Plan Review Details - Permit 07020284
Plan Review Stops For Permit 07020284
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-02-23 Cont ID  
Sent By btrobaug Date 2007-02-23 Time 12:39 Rev Time 0.25
Received By btrobaug Date 2007-02-23 Time 12:39 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-20 Cont ID  
Sent By btrobaug Date 2007-02-20 Time 07:27 Rev Time 0.33
Received By btrobaug Date 2007-02-20 Time 07:08 Sent To I
Notes
2007-02-20 07:27:12 
 DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 INSPECTION.
  
 1} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 2}SUBMIT A FLOOR PLAN INDICATING THE INSTALLATION OF
 THE LIGHTS, AND CIRCUIT NUMBER PER 700.12(F)(4).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-20 Cont ID  
Sent By btrobaug Date 2007-02-20 Time 07:27 Rev Time 0.00
Received By btrobaug Date 2007-02-13 Time 13:06 Sent To PC
Notes
2007-02-13 13:07:14TO "E" BOX