAL PANELS ETC ARE OWNER SUPPLIED.
 PLEASE ADJUST THE APPLIED VALUE FOR ALL WORK AS SHOWN.
 FBC 108.3 ADMIN SECTION.
  
 7) NOTE: PLEASE PROVIDE MORE INFORMATION ON ELECTRICAL
 SYSTEM(S). PLEASE PROVIDE INFORMATION ON LISTINGS OF
 CONTROL BOARDS/PANELS FROM A NRTL.
 110.3, 90.7.
 PLEASE LIST ON RECORD SET OF PLANS WHERE POWER ETC IS
 COMING FROM. THIS SHOULD CORRELATE WITH THE MAIN
 BUILDING PLANS SHOWING CIRCUITING ETC.
  
 8) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 9) NOTE: PLEASE SEE SEVERAL SHEETS FROM THE ARCHITECT
 IN EACH SET ARE NOT SIGNED, DATED AND SEALED AS
 REQUIRED. PLEASE SEE SOME SHEETS WHERE IT APPEARS THE
 DESIGNER STARTED TO SIGN PLANS AND STOPPED MID-POINT?
 481.221.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-24 Cont ID  
Sent By mawillia Date 2007-07-24 Time 13:32 Rev Time 0.00
Received By mawillia Date 2007-07-24 Time 12:41 Sent To  
Notes
2007-07-24 13:02:45*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEET A1.3 STAMPED,INITIALED, AND
 DATED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-08 Cont ID  
Sent By mawillia Date 2007-05-08 Time 13:31 Rev Time 0.00
Received By mawillia Date 2007-05-08 Time 13:01 Sent To  
Notes
2007-05-08 13:21:17*****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 1. THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK WILL
 BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.THE CONVEYOR SYSTEM SHALL NOT OBSTRUCT EXITS,
 ACCESS THERETO, EGRESS THEREFROM, OR VISIBILITY
 THEREOF.
  
 4.INDUSTRIAL EQUIPMENT ACCESS STAIRS THAT SERVE AS A
 COMPONENT OF THE MEANS OF EGRESS FROM THE INVOLVED
 EQUIPMENT SHALL BE PERMITTED IN ACCORDANCE WITH TABLE
 40.2.5.2.1 OF NFPA101.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By mawillia Date 2007-03-30 Time 17:43 Rev Time 0.00
Received By mawillia Date 2007-03-30 Time 16:19 Sent To  
Notes
2007-03-30 17:42:57*****DENIED*****
  
  
 1. THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK WILL
 BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.THE CONVEYOR SYSTEM SHALL NOT OBSTRUCT EXITS,
 ACCESS THERETO, EGRESS THEREFROM, OR VISIBILITY
 THEREOF.
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.INDUSTRIAL EQUIPMENT ACCESS STAIRS THAT SERVE AS A
 COMPONENT OF THE MEANS OF EGRESS FROM THE INVOLVED
 EQUIPMENT SHALL BE PERMITTED IN ACCORDANCE WITH TABLE
 40.2.5.2.1 OF NFPA101.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 14:14 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 14:14 Sent To E
Notes
2007-08-02 14:14:36TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-11 Cont ID  
Sent By adarroug Date 2007-06-11 Time 08:35 Rev Time 0.00
Received By adarroug Date 2007-06-11 Time 08:35 Sent To  
Notes
2007-06-22 16:34:37TO "COMM" BD#43
2007-06-11 08:35:59WAITING FOR"COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 12:02 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 12:02 Sent To  
Notes
2007-04-25 08:57:14TO "COMM" BD#52/PLANS ON RACK--1 ROLL
2007-04-23 12:02:24WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-03 Cont ID  
Sent By shill Date 2007-04-03 Time 08:59 Rev Time 0.00
Received By shill Date 2007-02-15 Time 14:19 Sent To  
Notes
2007-02-26 11:51:02TO "COMM" BD#45
2007-02-15 14:20:05WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 1 Status N Date 2007-02-28 Cont ID  
Sent By eschneid Date 2007-02-28 Time 17:08 Rev Time 0.00
Received By eschneid Date 2007-02-28 Time 17:08 Sent To  
Notes
***NONE***