Plan Review Details - Permit 07020339
Plan Review Stops For Permit 07020339
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2007-10-31 Cont ID  
Sent By lursu Date 2007-10-31 Time 09:16 Rev Time 0.00
Received By lursu Date 2007-10-31 Time 09:16 Sent To  
Notes
2007-10-31 10:18:42THE SITE ADDRESS FOR BLDG 2 IS CORRECT AS 5840 N
 FLAGLER DR.

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2007-05-08 Cont ID  
Sent By lursu Date 2007-05-08 Time 08:55 Rev Time 0.00
Received By lursu Date 2007-05-08 Time 08:55 Sent To  
Notes
2007-05-08 08:55:54THE UNITY OF TITLE WAS RECEIVED BY THIS DEPARTMENT. FOR
 BUILDING 2 A NEW ADDRESS WILL BEISSUED AS 5840 N
 FLAGLER DR .THIS ADDRESS WILL BE USED ONLY FOR THE
 PERMIT PURPOSES .THE TWO UNITS INSIDE THE BUILDING WILL
 RECEIVE UNIQUE SITE ADDRESSES .ON THE REVISED SITE
 PLANS AND APPLICATION PLEASE REFLECT THE NEW SITE
 ADDRESS FOR BUILDING 2.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-04-16 Cont ID  
Sent By lursu Date 2007-04-16 Time 14:44 Rev Time 0.00
Received By lursu Date 2007-04-16 Time 14:44 Sent To  
Notes
2007-04-16 14:45:17THE SAME COMMENTS DATED FEB 22, 2007 ARE APLLIED NOW
 .WHEN THE UOT IS RECEIVED THREE NEW ADDRESSES WILL BE
 ASSIGNED TO THESE NEW BUILDINGS.ALSO THE REVISED SITE
 PLANS AND PERMIT APPLICATIONS MUST HAVE THE CORRECT
 ADDRESS .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-02-22 Cont ID  
Sent By lursu Date 2007-02-22 Time 14:06 Rev Time 0.00
Received By lursu Date 2007-02-22 Time 14:06 Sent To  
Notes
2007-02-22 14:10:48THE UNITY OF TITLE IS REQUIRED FOR THE TWO PARCELS
 INVOLVED IN THIS PROJECT : 74434304060380070 &
 74434304060380040.
 BASED ON THE RECORDED UNITY OF TITLE AND THE APPROVED
 SITE PLANS ,NEW UNIQUE SITE ADDRESSES WILL BE ASSIGNED
 TO EACH OF THE THREE BUILDINGS.
 NOTE: THE LIST OF ADDRESSES FOR ALL THE UNITS FOR ALL
 THREE BUILDINGS MUST BE APPROVED BY THE SUPPORT
 SERVICES DEPARTMENT IN CHARGE OF ADDRESSING PRIOR TO
 RELEASE THE CERTIFICATE OF OCCUPANCY.
  
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-12-22 Cont ID  
Sent By jwitmer Date 2008-12-22 Time 11:39 Rev Time 0.77
Received By jwitmer Date 2008-12-22 Time 11:39 Sent To  
Notes
2008-12-22 11:39:36REVISON# 4 DATED 11-12-08

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-09-02 Cont ID  
Sent By lmartine Date 2008-09-02 Time 14:20 Rev Time 0.00
Received By lmartine Date 2008-09-02 Time 14:20 Sent To  
Notes
2008-09-02 14:30:31REVISION #4, OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-02-11 Cont ID  
Sent By jwitmer Date 2008-02-11 Time 15:51 Rev Time 0.77
Received By jwitmer Date 2008-02-11 Time 15:51 Sent To  
Notes
2008-02-11 15:52:18S1, S2 & S3

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-05 Cont ID  
Sent By jwitmer Date 2007-12-05 Time 09:16 Rev Time 1.22
Received By jwitmer Date 2007-12-05 Time 09:16 Sent To  
Notes
2007-12-05 09:18:42*** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 07020339
 ADDRESS: 5840 N FLAGLER DR
 CONT: SCOTCORP
 TELL # (561) 747-3800
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.106.1.1 ADMINISTRATIVE CODE/ 06.
  
 BUILDING PROVISOS:
  
 1) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 3) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 4) ROOFING PERMIT UNDER SEPERATE PERMIT, PRODUCT
 APPROVALS REVIEWED AS FOLLOWS:
 FLORIDA FILE NUMBER 618-R1/2004
 NOA# 03-0827.11
 SUBSYSTEM: SBS
 DECK TYPE: CONCRETE DECK, INSULATED, NEW CONSTRUCTION
 MAXIMUM DESIGN PRESSURE: -152.5
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-01 Cont ID  
Sent By jwitmer Date 2007-11-01 Time 16:11 Rev Time 2.22
Received By jwitmer Date 2007-11-01 Time 16:11 Sent To  
Notes
2007-11-01 16:12:34BUILDING PLAN REVIEW
 PERMIT: 07020339
 ADD: 5820 N FLAGLER BLDG# 2
 CONT: SCOT CORP INC
 TEL: (561)346-9888
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDTREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) BUILDING PROVISO: PROJECT IS LOCATED IN A A- 5,
 MINIMUM ELEVATION FINISH FLOOR
 @ 7'-6", THIS INCLUDES EXTERIOR A/C PADS.PROVIDE
 FLOOD ZONE ELEVATION CERTIFICATE FOR NEW CONSTRUTION
 WITH
 BASE FLOOD ELEVATION 7'-0" , CITY CODE REQUIRES AN
 ADDITIONAL 6".
  
 6)BUILDING PROVISO: 109.3.10* IMPACT OF
 CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
  
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 7) BUILDING PROVISO:
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 8) COMPLIED, SPECIAL INSPECTOR NOT REQUIRED.
  
 9) COMPLIED.
  
 10-13)COMPLIED.
  
 14)COMPLIED.
  
 15-18) COMPLIED.
  
 19) 2ND REQUEST,BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 20) SEE REMAINDER OF FEES DUE
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-12 Cont ID  
Sent By jwitmer Date 2007-06-12 Time 12:21 Rev Time 2.22
Received By jwitmer Date 2007-06-12 Time 12:21 Sent To PC
Notes
2007-06-12 12:41:42BUILDING PLAN REVIEW
 PERMIT: 07020339
 ADD: 5818 N FLAGLER BLDG# 2
 CONT: SCOT CORP INC
 TEL: (561)346-9888
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) BUILDING PROVISO: PROJECT IS LOCATED IN A A- 5,
 MINIMUM ELEVATION FINISH FLOOR
 @ 7'-6", THIS INCLUDES EXTERIOR A/C PADS.PROVIDE
 FLOOD ZONE ELEVATION CERTIFICATE FOR NEW CONSTRUTION
 WITH
 BASE FLOOD ELEVATION 7'-0" , CITY CODE REQUIRES AN
 ADDITIONAL 6".
  
 6)BUILDING PROVISO: 109.3.10* IMPACT OF
 CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 7) BUILDING PROVISO:
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 8)MAY REQUIRE A SPECIAL INSPECTOR:
 FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 X - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 9) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) COMPLIED.
 B) COMPLIED.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601. SHEET A01.01 INDICATES THIS TO BE A III-B
 TYPE OF CONSTRUCTION. THE BUILDING CODE IS A MINIMUM
 CODE THIS DESIGN IS TRUELY A 5B, IF YOU AS THE DESIGNER
 WANT TO DESIGN TO THE MORE RESTRICTIVE STANDARD, THEN
 WE WILL REQUIRE THE EQUIVALENT THICKNESS FROM THE BLOCK
 MANUFACTURER
 FOR A 2HR RATED BLOCK AS PER TABLE 601 BEARING WALLS.
 D-K)COMPLIED.
  
 10-13)COMPLIED.
  
 14) 2ND REQUEST,SHEET A201 INDICATES BETWEEN UNITS
 THE DESIGNER REQUIRES A 2HR FIRE RATED BLOCK, DETAIL#
 5, A800 INDICATESA UL DESIGN U-905 IF UL IS PRODUCING
 THE BLOCK THIS IS OK, THE BLOCK MANUFACTURER NEEDS TO
 SUPPLY THE EQUIVANT BLOCK THICKNESS WITH TYPE OF
 AGGRAGETE FOR A 2 HR RATED WALL BETWEEN UNITS.
  
 15) 2ND REQUEST,FL BLD CODE 1609.1.4/ R- 301.2.1 :
 COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD
 OR RESIDENT INSPECTOR) OF PRODUCT TESTING REPORTS,
 REPORTS WITH PROBLEMS ARE AS FOLLOWS:
 A) PGT "PW-701" PRINT COVERSHEET
 HIGHLIGHT GLASS TYPE TO
 BE USED IN THIS INSTALLATION
  
 B) SIMONTON CLIPPED MULLION
 LOW PRESSURE SEE END ZONES -72.8 , WINDOW TYPE "C"
  
 C) PGT CASEMENT LOW PRESSURE ZONE 5 SHEET 7 OF 13
 HIGHLIGHTED5 TYPES OF GLAZING THE HIGHEST PRESSURE IS
 -70 AND THE PRESSURE ZONE IS A -71.76.
  
 D) PGT ALUM FRENCH DOORS/ W SIDELIGHT-REQUIRES FLORIDA
 COVERSHEET AND ONLY ONE REORT SUBMITTED.
  
 E) GAF MODIFIED- SHEET 9 OF 40ARE THE SUB SYSTEMS,
 PLEASE CICLE OR HIGHLIGHT THE SECTION YOU ENTEND ON
 USING. NOTE THE PRESSURES AND LIMITATION FOR EACH
 SUBSYSTEM.
 ENHANCED FASTENING WILL BE NEEDED IF THE REPORT
 SELECTED HAS A DESIGN PRESSURE OF LESS THAN -138.44.
 NOTE ALSO FOR ENHANCED FASTENING IF LIMITATIN# 7 IS
 INDICATED THEN PROVIDE THE CALCULATION FOR RAS 117.
  
 16) 2ND REQUEST R-613.7.1/ 1707.4.5.1 MULLIONS OCCURING
 BETWEEN INDIVIDUAL WINDOWS AND GLASS DOOR ASSEMBLIES.
 TESTING REPORTS ARE REQUIRED BY AN APPROVED TESTING
 LABRATORY OR BE ENGINEERED.
  
 17) COMPLIED.
  
 18) 2ND REQUEST,THE DESIGNER MAY HAVE STAMPED THE
 PRODUCT AS REVIEWED , PLEASE SEE THE PROBLEMS OF THE
 PRODUCT APPROVALS LISTED ABOVE TO BE CORRECTED BEFORE
 RESUBMITTAL,WPB ADMIN CODE 106.3* PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 19) 2ND REQUEST,BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 20) CALCULATED VALUE.
  
 21) IN ADDRESSING THE NEW ADDRESS FOR THIS LOCATION
 PLEASE SEE THAT THE PERMIT APPLICATION WILL NEED TO
 HAVE THE ADDRESS CHANGED AS WELL AS THE PLANS!!!!
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By jwitmer Date 2007-03-15 Time 12:07 Rev Time 5.55
Received By jwitmer Date 2007-03-15 Time 12:07 Sent To  
Notes
2007-03-15 12:11:11BUILDING PLAN REVIEW
 PERMIT: 07020339
 ADD: 5818 N FLAGLER BLDG# 2
 CONT: SCOT CORP INC
 TEL: (561)346-9888
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL
 REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
 4) UNITY OF TITLE: THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 5)PROJECT IS LOCATED IN AN A- 5, MINIMUM ELEVATION
 FINISH FLOOR
 @ 7'-6", THIS INCLUDES EXTERIOR A/C PADS.
 PROVIDE FLOOD ZONE ELEVATION CERTIFICATE FOR NEW
 CONSTRUCTION WITH
 BASE FLOOD ELEVATION 7'-0", CITY CODE REQUIRES
 AN ADDITIONAL 6".
  
 6)109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER. THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCEL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 7) 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
  
 8) MAY REQUIRE A SPECIAL INSPECTOR:
 FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQ FT IN AREA
 X - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
  
  
  
 9) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) NUMBER OF BEDROOMS
 H) SQ. FT. LIV. SPACE/ FL
 I) SQ. FT. FOOTPRINT
 J) SQ. FT. UNDER ROOF (TOTAL)
 J) FLOOD ZONE
 K) FLOOD ELEVATION
  
 10) S-02 THE FOUNDATION INDICATES IT IS DESIGNED TO THE
 REQUIREMENTS OF 1603.1-BLDG
 BUT NO WHERE DOES THE BUILDING STATE IT MEETS THE SAME
 STANDARD.
 2006 FL. BLDG CODE 1603.1.4-BLDG /THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 11) NOTE THE REMAINDER OF THIS REVIEW WILL BE COMPLETED
 UNDER THE 2004/ 2006 FLORIDA BUILDING CODE -
 RESIDENTIAL, FOR ONE & TWO RESIDENTIAL.
 ALTHOUGH NO SPRINKLER IS REQUIRED, SHEET A01.1/ BLDG1
 INDICATES ALL BUILDINGS ARE TO BE FIRE SPRINKLED, SP-1
 DOESN'T INDICATE IF THIS SYSTEM IS TO BE A FULL 13 OR A
 13-R SYSTEM?
 BY DEFINITION THIS STRUCTURE IS CONSIDERED A R-3
 OCCUPANCY, A R-2 IS FOR MORE THAN 2 UNITS SEE SECTION
 310 FBC- BUILDING.
  
  
  
 12) S-02 NEITHER THE FOUNDATION NOR THE SLAB ON GRADE
 NOTE CODE COMPLIANCE FOR TERMITE TREATMENT: RESIDENTIAL
 -R 320.
  
 13) S-02 STRUCTURAL STEEL NOTE # 7 INDICATES THE WRONG
 ASCE 7-98.PLEASE CORRECT.
  
 14)SHEET A201 INDICATES BETWEEN UNITS THE DESIGNER
 REQUIRES A 2HR FIRE RATED BLOCK, DETAIL# 5, A800
 INDICATESA UL DESIGN U-905 IF UL IS PRODUCING THE
 BLOCK THIS IS OK, THE BLOCK MANUFACTURER NEEDS TO
 SUPPLY THE EQUIVALENT BLOCK THICKNESS WITH TYPE OF
 AGGREGATE FOR A 2 HR RATED WALL BETWEEN UNITS.
  
 15)FL BLD CODE 1609.1.4/ R- 301.2.1 :
 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
  
 A) WINDOWS
 CASEMENT 1) HIGHLIGHT TYPE OF GLASS TO BE USED 2)
 DEPENDING ON TYPE OF GLASS ZONE 4 MAY BE OK BUT ZONE 5
 - PRESSURE IS -74.5
  
 FIXED GLASS- OK
  
 GLASS BLOCK 1) PRESSURE ZONE 5 PRESSURES -77.23
 2) S-04 NORTH ELEVATION MISSING ZONE 5 ON ELEVATIONS
 3) MUST MEET REQUIREMENTS OF 2110- FBC-B
  
 B)EXTERIOR DOORS
 1) DISCREPANCY- A101 & A102
 THE DOOR SCHEDULE INDICATES DOOR # 3 TO BE A PAIR OF
 FRENCH DOORSA102 INDICATES THESE DOORS TO BE FRENCH
 DOORS WITH SIDE LIGHTS & TRANSOM WHEREAS THE
 MIAMI-DADE NOA 05-0829.08 INDICATES A MAXIMUM WIDTH OF
 72?, EITHER A STRUCTURAL MULLION AND FIXED WINDOW
 REPORT REQUIRED OR A PRODUCT APPROVAL WITH SIDE LIGHT
 AS PART OF THE CONFIGURATION.
  
 C) MULLIONS: NO REPORT SUBMITTED FRENCH DOORS & FIXED
 GLASS
  
 D) OVERHEAD GARAGE DOOR: PLEASE HIGHLIGHT WHICH MODEL
 DOOR TO BE USED,
 PRODUCE CLEARER /DARKER NOA REPORT FOR RECORD KEEPING
 PURPOSES.
  
 E) ROOFING ASSEMBLIES: REPORT SUBMITTED IS MISSING OR
 NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 __X___ CONTRACTOR DID NOT PROVIDE THE MEAN
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 __X___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 __X___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ 2&3___ .
  
 __X___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 16)R-613.7.1/1707.4.5.1 MULLIONS OCCURRING BETWEEN
 INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE REQUIRED BY AN
 APPROVED TESTING LABORATORY OR BE ENGINEERED.
  
 17)1707.4.5.2 / R613.7.2 MULLIONS SHALL BE DESIGNED
 TO TRANSFER THE DESIGN PRESSURE LOADS APPLIED BY THE
 WINDOW OR DOOR ASSEMBLIES TO THE ROUGH OPENING
 SUBSTRATE.
  
 18WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
  
 19) S-04 VS A-101& A102 THE EAST ELEVATIONS 2ND AND
 THIRD FLOOR WINDOW ARE IN THE END ZONE # 5 AS THEY ARE
 CURRENTLY CONFIGURED BY 4? WHICH SHOULD REFLECT HIGH
 PRESSURES.
  
 20) ADDITIONAL INFORMATION REQUIRED, S-04 EAST
 ELEVATION INDICATES A # 7 ON THE END ZONES OF THE
 PARAPET?
 21) SHEET A101 IS MISSING THE WALL TAG IDENTIFYING THE
 WALL TYPE THE SAME WITH THE DOOR OPENING.
  
  
 .
 22 ) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION. )
  
 23) SEE CALCULATED VALUE OF PROJECT AND
 ASSOCIATED PERMIT FEES OUTSTANDING.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-26 Cont ID  
Sent By dpalmer Date 2007-10-26 Time 11:15 Rev Time 0.00
Received By dpalmer Date 2007-10-26 Time 11:15 Sent To  
Notes
2007-10-26 11:15:45** REDLINED PLANS **
  
 A/C CU DISCONNECTS TO BE ON WALL AND MEET 110.26. MOVED
 PER OWNER/GC ARCHITECT.
  
  
 ** ADDRESSING STILL NEEDS TO BE CORRECTED AS PLANS
 INDICATES A SEPARATE ADDRESS THAN SYSTEM. CHANGES TO BE
 MADE BY THE ADDRESSING REVIEWER. THIS INFORMATION WAS
 SENT BY E-MAIL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-15 Cont ID  
Sent By dpalmer Date 2007-04-15 Time 15:59 Rev Time 0.00
Received By dpalmer Date 2007-04-15 Time 15:52 Sent To  
Notes
2007-04-15 15:59:54********* UNSAT 2ND REVIEW ***********
  
 1) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 CODES REQUIRED TO BE STATED ON PLANS FOR PROJECT. THESE
 WERE ADDED TO ELECTRICAL SHEETS; HOWEVER CODES COULD
 NOT BE LOCATED ON ARCHITECTURAL SHEETS.
 FBC 106.1.2
 FBC 2004 W/2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE BE SURE THE TITLE BLOCKS FOR THE
 ARCHITECTURE FIRM AS LICENSED THROUGH THE STATE
 CONTAINS THE PRINTED FIRM CERTIFICATE OF AUTHORIZATION
 NUMBER ON ALL SHEETS WHICH CONTAIN THE FIRM.
 ON ANY SHEETS WHICH DO NOT NEED TO BE REPLACED, THIS
 MAY BE HAND PRINTED OR STAMPED ON SHEETS.
 FAC 61G1-16.004, FS481.219 *SEE ATTACHED PRINT OUT FROM
 THE STATE OF FLORIDA.
  
 3) NOTE: PLEASE SEE THE MINIMUM CLEARANCES FOR THE A/C
 CU DISCONNECTS DOES NOT MEET 110.26
  
 4) NOTE: PLEASE SEE 422.13 AS THE LOADS FOR THE WATER
 HEATER MUST BE FIGURED INTO LOAD CALCULATIONS AT 125%.
  
 6) NOTE: PLEASE SEE THE NEW SERVICE AS SHOWN MUST HAVE
 THE GROUNDING ELECTRODE CONDUCTOR CONTINUOUS TO FOOTER
 STEEL WITH ALL ITEMS AS SHOWN ON GROUNDING RISER PER
 250.66
 SHOWS #4, WHEN THIS SHOULD BE THE #2. 250.64C
 250.66C IS USED WHEN THE SOLE CONNECTION.
 PLEASE CLARIFY ANY METALLIC COLD WATER PIPE ?
  
 7) NOTE: PLEASE SEE CODE SECTIONS FOR LOAD CALCULATIONS
 FOR EACH ARE FROM THE 2002 NEC.
 PLEASE ADJUST TO THE 2005 NEC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-02 Cont ID  
Sent By dpalmer Date 2007-03-02 Time 17:12 Rev Time 0.00
Received By dpalmer Date 2007-03-02 Time 17:05 Sent To  
Notes
2007-03-02 17:16:03*** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGE SIN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE ALSO SEE ELECTRICAL CHANGES UNDER THE 2005
 INCLUDING ANY SECTIONS OF CODES WHICH ARE REFLECTED ON
 PLANS FROM THE PREVIOUS 2002 NEC.
 PLEASE LIST THE FOLLOWING FOR THIS REVIEWER AT A
 MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION AND
 OTHER INFORMATION ON TITLE BLOCKS FOR LANDSCAPE
 SHEETS.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND
 FS 481.219
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
  
 3) NOTE: PLEASE SEE PLANS APPEAR TO SHOW A *D* FOR WHAT
 IS BEING ASSUMED AS A SMOKE DETECTOR. PLEASE KNOW THAT
 AS THE SYMBOL LEGEND DOES NOT CORRELATE WITH PLANS IT
 CAN NOT BE CONFIRMED AT THIS TIME.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY
 THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 4) NOTE: PLEASE KNOW THATTHE PLANS NEED TO LABEL AND
 PROVIDE ROOM AND ARE DESIGNATIONS ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS
 AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR
 EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN FROM
 COMMENTARY IN THE CODE WHICH STATES THE USE OF *GEN LT*
 ETC IS NOT ACCEPTABLE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 5) NOTE: PLEASE LABEL DEVICES WHICH ARE SHOWN OUTSIDE
 AS TO WHICH PANEL THEY ARE BEING FED FROM. PLEASE SEE
 THAT THE OUTSIDE GFI IS BEING SHOWN BY BOTH CONDENSING
 UNITS YET ONE GFI MAY NOT BE USED TO SERVICE OTHER
 OWNERS UNIT UNLESS A HOUSE PANEL IS PROVIDED? PLEASE
 ALSO SEE NOTE FOR SERVICE AS METER/MAIN COMBO PANELS
 ARE BEING SHOWN YET THE CU'S ARE BEING FED FROM PANELS
 INSIDE.
 210.25
 FBC 106.1.2, 106.3.5.4
  
 6) NOTE: PLEASE SEE THAT THIS IS CONSIDERED ONE
 BUILDING AND ONLY ONE ELECTRICAL SERVICE IS PERMITTED.
 230.2
 PLEASE REVISE SERVICE RISER WHICH MAY INCLUDE TWO
 METERS FOR THE MULTI-FAMILY BUILDING.
 PLEASE KNOW ONE THE RISER IS REVISED, REVIEW OF NEW
 RISER WILL TAKE PLACE.
  
 7) NOTE: PLEASE SEE THAT THE GROUNDING ELECTRODE DETAIL
 DOES NOT CARRY THE GROUNDING ELECTRODE CONDUCTOR TO THE
 REQUIRED FOOTER STEEL BEING LOCATED IN THE BOTTOM OF
 THE FOOTER AS REQUIRED PER 250.50,250.52.
 PLEASE SEE ONE NOTE MENTIONS SLAB, ONE SHOWS WALL
 CONNECTION? PLEASE ADJUST RISER FOR THIS.
  
 8) NOTE: PLEASE SEE 210.52C1-5.
 PLEASE SEE UNIT A AS THE COUNTER SPACE GFI DOES NOT
 SEEM TO SERVE COUNTER FOR WHAT SEEMS TO BE SHOWN AS A
 PENINSULAR.
 PLEASE ALSO SEE THAT THE GFI AS SHOWN APPEARS TO BE
 LOCATED ON THE WALL WHICH IS IN THE DINING AREA. PLEASE
 ALSO SEE 210.52 AND SEE OTHER UNIT AND GO OVER COUNTER
 SPACE DEVICES AS ONE OR TWO APPEAR TO BE NEEDED.
  
 9) NOTE: PLEASE BE SURE ALL SYMBOLS ON PLANS CORRELATE
 WITH THE SYMBOL LEGEND. PLEASE SEE SOME ITEMS ON PLANS
 WHICH ARE NOT LISTED.
 FBC 106.1.2, 106.3.5.4.
  
 10) NOTE: PLEASE SEE NOTES FORM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS AND SHEETS.
 PLEASE SEE NOTES FROM ADDRESSING REVIEWER WHICH MAY
 AFFECT THE TITLE BLOCKS FOR ADDRESSING OF PROJECT.
  
 11) NOTE: PLEASE SEE THAT AS THIS BUILDING IS LOCATED
 IN A FLOOD ZONE, PLEASE INDICATE THE HEIGHT OF THE
 EQUIPMENT/ ELEVATION DETAIL. REQUIRED FOR ELECTRICAL
 SERVICE AND A/C EQUIPMENT ALSO.
  
 12)NOTE: PLEASE SEE BOTH CU'S ARE SHOWN BEING FED
 FROM THE SAME UNIT "A".
  
 13) NOTE:PLEASE PLACE NOTE ON PLANS FOR ANY RECESSSED
 LIGHTING TO MEET THE FBC 2004 W/2006 REVSION SECTION
 13-606.1.ABC.1.2.4
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2007-11-13 Cont ID  
Sent By rchokshi Date 2007-11-13 Time 11:23 Rev Time 0.00
Received By rchokshi Date 2007-11-13 Time 11:17 Sent To  
Notes
2007-11-13 11:23:34PASSED PER JONATHAN BRAMLEY'S E-MAIL COMMENTS DATED
 11/02/07 & 11/09/07.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2007-11-13 Cont ID  
Sent By rchokshi Date 2007-11-13 Time 10:41 Rev Time 0.00
Received By rchokshi Date 2007-11-13 Time 10:36 Sent To  
Notes
2007-11-13 10:41:35PASSED PER JONATHAN BRAMLEY'S E-MAIL COMMENTS DATED
 11/02/07 & 11/09/07.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-10-30 Cont ID  
Sent By rchokshi Date 2007-10-30 Time 11:30 Rev Time 0.00
Received By rchokshi Date 2007-10-30 Time 11:18 Sent To  
Notes
2007-10-30 11:30:291. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2.PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINEDTHE FIRST
 FLOOR ELEVATION.
 5. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE.
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, & REVISED
 STORM WATER QUALITY CALCULATIONS & RESUBMIT GEOTECH
 REPORT.STORM WATER CALS MUST BE APPROVED FROM 1000
 45TH STREET ENGINEERING SERVICES BEFORE WE ISSUE
 PERMIT.
 9. POLLUTION PREVENTION DETAILS:PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS DURINGALL
 DEMOLITION PHASE.HEIGHT OF FENCE SHOULD BE HIGH
 ENOUGH PER FDEP TO STOP DUST PARTICLES. YOU HAVE SHOWN
 SILT FENCE DURING CONSTRUCTION PHASE BUT NOT DURING
 DEMOLITION PHASE.
 10. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-05-10 Cont ID  
Sent By rchokshi Date 2007-05-10 Time 10:03 Rev Time 0.00
Received By rchokshi Date 2007-05-10 Time 09:46 Sent To  
Notes
2007-05-10 10:02:50FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE WRITE NOTES ON DRAWINGS FOR HANDICAP PARKINGS
 PER ADA & ETC.
 2.PLEASE WRITE A NOTES ON DRAWINGS THAT DUMPSTER
 LOCATION IS ACCESSIBLE FOR CITY'S PICK UP TRUCK. 3.YOU
 WROTE IN YOUR COMMENT THAT WATER QUALITY CAS ARE BEING
 SUBMITTED SAPERATELY.I HAVE NOT RECEIVED YET AT CITY
 HALL.WATER QUALITY CALS ARE NOT IN THE PACKAGE YOU
 SUBMITTED AT CONSTRUCTION SERVICE, CITY HALL. PLEASE DO
 NOT SEND PACKAGE AT 45TH STREET, ENG DEPT.
 4. POLLUTION PREVENTION: PLEASE SHOWTHE HEIGHT OF
 THE SILTFENCE AROUND THE SITE, SILT FENCE HEIGHT
 SHOULD BE HIGH ENOUGH TO STOP FLYING DIRT. EACH PROJECT
 MUST SHOW POLLUTION PREVENTION PLAN IN THEIR OWN
 DRAWING SETS. NO CROSS REFERENCES, PLEASE.
 5. THE CITY'S UTILITY HAS TO APPROVE FIRST BEFORE WE
 APPROVE IT.
  
 PLEASE NOTE THAT WHEN YOU HAVE MORE THAN ONE PERMIT #,
 IN THE SAME SITE YOU NEED TO PROVIDE INDEPENDENT PERMIT
 REQUIREMENTS, LIKE YOU ARE PREPARING A DRAWING SET FOR
 EACH BUILDING. WATER QUALITY CALS MAY BE ONEFOR WHOLE
 SITE, STILL WE LOOK AT AS IT IS AN INDEPENDENT OF EACH
 OTHER AND WE FILE SEPARATELY BY PERMIT #.HOPE THIS
 CLEARIFICATION HELP YOU.
  
 PLEASE RESPOND EACH ITEM YO EXPEDITE THE PERMITTING.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-03-08 Cont ID  
Sent By rchokshi Date 2007-03-08 Time 16:00 Rev Time 0.00
Received By rchokshi Date 2007-03-08 Time 16:00 Sent To  
Notes
2007-03-08 16:00:13PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,YOU CAN GET STANDARD NOTES OF
 CITY OF WPB IN A C.D. FROM 1000 45TH STREET. WE SHOULD
 HAVE THOSE NOTES ON YOUR DRAWINGS.
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, & FLOOD
 ZONE,FIRST FLOOR ELEVATION MUST MEET THESE
 MINIMUMREQUIREMENTS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, & GEO TECH
 REPORT.
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ?ALSO, WHAT IS TOTAL PERVIOUS,&
 IMPERVIOUSAREA FOR THIS PROJECT.
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 10. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-11-10 Cont ID  
Sent By lmartine Date 2009-11-10 Time 16:41 Rev Time 0.00
Received By lmartine Date 2009-11-10 Time 16:41 Sent To  
Notes
2009-11-10 16:43:23********************EXPEDITED********************
 GAVE TO KENNY

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-11-10 Cont ID  
Sent By lmartine Date 2009-11-10 Time 16:31 Rev Time 0.00
Received By lmartine Date 2009-11-10 Time 16:31 Sent To  
Notes
2009-11-10 16:31:48********************EXPEDITED**********************
 GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-12-03 Cont ID  
Sent By adarroug Date 2008-12-03 Time 09:32 Rev Time 0.00
Received By adarroug Date 2008-12-03 Time 09:32 Sent To  
Notes
2008-12-03 09:34:50TO "COMM" BD#10

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-08-15 Cont ID  
Sent By adarroug Date 2008-08-15 Time 10:01 Rev Time 0.00
Received By adarroug Date 2008-08-15 Time 10:01 Sent To B
Notes
2008-08-15 10:02:00TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 16:20 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 16:20 Sent To B
Notes
2008-05-19 16:20:34TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-08 Cont ID  
Sent By adarroug Date 2008-02-08 Time 10:44 Rev Time 0.00
Received By adarroug Date 2008-02-08 Time 10:44 Sent To B
Notes
2008-02-08 10:45:56TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-29 Cont ID  
Sent By adarroug Date 2007-11-29 Time 12:39 Rev Time 0.00
Received By adarroug Date 2007-11-29 Time 12:39 Sent To  
Notes
2007-11-29 12:39:28WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 11:16 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 11:16 Sent To  
Notes
2007-10-25 14:55:49TO "COMM" BD#43
2007-10-03 11:16:34WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-05 Cont ID  
Sent By spalmer Date 2007-04-05 Time 17:56 Rev Time 0.00
Received By spalmer Date 2007-04-05 Time 17:56 Sent To  
Notes
2007-04-09 08:51:39TO "COMM" BD#55/PLANS ON RACK/2 ROLLS
2007-04-05 17:56:47WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-15 Cont ID  
Sent By jwitmer Date 2007-03-15 Time 12:08 Rev Time 0.00
Received By jwitmer Date 2007-02-15 Time 15:59 Sent To  
Notes
2007-02-26 13:14:49TO "COMM" BD#26
2007-02-15 15:59:27WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-11-17 Cont ID  
Sent By rregueir Date 2009-11-17 Time 15:32 Rev Time 0.00
Received By rregueir Date 2009-11-17 Time 15:32 Sent To  
Notes
2009-11-17 15:32:33ALL PREVIOUS PROVISOS ON REVISION HAVE BEEN ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-11-11 Cont ID  
Sent By rregueir Date 2009-11-11 Time 11:03 Rev Time 0.00
Received By rregueir Date 2009-11-11 Time 10:19 Sent To  
Notes
2009-11-11 11:02:55**PROVISO** REVISED AC-1 THRU AC-4 DELTA 4
  
 PG AC-1: REVISE PLAN TO COORDINATE SIZE OF FLEX DUCT
 FEEDING THE FIRST FLOOR. THE SECOND FLOOR PLAN SHOWS
 THIS AS 12 INCH ROUND WHILE THE FIRST FLOOR PLAN SHOWS
 THIS SAME DUCT AS 8 INCH ROUND. WHICH IS CORRECT?
  
 PG AC-2: BEDROOM 2 BATHROOM EXHAUST DUCT IS MSSING
 SIZE. DRYER EXHAUST DUCT IS MISSING SIZE. REVISE PLAN
 TO SHOW MISSING DUCT SIZES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-30 Cont ID  
Sent By tgordon Date 2007-10-30 Time 08:15 Rev Time 0.25
Received By tgordon Date 2007-10-30 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-01 Cont ID  
Sent By rregueir Date 2007-05-01 Time 07:07 Rev Time 0.00
Received By rregueir Date 2007-04-30 Time 19:32 Sent To  
Notes
2007-05-01 07:07:51-------------DENIED---------------
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS COMMENTS FOR CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. NOT ALL DUCT DIRECTIONAL NOTES CORRECTED.
  
 4. OK
  
 5. OK
  
 6. NOT ALL DUCT DIRECTIONAL NOTES CORRECTED.
  
 7. OK
  
 8. OK
  
 9. OK
  
 10. OK
  
 11. REFRIGERANT PIPE DETAIL SHOWS CONDENSATE FROM
 AUXILIARY DRAIN PAN BEING DISCHARGED THRU AUXILIARY
 WATER HEATER LINE. WATER HEATER IS NOT SHOWN IN A/C
 CLOSET ON PLUMBING PLANS. AUXILIARY DRAIN PAN FOR A/C
 CONDENSATE SHOULD HAVE EITHER A FLOAT SWITCH OR A
 SECONDARY DRAIN LINE PIPED TO A CONSPICUOUS LOCATION
 PER FRC M1411.3.1. CONDENSATE OVERFLOW CAN NOT BE
 DISCHARGED INTO AN AUXILIARY WATER HEATER LINE AS IT
 WILL NOT PROVIDE WARNING OF A PROBLEM WITH THE PRIMARY
 CONDENSATE DRAIN.
  
 12. OK
  
 13. DRYER EXHAUST TERMINATION AT ROOF REQUIRES
 BACKDRAFT DAMPER PER FRC M1501.1.
  
 14. OK
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By rregueir Date 2007-03-15 Time 08:18 Rev Time 0.00
Received By rregueir Date 2007-03-14 Time 10:21 Sent To  
Notes
2007-03-15 10:20:48--------------DENIED----------------
  
 FBC 2004 W/ 2006 REVISIONS
 FRC 2004
 FBC,M 2004
  
 1. BUILDING PLAN SHOWS A UNIT A AND A UNIT B, AC PLAN
 SHOWS BOTH TO BE UNIT A. FOR PURPOSE OF CLARITY, PLEASE
 CORRELATE DRAWINGS. FBC 106.1.1
  
 2. PG AC-2 1ST FLOOR: PLEASE INDICATE THE SIZE OF THE
 DUCT BETWEEN THE 16X6 TRANSFER GRILLS. FBC 106.1.1
  
 3. PG AC-2 1ST FLOOR: LEFT UNIT SHOWS 10X6 DUCT DOWN TO
 1ST FLOOR. THIS DUCT IS ALREADY ON THE FIRST FLOOR.
 SHOULD IT SAY ?UP TO 2ND FLOOR?? FBC 106.1.1
  
 4. PG AC-2 PIPING IN OR BENEATH CONCRETE FLOORS SHALL
 BE ENCASED IN A PIPE DUCT PER FRC R101.2, FBC,M
 1107.2.1.
  
 5. PG AC-2 1ST FLOOR: RIGHT UNIT SHOWS A 10X6 DUCT UP
 TO 1ST FLOOR. SHOULD THIS SAY ?UP TO 2ND FLOOR?? ALSO,
 PLEASE SHOW SIZE OF DIFFUSER AND CFM AT 4? ROUND FLEX
 DUCT TERMINATIONS. PLEASE CLARIFY. FBC 106.1.1
  
 6. PG AC-2 2ND FLOOR: LEFT UNIT SHOWS 22X8 DUCT UP TO
 2ND FLOOR. DUCT IS ALREADY ON 2ND FLOOR. SHOULD IT SAY
 ?UP TO 3RD FLOOR?? ALSO, REFRIGERANT LINES ARE SHOWN
 GOING UP WHERE THEY SHOULD BE GOING DOWN AS WELL AS
 GOING DOWN WHERE THEY SHOULD BE GOING UP. PLEASE
 CLARIFY. FBC 106.1.1
  
 7. PG AC-2 2ND FLOOR: RIGHT UNIT FE-1 EXHAUST DUCT IS
 SHOWN GOING OUT SOUTH EXTERIOR WALL WITH NO WALL CAP.
 THERE IS ALSO A 4? ROUND DUCT GOING UP TO THE 3RD FLOOR
 FROM NOWHERE. PLEASE CLARIFY. FBC 106.1.1
  
 8. PGS AC-2 AND AC-3: PLEASE REMOVE CLOUDS FROM DRAWING
 FOR THE PURPOSE OF CLARITY AS THERE ARE YET TO BE ANY
 REVISIONS.
  
 9. PG AC-3: DOOR SCHEDULE INDICATES LOUVERED DOORS ON
 A/C CLOSET. A SOLID DOOR W/ GASKET SHOULD BE USED AS
 THIS CLOSET IS BEING USED AS A PLENUM AND THE DRAWING
 OF RETURN AIR FROM A CLOSET IS PROHIBITED UNDER FRC
 M1602.2(5)
  
 10. PG AC-3 EF-1 IN BOTH ROOMS LABELED ?BATH 2? THERE
 IS A 4? ROUND DUCT GOING TO A 5? ROUND ROOF CAP. IS
 THIS INTENTIONAL OR A MISTAKE? ALL OTHER ROOF CAPS
 MATCH THE CORRESPONDING DUCT SIZE.
  
 11. PLEASE SHOW AN AUXILIARY OR SECONDARY DRAIN SYSTEM
 THAT IS IN COMPLIANCE WITH FRC 1411.3.1
  
 12. PLEASE INDICATE ON PLAN WHERE R-4.2 DUCT IS
 ACCEPTABLE AND WHERE R-6 DUCT IS REQUIRED. FBC 106.1.1
  
 13. PLEASE PROVIDE DETAIL ON PLAN SHOWING WHICH TYPES
 OF ROOF/WALL CAPS ARE TO BE USED AS THERE ARE DIFFERENT
 REQUIREMENTS FOR BATHROOM AND DRYER EXHAUST. SEE: FBC,M
 TABLE 401.6 AND FRC M1501.1
  
 14. GENERAL NOTE #15: THIS PROJECT IS UNDER FBC/FRC
 2004 W/ 2006 REVISIONS, NOT FBC 2001. PLEASE CORRECT
 AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS REGARDING THIS REVIEW, PLEASE
 FEEL FREE TO CONTACT ME AT ANY TIME.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-11-17 Cont ID  
Sent By kstevens Date 2009-11-17 Time 07:49 Rev Time 0.00
Received By kstevens Date 2009-11-17 Time 07:49 Sent To  
Notes
2009-11-17 07:50:53REVISION OK -- SHTS P-2, P-3, P-4 & P-6. NOTE: P-6
 SUBMITTED AS A REVISION DOES NOT INDICATE A REVISION.
 NO REVISION NUMBER FOUND, NOR REVISION CLOUD.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-01-13 Cont ID  
Sent By lwagner Date 2009-01-13 Time 13:57 Rev Time 0.00
Received By lwagner Date 2009-01-13 Time 13:39 Sent To  
Notes
2009-01-13 13:57:27REVISION OK- SHEETS P1, P2, P3, P5

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-05-31 Cont ID  
Sent By kstevens Date 2007-05-31 Time 14:48 Rev Time 0.00
Received By kstevens Date 2007-05-31 Time 14:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By kstevens Date 2007-03-12 Time 11:39 Rev Time 0.00
Received By kstevens Date 2007-03-12 Time 11:39 Sent To  
Notes
2007-03-12 12:41:29DENIED
 REFERENCE: FBC-2004 W/2006 AMENDMENTS
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. PLEASE INDICATE CODE REFERENCES ON PLANS. SECTIONS
 106.1.1 & 106.1.2.
  
 2. SHT 2 OF 6A INDICATES 3" DUAL RPZV BACKFLOW
 PREVENTERS ON 4" DIP WATER LINE. PER TABLE 603.1(D),
 ALL BACKFLOW ASSEMBLIES SHALL BE AT LEAST THE SAME SIZE
 AS THE LINE IN WHICH THEY ARE INSTALLED.4" DUAL RPZV
 BACKFLOWS ARE REQUIRED.
  
 3. SHT A103 ROOF PLAN NOTE POINTS TO A 4"X8" "TRANSFER
 SCUPPER" AND INDICATES (TYP OF 2), BUT ONLY ONE SHOWN.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 4. SHT A103 ROOF PLAN NOTED "TRANSFER SCUPPER" IS SHOWN
 AS 4"X8", WHEREAS SHT P-3 INDICATES THE "TRANSFER
 SCUPPER" AS 4"X6". PLEASE CORRELATE THE INFORMATION
 BETWEEN THE TWO SHEETS. SECTION 106.1.1.
  
 5. SHT P-5 WATER RISER DIAGRAMS DO NOT REFLECT THE
 FLOOR PLAN FOR THE REF. & THE WATER SERVICE ROUTING FOR
 BOTH UNITS. PLEASE CORRELATE. SECTION 106.1.1.
  
 6. SUBMIT A HORIZONTAL STORM RISER ISOMETRIC RISER, AND
 VERTICAL STORM RISER DIAGRAMS. SHOW ALL PIPE SIZES, AND
 INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE
 SYSTEM. SECTION 106.3.5.1.3(7)(13) & TABLE 1106.3.
  
 7. SHT IR-1 IRRIGATION PLANS ARE INCOMPLETE. SHOW ALL
 PIPING AND INDICATE PIPE SIZE. SHOW THE LOCATION OF THE
 METER, BACKFLOW PREVENTER, & RAIN SENSOR. SECTION
 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-12-09 Cont ID  
Sent By eschneid Date 2008-12-09 Time 12:13 Rev Time 0.00
Received By eschneid Date 2008-12-09 Time 12:13 Sent To  
Notes
2008-12-09 12:13:23REVISIONS ON SHEETS A300 AND A301.
  
 NOTE: PRIOR TO ZONING DIVISION SIGN OFF FOR THE C.O., A
 MINOR AMENDMENT IS REQUIRED THAT INCLUDES THE AS-BUILT
 SET OF ARCHITECTUAL DRAWINGS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-25 Cont ID  
Sent By choops Date 2007-10-25 Time 16:23 Rev Time 0.00
Received By ESCHNEID Date 2007-10-25 Time 16:23 Sent To  
Notes
2007-10-25 16:23:48PROVISOS
  
 1) SUBMIT 2 SIGNED COPIES OF THE ABSTRACTED SURVEY.
  
 2) A SITE PREPERATION PERMIT IS REQUIRED PRIOR TO
 BEGINING WORK ON THE SITE.THE TREE RELOCATION WILL BE
 REVIEWED AT THAT TIME.
  
 3) THE WALLS AND FENCES TO BE UNDER A SEPERATE PERMIT.
  
 4) A PERMIT IS REQUIRED FOR THE IRRIGATION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-05-11 Cont ID  
Sent By eschneid Date 2007-05-11 Time 14:21 Rev Time 0.00
Received By eschneid Date 2007-05-11 Time 14:19 Sent To  
Notes
2007-05-11 14:54:34FAILED - 2ND REVIEW
  
 1) WHICH PERMIT (07020339 OR 07020336) IS THE SITE
 WORK, LANDSCAPING AND LIGHTING UNDER?EACH PERMITS
 LIMIT OF WORK INCLUDES THESE ITEMS.
  
 2) ILLUMINATION IN A RESIDENTIAL DISTRICT MAY NOT
 EXCEED 0.5 FOOT CANDLES AT THE PROPERTY LINE.THIS IS
 EXCEEDED AT THE SOUTHWEST CORNER OF THE SITE AND THE
 ENTRANCE TO THE PROJECT AS PART OF THIS PERMIT.PLEASE
 NOTE THAT THE POOL AREA EXCEEDS THIS REQUIREMENT AS
 WELL.THE LIGHTS SHOULD BE SHIELDED TO PREVENT GLARE.
  
 3) PLEASE ADD A NOTE TO SHEET A101 STATING THAT "NO
 REFLECTIVE GLASS WILL BE USED."
  
 4) THE REVISED ELEVATIONS FOR BUILDING 2 NEED TO BE
 INCLUDED WITH THE CURRENTLY SUBMITTED MINOR AMENDMENT.
  
 5) PLEASE NOTE THAT THE WALLS/FENCES, TO INCLUDE THE
 COLUMNS, SHALL NOT EXCEED SIX FEET IN HEIGHT WITHIN THE
 SIDE PROPERTY LINES.
  
 6) AN ABSTRACTED SURVEY, SHOWING ALL EASEMENTS, IS
 REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status P Date 2008-12-09 Cont ID  
Sent By eschneid Date 2007-03-05 Time 17:45 Rev Time 0.00
Received By eschneid Date 2007-03-05 Time 17:35 Sent To  
Notes
2007-03-05 17:46:01FAILED
  
 1) INDICATE THE LIMITS OF WORK, TO INCLUDE DRIVE AISLES
 AND LANDSCAPE, INCLUDED AS PART OF THIS PERMIT.
  
 2) ORDINANCE NO. 3856-05 REQUIRES THE SUBMITTAL OF A
 PHOTOMETRIC PLAN PRIOR TO BUILDING PERMIT APPROVAL.
  
 3) THE LANDSCAPE PLAN DOES NOT REFLECT THE LOCATION OF
 THE AC UNITS.THE APPROVAL OF A MINOR AMENDMENT IS
 REQUIRED FOR THE REVISED LANDSCAPE PLAN.
  
 4) A UNITY OF TITLE IS REQUIRED.
  
 5) PLEASE NOTE THAT ORDINANCE NO. 3856-05 PROHIBITS THE
 USE OF REFLECTIVE GLASS AND REQUIRES THE USE OF AUGER
 CAST PILINGS.
  
 CONTACT ERIC SCHNEIDER @ 822-1435.