Plan Review Details - Permit 07020267
Plan Review Stops For Permit 07020267
Review Stop AD ADDRESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-05-24 Time   Rev Time 0.00
Received By   Date 2007-05-24 Time   Sent To  
Notes
2007-04-10 11:03:14THE ADDRESS ON THE SUBMITTED APPLICATION (600 NO.
 DIXIE)DOES NOT MATCH THE SITE PLAN LOCATION (600 SO.
 DIXIE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-12-01 Cont ID  
Sent By mjacobs Date 2008-12-01 Time 07:53 Rev Time 0.00
Received By mjacobs Date 2008-12-01 Time 07:53 Sent To  
Notes
2008-12-01 07:53:16REVISION TO SHEETS #1 & 2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-09-05 Cont ID  
Sent By jwitmer Date 2008-09-05 Time 15:38 Rev Time 2.22
Received By jwitmer Date 2008-09-05 Time 15:38 Sent To  
Notes
2008-09-05 15:39:15REVISION # & 6 SHEET 1& 2

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-05-12 Cont ID  
Sent By mjacobs Date 2008-05-12 Time 07:47 Rev Time 0.00
Received By mjacobs Date 2008-05-03 Time 07:10 Sent To  
Notes
2008-05-12 07:47:12BUILDING PLAN REVIEW
 PERMIT: 07020267
 ADD: 600 S.DIXIE HWY
 CONT: AMERICA HOME CARE.
 TEL: (954)646-2283
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION
 ACTION: DENIED
  
 1) 61G1-18.002PROCEDURES FOR A SUCCESSOR ARCHITECT
 ADOPTING AS HIS OWN THE WORK OF ANOTHER ARCHITECT. (1)
 A SUCCESSOR REGISTERED ARCHITECT SEEKING TO REUSE
 ALREADY SEALED CONTRACT DOCUMENTS UNDER THE SUCCESSOR
 REGISTERED ARCHITECT'S SEAL MUST BE ABLE TO DOCUMENT
 AND PRODUCE UPON REQUEST EVIDENCE THAT HE HAS IN FACT
 RECREATED ALL THE WORK DONE BY THE ORIGINAL REGISTERED
 ARCHITECT. FURTHER, THE SUCCESSOR REGISTERED ARCHITECT
 MUST TAKE ALL PROFESSIONAL AND LEGAL RESPONSIBILITY FOR
 THE DOCUMENTS WHICH HE SEALED AND SIGNED AND CAN IN NO
 WAY EXEMPT HIMSELF FROM SUCH FULL RESPONSIBILITY. PLANS
 NEED NOT BE REDRAWN BY THE SUCCESSOR REGISTERED
 ARCHITECT; HOWEVER, JUSTIFICATION FOR SUCH ACTION MUST
 BE AVAILABLE THROUGH WELL KEPT AND COMPLETE
 DOCUMENTATION ON THE PART OF THE SUCCESSOR REGISTERED
 ARCHITECT AS TO HIS HAVING RETHOUGHT AND REWORKED THE
 ENTIRE DESIGN PROCESS. A SUCCESSOR REGISTERED ARCHITECT
 MUST USE HIS OWN TITLE BLOCK, SEAL AND SIGNATURE AND
 MUST REMOVE THE TITLE BLOCK, SEAL AND SIGNATURE OF THE
 ORIGINAL REGISTERED ARCHITECT BEFORE SEALING, SIGNING
 AND DATING ANY SEALED CONTRACT DOCUMENTS.
 (2) PRIOR TO SEALING, SIGNING AND DATING WORK, A
 SUCCESSOR REGISTERED ARCHITECT SHALL BE REQUIRED TO
 NOTIFY THE ORIGINAL REGISTERED ARCHITECT, HIS
 SUCCESSORS, OR ASSIGNS BY CERTIFIED LETTER TO THE LAST
 KNOWN ADDRESS OF THE ORIGINAL REGISTERED ARCHITECT OF
 THE SUCCESSOR'S INTENTION TO USE OR REUSE THE ORIGINAL
 REGISTERED ARCHITECT'S WORK. THE SUCCESSOR REGISTERED
 ARCHITECT WILL TAKE FULL RESPONSIBILITY FOR THE DRAWING
 AS THOUGH THEY WERE THE SUCCESSOR REGISTERED
 ARCHITECT'S ORIGINAL PRODUCT.
  
 2)UNLESS THE NEW ARCHITECT IS TAKING OVER THE PROJECT
 HE CANNOT MAKE ANY CHANGES TO THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-05-24 Cont ID  
Sent By mjacobs Date 2007-05-24 Time 15:50 Rev Time 0.00
Received By mjacobs Date 2007-05-24 Time 09:16 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-03 Cont ID  
Sent By mjacobs Date 2007-04-03 Time 08:47 Rev Time 0.00
Received By mjacobs Date 2007-03-31 Time 10:51 Sent To PC
Notes
2007-03-31 11:22:37BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)OK
  
 4)OK
  
 5) OK
  
 6)FBC 11-7.2(2) (I) A PORTION OF THE MAIN COUNTER
 WHICH IS A MINIMUM OF 36 INCHES IN LENGTH SHALL BE
 PROVIDED WITH A MAXIMUM HEIGHT OF 36 INCHES.IN NEW
 CONSTRUCTION, WHERE THE SELLING SPACE IS UNDER 5,000
 SQUARE FEET, ONLY ONE CHECK-OUT AISLE IS REQUIRED TO BE
 ACCESSIBLE. SHOW COMPLIANCE WITH ELEVATION DRAWINGS.
  
 6A)11-2.2 EQUIVALENT FACILITATION.
 DEPARTURES FROM PARTICULAR TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE BY THE USE OF OTHER DESIGNS
 AND TECHNOLOGIES ARE PERMITTED WHERE THE ALTERNATIVE
 DESIGNS AND TECHNOLOGIES USED WILL PROVIDE
 SUBSTANTIALLY EQUIVALENT OR GREATER ACCESS TO AND
 USABILITY OF THE FACILITY. SHOW THE WHEELCHAIR TURNING
 SPACE IN OFFICE #2. SEE FBC.CH.11 FIG #3.
  
 7)FBC.11-5.2 WHERE FOOD OR DRINKIS SERVED AT
 COUNTERS EXCEEDING 34 INCHES IN HEIGHT FOR CONSUMPTION
 BY COUSTOMERS SEATED ON STOOLS OR STANDING AT THE
 COUNTER, A PORTION OF THE MAIN COUNTERWHICH IS60
 INCHES IN LENGTH MINIMUM SHALL BE PROVIDED IN
 COMPLIANCE WITH SECTION 11-4.32 OR SERVICES SHALL BE
 AVAILABLE AT TABLES WITHIN THE SAME AREA.
  
 7A)FBC. 11-4.33.3AT LEAST ONE COMPANION FIXED SEAT
 SHALL BE PROVIDED NEXT TO EACH WHEEL CHAIR SEATING
 AREA. SHOW COMPLIANCE WITH ELEVATION DRAWINGS. ALSO
 SHOW THE ELEVATION DETAILS OF THE TABLE PROVIDED. SEE
 FIG.45.
  
  
 8)OK
  
 9)SHOWER STALLS SHALL COMPPLY WITH SECTION 11-4.21
 PROVIDE AN ELEVATION DRAWINGS WITH ALL THE
 DIMENTIONS............
 OK, BUT SHOWER #2 IS MISSING THE DIMENTIONS. COMPLY AND
 SHOW DIMENTIONS. ALSO INDICATE THE TYPE OF
 MATERIALWHICH WILL BE USED FOR THE GRAB BARS BACKING
 AND THE 250 LBSREQUIREMENT OF SECTION 11-4.26.3.
  
 10)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-16 Cont ID  
Sent By mjacobs Date 2007-02-16 Time 15:40 Rev Time 0.00
Received By mjacobs Date 2007-02-15 Time 15:21 Sent To  
Notes
2007-02-15 16:31:20BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED. FBC 2004 WITH 2006 REVISIONS
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 4)THE VALUE ON THE APPLICATION IS LOW.108.3*IF,
 IN THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION. STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, ARCHITECTURAL
 AND DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT;
 EXCLUDING LAND ONLY. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS
 SERVICES.
  
 5)FBC 106.3.5.1.1SUBMIT A LIFE SAFETY PLAN SHOWING
 THE MEANS OF EGRESS AND TRAVEL DISTANCE. IS THERE A
 SPRINKLER SYSTEM IN THIS AREA?CLARIFY.
  
 6)FBC 11-7.2(2) (I) A PORTION OF THE MAIN COUNTER
 WHICH IS A MINIMUM OF 36 INCHES IN LENGTH SHALL BE
 PROVIDED WITH A MAXIMUM HEIGHT OF 36 INCHES.IN NEW
 CONSTRUCTION, WHERE THE SELLING SPACE IS UNDER 5,000
 SQUARE FEET, ONLY ONE CHECK-OUT AISLE IS REQUIRED TEO
 BE ACCESSIBLE. SHOW COMPLIANCE WITH ELEVATION
 DRAWINGS.
  
 7)FBC.11-5.2 WHERE FOOD OR DRINKIS SERVED AT
 COUNTERS EXCEEDING 34 INCHES IN HEIGHT FOR CONSUMPTION
 BY COUSTOMERS SEATED ON STOOLS OR STANDING AT THE
 COUNTER, A PORTION OF THE MAIN COUNTERWHICH IS60
 INCHES IN LENGTH MINIMUM SHALL BE PROVIDED IN
 COMPLIANCE WITH SECTION 11-4.32 OR SERVICES SHALL BE
 AVAILABLE AT TABLES WITHIN THE SAME AREA.
  
 8)CLARIFY IF THE BUILDING OR NEW SPACE HAS A
 SPRINKLER SYSTEM, AND IF IT DOES, STATE THE TYPE OF
 SPRINKLER SYSTEM ON THE DRAWINGS. SEE SHEET 1.
  
 9)SHOWER STALLS SHALL COMPPLY WITH SECTION 11-4.21
 PROVIDE AN ELEVATION DRAWINGS WITH ALL THE DIMENTIONS.
  
 10)FBC 1210.3 SHOWER COMPARTMENTS AND WALLS ABOVE
 BATHBUBS WITH INSTALLED SHOWER HEADS SHALL BE FINISHED
 WITH A SMOOTH, NONABSORBENT SURFACE TO A HEIGHT NOT
 LESS THAN 70 INCHES ABOVE THE DRAIN INLET.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-12-05 Cont ID  
Sent By btrobaug Date 2008-12-05 Time 16:15 Rev Time 0.00
Received By btrobaug Date 2008-12-05 Time 15:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-09-16 Cont ID  
Sent By btrobaug Date 2008-09-16 Time 15:32 Rev Time 0.00
Received By btrobaug Date 2008-09-16 Time 10:21 Sent To  
Notes
2008-09-16 14:23:54 
  
 NONCOMPLIANT/ REVISION DENIED
  
 ALL COMMENTS RELATE TO SHEET #2, UNLESS OTHERWISE
 NOTED. SEE REVIEWED SET FOR SOME, BUT NOT ALL, EXAMPLES
 OF NONCOMPLIANCE.
  
 1} THE "EM" FIXTURES MUST BE CIRCUITED PER 700.12 NEC
 (F)(4). THE ADDED "EM" LIGHTS AND SOME MISSED ON
 PREVIOUS REVIEW, EXIT AND EMERGENY, DO NOT COMPLY.
  
 2} THERE ARE SEVERAL MOTION SENSORS THAT HAVE BEEN
 REMOVED AND WERE NOT INDICATED AS A REVISION (CLOUDED)
 ON THE PLAN. INDICATE HOW COMPLIANCE WITH
 13-415.1.ABC.1.2 SPACE CONTROL, IS TO BE ACHIEVED, OR
 INSTALL, THE PERMITTED DETECTORS
  
 3} THERE ARE CHANGES IN TYPE "I" AND "J" FIXTURES AND
 ADDITIONS OF TYPE "H", "L", "M", AND "N" FIXTURES. IT
 IS NOT CLEAR HOW THE MAXIMUM WATTAGES STILL COMPLY WITH
 13-415.2B FBC AS STATED IN THE NOTE ON SHEET
 #4,THEREFORE THE FOLLOWING IS REQUIRED:
  
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE AND SQUARE FOOTAGE FOR EACH ARE IN COMPLIANCE
 THE WITH WATTAGE ALLOWANCE*** NOTE : OFFICE AREAS ARE
 NOT ALLOWED 1.5 WATTS PER SQUARE FOOT.
  
 4} ADD THE COST OF THE ADDITIONAL LABOR, MATERIAL AND
 EQUIPMENT ADDED IN THIS REVISION TO THE ORIGINAL VALUE
 ON THE APPLICATION ADJUST THE VALUE AT THE PERMIT
 CLERK?S DESK, AND PAY THE DIFFERENCE IN FEES PRIOR TO
 RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-05-22 Cont ID  
Sent By btrobaug Date 2008-05-22 Time 16:18 Rev Time 0.00
Received By btrobaug Date 2008-05-22 Time 16:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-09 Cont ID  
Sent By btrobaug Date 2007-04-09 Time 12:24 Rev Time 0.10
Received By btrobaug Date 2007-04-09 Time 07:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-02-13 Cont ID  
Sent By btrobaug Date 2007-02-13 Time 13:27 Rev Time 1.00
Received By btrobaug Date 2007-02-13 Time 07:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-12-02 Cont ID  
Sent By mawillia Date 2008-12-02 Time 14:48 Rev Time 0.00
Received By mawillia Date 2008-12-02 Time 14:35 Sent To  
Notes
2008-12-02 14:48:27***** REVISION #7, DATED 11/07/2008, APPROVED*****
  
  
 REVISED SHEETS 1, 2, & 4 WERE STAMPED INITIALED AND
 DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIORE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2008-09-22 Cont ID  
Sent By mawillia Date 2008-09-22 Time 13:57 Rev Time 0.00
Received By mawillia Date 2008-09-22 Time 13:41 Sent To  
Notes
2008-09-22 13:48:13*****PROVISO*****
  
  
 REVISED SHEET 1 STAMPED, INITIALED, AND DATED; HOWEVER
 REVISED PLAN SHEETS 2 & 4 TO BE FIRE-STAMPED WHEN THE
 ELECTRICAL PLAN REVIEW COMMENT(S) HAVE BEEN SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIORE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2008-05-12 Cont ID  
Sent By mawillia Date 2008-05-12 Time 13:09 Rev Time 0.00
Received By mawillia Date 2008-05-12 Time 12:56 Sent To  
Notes
2008-05-12 13:03:04*****PROVISO*****
  
  
 REVISED SHEETS 1 AND 2 TO BE FIRE-STAMPED WHEN THE
 BUILDING REVIEW COMMENT(S) HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-05-10 Cont ID  
Sent By mawillia Date 2007-05-10 Time 12:50 Rev Time 0.00
Received By mawillia Date 2007-05-10 Time 12:25 Sent To  
Notes
2007-05-10 12:32:53*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS 2 AND 4 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-04-10 Cont ID  
Sent By mawillia Date 2007-04-10 Time 10:45 Rev Time 0.00
Received By mawillia Date 2007-04-10 Time 10:20 Sent To  
Notes
2007-04-10 10:45:05*****UNSAT*****
  
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
 ACKNOWLEDGE ON THE APPROPIATE PLAN SHEET
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-22 Cont ID  
Sent By mawillia Date 2007-02-22 Time 17:41 Rev Time 0.00
Received By mawillia Date 2007-02-22 Time 12:23 Sent To AD
Notes
2007-02-22 18:47:47*****DENIED*****
  
  
 01.THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK WILL
 BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.THE CORRECT ADDRESS FOR THIS
 LOCALE IS 600 SOUTH DIXIE HIGHWAY - SUITE 103.
  
 02.ON SHEET 1, THE MENTIONED CODE OF 2003 NFPA 101 IS
 CORRECT.HOWEVER, ROOM FINISH NOTE #8INCORRECTLY
 REFERENCES 2005 NFPA 101.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH EMERGENCY ACCESS RESPONSE TO THE
 STRUCTURE OR THE VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 05.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXITS. THIS SHEET MAY ALSO
 INCLUDE THE LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS,
 FIRE EXTINGUISHERS,FIRE ALARM DEVICES, AND FIRE
 SPRINKLERS APPLICABLE TO THE PROPOSED STRUCTURE.
  
 06.SHOW/DISPLAY THESUITE NUMBER ON THE EXTERIOR
 ELEVATION SO THAT THIS TENANT SPACE IS DISTINGUISHABLE
 FROM THE OTHER SUITES.AS PER WEST PALM BEACH CODE,
 THOSE NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO
 LESS THAN 1" IN WIDTH.
  
 07.IT IS NOTED ON SHEET 1 THAT DOOR #25 IS NOT A
 REQUIRED EXIT DOOR, HOWEVER SHEET 2 HAS IT LABELED AS
 AN EXIT DOOR.PLEASE EXPLAIN THIS DOOR AND WHERE IT
 WOULD LEAD PEOPLE.
  
 08.IF SO EQUIPPED WITH A FIRE ALARM SYSTEM, WILL IT
 BE INDEPENDANT OR WILL IT BE TIED INTO THE PRADO
 CONDOMINIUM'S SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE ON THE PLANS EACH COMMENT
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-11-18 Cont ID  
Sent By adarroug Date 2008-11-18 Time 14:40 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 14:40 Sent To  
Notes
2008-11-21 16:51:31TO "BOB"#13
2008-11-18 14:41:14WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-25 Cont ID  
Sent By tgordon Date 2008-08-25 Time 10:08 Rev Time 0.00
Received By tgordon Date 2008-08-25 Time 10:08 Sent To  
Notes
2008-09-11 09:12:58MOVED TO #9
2008-08-25 10:08:57TO "COMM" BD #5.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-21 Cont ID  
Sent By adarroug Date 2008-05-21 Time 10:17 Rev Time 0.00
Received By adarroug Date 2008-05-21 Time 10:17 Sent To  
Notes
2008-05-21 10:17:23TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 15:03 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 15:03 Sent To  
Notes
2007-05-02 15:05:48TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 16:53 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 16:53 Sent To  
Notes
2007-03-24 16:55:20TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-22 Cont ID  
Sent By mawillia Date 2007-02-22 Time 12:23 Rev Time 0.00
Received By mawillia Date 2007-02-12 Time 16:54 Sent To  
Notes
2007-02-12 16:57:14TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-12-06 Cont ID  
Sent By rregueir Date 2008-12-06 Time 15:48 Rev Time 0.00
Received By rregueir Date 2008-12-06 Time 15:48 Sent To PC
Notes
2008-12-06 15:48:44REVISED M-1 AND M-2

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-09-09 Cont ID  
Sent By tgordon Date 2008-09-09 Time 08:07 Rev Time 1.30
Received By tgordon Date 2008-09-09 Time 08:07 Sent To  
Notes
2008-09-09 08:15:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS M-1 AND M-2.
 *** DENIED ***
  
 1) MECHANICAL PLAN M-2 EQUIPMENT SCHEDULE A/C SYSTEM #1
 IS A 9.95 EER. PER 2004 FBC 13-407.1.ABC.3.2A (TABLE)
 THE MINIMUM EER IS 10.3 FOR THIS SIZE SYSTEM. PLEASE
 CORRECT.
  
 2) THE COOLING LOAD CALCULATIONS WILL NEED TO BE
 REVISED AS THE COOLING ZONES HAVE CHANGED, PER 2004 FBC
 13-407.1.ABC.1 AND 13-407.1.ABC.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-05-22 Cont ID  
Sent By tgordon Date 2008-05-22 Time 13:38 Rev Time 0.45
Received By tgordon Date 2008-05-22 Time 13:38 Sent To  
Notes
2008-05-22 13:49:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION PG. M-1 AND M-2.
  
 *** DENIED ***
 1)A/C SYSTEM #1 MODEL NUMBERS (C/U 2TTA0072 A/H
 TWE063P13) LISTED ON THE A/C EQUIPMENT SCHEDULE COULD
 NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE
 CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 FBC
 13-407.1.ABC.3.1.1.
  
 2) FLEX DUCT FROM AC-1 TO 10X10 OUTSIDE AIR DUCT NEEDS
 TO BE SIZED, PER 2004 FBC/M 106.3.3.
  
 3) PROVIDE OUTDOOR AIR CALCULATION, PER 2004 FBC/M
 403.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-05-03 Cont ID  
Sent By tgordon Date 2007-05-03 Time 09:27 Rev Time 0.30
Received By tgordon Date 2007-05-03 Time 09:27 Sent To  
Notes
2007-05-03 09:33:17*** PROVISO ***
 1) CLOTHES DRYER VENT MUST COMPLY WITH CLOTHES DRYER
 MANUFACTURER'S SPECIFICATION'S.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-29 Cont ID  
Sent By tgordon Date 2007-03-29 Time 11:23 Rev Time 0.45
Received By tgordon Date 2007-03-29 Time 11:23 Sent To  
Notes
2007-03-29 11:34:24*** DENIED ***
 1) IT HAS BEEN OBSERVED THAT MOST CLOTHES DRYER
 MANUFACTURES WILL NOT WARRANTY THEIR EQUIPMENT IF A
 BOOSTER FAN IS INSTALLED IN THE DRYER VENT, PLEASE
 PROVIDE A TECHNICAL SUBMITTAL FROM THE CLOTHES DRYER
 MANUFACTURE STATING THE WARRANTY WILL NOT BE VOIDED IF
 A BOOSTER FAN IS USED, PLEASE DO NOT PROVIDE
 INFORMATION FROM A SALES DEPARTMENT
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-15 Cont ID  
Sent By tgordon Date 2007-02-15 Time 13:40 Rev Time 1.15
Received By tgordon Date 2007-02-15 Time 13:40 Sent To  
Notes
2007-02-15 13:48:37*** DENIED ***
 1) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1.
  
 2) AS THE CLOTHS DRYER VENT IS OVER 25 FEET, PLEASE
 SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR THE CLOTHS DRYER.
  
 3) SEE MECHANICAL PLANS PAGE M-1, EF-5 NEEDS TO BE 50
 CFM'S., SEE 2004 FBC/M TABLE 403.3 PUBLIC SPACES,
 SHOWER ROOM, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 7 Status P Date 2009-01-14 Cont ID  
Sent By lwagner Date 2009-01-14 Time 10:30 Rev Time 0.00
Received By lwagner Date 2009-01-14 Time 10:18 Sent To  
Notes
2009-01-14 10:19:27REVISION OK- SHEET 3

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-12-01 Cont ID  
Sent By kstevens Date 2008-12-01 Time 12:11 Rev Time 0.00
Received By kstevens Date 2008-12-01 Time 12:11 Sent To  
Notes
2008-12-01 12:17:11REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. OK
 2. OK
  
 3. SHT 3 OF 4. NEW FLOOR DRAIN IS INDICATED AS A FLOOR
 SINK ON THE FLOOR PLAN. A FLOOR SINK IS REQUIRED FOR
 INDIRECT WASTE. SECTION 802.3. FLOOR SINK SHALL CONNECT
 TO THE VENTED LINE PER SECTION 912.2.4, NOT TO THE
 BRANCH/FIXTURE LINE FOR THE OTHER FLOOR DRAIN IN SPA 2.
 A SEPARATE VENT FOR NEW FLOOR SINK WOULD ALSO WORK.
 SECTION 901.2.1.
 ****RESPONSE NOTED, BUT THE FLOOR PLAN AND SANITARY
 RISER DIAGRAM STILL SHOW THE DRAIN FOR THE ICE MACHINE
 AS A FLOOR DRAIN. A FLOOR SINK IS REQUIRED FOR INDIRECT
 WASTE. FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE
 RECEPTORS.
  
 ***********NEW COMMENT**********
  
 1B. A RELIEF VENT IS REQUIRED FOR THE AIR ADMITTENCE
 VALVE INDICATED ON THE NEW S-4 SINK. SECTION 917.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-08-28 Cont ID  
Sent By kstevens Date 2008-08-28 Time 09:12 Rev Time 0.00
Received By kstevens Date 2008-08-28 Time 09:12 Sent To  
Notes
2008-08-28 09:24:23REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT 3 OF 4. A WATER HAMMER ARRESTOR IS REQUIRED ON
 THE WATER SUPPLY LINE TO THE ICE MAKER. SECTION 604.9 &
 PDI-WH 201.
  
 2. SHT 3 OF 4. THE NEW S-4 SINK DRAIN SHALL NOT DRAIN
 THRU THE HORIZONTAL WET VENT FOR THE TOILET ROOM
 FIXTURES. ALL OTHER FIXTURES SHALL DISCHARGE DOWNSTREAM
 OF THE HORIZONTAL WET VENT. SECTION 909.1. SINK SHALL
 CONNECT DOWNSTREAM OF THE TOILET ROOM FIXTURES.
  
 3. SHT 3 OF 4. NEW FLOOR DRAIN IS INDICATED AS A FLOOR
 SINK ON THE FLOOR PLAN. A FLOOR SINK IS REQUIRED FOR
 INDIRECT WASTE. SECTION 802.3. FLOOR SINK SHALL CONNECT
 TO THE VENTED LINE PER SECTION 912.2.4, NOT TO THE
 BRANCH/FIXTURE LINE FOR THE OTHER FLOOR DRAIN IN SPA 2.
 A SEPARATE VENT FOR NEW FLOOR SINK WOULD ALSO WORK.
 SECTION 901.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-06-03 Cont ID  
Sent By jleech Date 2008-06-03 Time 08:36 Rev Time 0.00
Received By jleech Date 2008-06-03 Time 08:03 Sent To  
Notes
2008-06-03 08:37:05REVISED RISER DIAGRAM

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-05-09 Cont ID  
Sent By jleech Date 2007-05-09 Time 07:15 Rev Time 0.00
Received By jleech Date 2007-05-09 Time 07:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-31 Cont ID  
Sent By jleech Date 2007-03-31 Time 07:34 Rev Time 0.00
Received By jleech Date 2007-03-31 Time 07:34 Sent To  
Notes
2007-03-31 07:50:40DENIED;
 1. WATER RISER DIAGRAM; WATER HAMMER ARRESTORS ARE
 REQUIRED FOR ALL QUICK CLOSE VALVES ONLY. ONLY THE
 JUICE BAR SINK AND THE AUTOMATIC CLOTHES WASHER HAVE
 QUICK CLOSING VALVES. WATER HAMMER ARRESTORS TO BE
 INSTALLED PER MANUFATURE SPECIFICATIONS, AT THE BOTTOM
 OF THE DROPS NOT IN CEILING.
 2.SANITARY RISER DIAGRAM; ADD DRINKING FOUNTAIN TO
 RISER DIAGRAM.
 3. A THERMAL EXPANSION CONTROL IS REQUIRED AT WATER
 HEATER. SHOW OR MAKE A NOTE ON PLAN. SPEC TYPE AND SIZE
 TO BE INSTALLED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-15 Cont ID  
Sent By jleech Date 2007-02-15 Time 09:39 Rev Time 0.00
Received By jleech Date 2007-02-15 Time 09:39 Sent To PC
Notes
2007-02-15 10:26:30DENIED;
 1. PLUMBING FIXTURE SCHEDULE, TOILETS TO BE ELONGATED
 TYPE (NOT SURE OF MODEL NUMBER) AND SEAT TO BE OPEN
 FRONT. SEE FBC PLUMBING SECTIONS, 420.2 AND 420.3.
 2. PLUMBING NOTE # 12; SEE SECTION 410.1. THE ONLY
 EXCEPTION FOR NOT INSTALLING A DRINKING FOUNTAIN IS FOR
 A RESTAURANT. DRINKING FOUNTAIN IS REQUIRED , SEE TABLE
 403.1 (2B).
 3. PLUMBING NOTE # 8; PVC PIPE CAN ONLY BE USED 5' INTO
 A BUILDING 605.3. SEE TABLE 605.4 FOR TYPE OF MATERIAL
 THAT CAN BE USED.
 4. PAGE 1 FLOOR PLAN NOTE #16;SHOW A DETAIL WITH ALL
 REQUIRED MEASUREMENTS TO MEET HANDICAP REQUIREMENTS
 PER. FBC-2004 BUILDING CHAPTER 11. SEE SECTION
 11-4.24.2 THRU 11-4.24.7.
 5. SANITARY RISER DIAGRAM;
 A) AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO
 BE 3" SECTION 406.3.
 B)FLOOR DRAIN IN WORK ROOM NOT VENTED AND
 SHOULD HAVE A TRAP PRIMER.
 C) F/D IN WOMAN'S ROOM NOT VENTED.
 D) F/D IN WOMAN'S SHOWER ROOM NOT VENTED.
 E) F/D IN MEN'S ROOM MISSING.
 F) F/D MEN'S SHOWER ROOM NOT VENTED.
 6. WATER RISER DIAGRAM; AUTOMATIC CLOTHES WASHER
 REQUIRE WATER HAMMER ARRESTORS, TOBE INSTALLED PER
 MANUFACTURE INSTALLATION INSTRUCTIONS. SEE SECTION
 604.9.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2008-09-05 Cont ID  
Sent By mflis Date 2008-09-05 Time 08:36 Rev Time 0.00
Received By mflis Date 2008-09-05 Time 08:36 Sent To  
Notes
***NONE***