Plan Review Details - Permit 07020266
Plan Review Stops For Permit 07020266
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-09-05 Cont ID  
Sent By jwitmer Date 2008-09-05 Time 14:10 Rev Time 2.22
Received By jwitmer Date 2008-09-05 Time 14:10 Sent To  
Notes
2008-09-05 14:12:38REVISION # 5 OK,
 BUILDING PROVISO: RESTROOM# 2 REVERSE SWING OF DOOR
 11-4.13.6 A MINIMUM OF 18" REQUIED FOR LATCH SIDE OF
 DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-31 Cont ID  
Sent By jwitmer Date 2007-07-31 Time 08:09 Rev Time 0.77
Received By jwitmer Date 2007-07-30 Time 09:50 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 08:40 Rev Time 2.22
Received By jwitmer Date 2007-06-13 Time 08:40 Sent To PC
Notes
2007-06-13 08:57:39BUILDING PLAN REVIEW
 PERMIT: 07020266
 ADD: 600 N DIXIE HWY# 105
 CONT: AMERICAN HOME CARE
 TEL: (954)646-2283
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 2ND REQUEST, PLEASE PROVIDE THE MANUFACTUREER'S
 INFORMATION ON THE X-RAY EQUIPMENT INDICATEING THAT
 SHIELDING IS NOT REQUIRED BECAUSE OF THE STRENGHT OF
 THE X-RAYS, SHIELDING REQUIREMENTS ARE NOT REQUIRED.
 PLANS INDICATE THE EITHER X-RAY MACHINES OR FUTURE
 X-RAY MACHINES, PLEASE SEE FBC 435.1 FOR SHIELDING
 REQUIREMENTS.
  
 4) PERMIT APPLICATION INDICATES WORK TO BE COMPLETED AT
 600 N DIXIE WHERE AS THE PLANS INDICATE A CHANGE TO 600
 SOUTH DIXIE? PLEASE CORRECT.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By jwitmer Date 2007-03-15 Time 12:40 Rev Time 2.22
Received By jwitmer Date 2007-03-15 Time 12:40 Sent To FIRE
Notes
2007-03-15 14:21:44BUILDING PLAN REVIEW
 PERMIT: 07020266
 ADD: 600 N DIXIE HWY# 105
 CONT: AMERICAN HOME CARE
 TEL: (954)646-2283
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS INDICATE THE EITHER X-RAY MACHINES OR FUTURE
 X-RAY MACHINES, PLEASE SEE FBC 435.1 FOR SHIELDING
 REQUIREMENTS.
  
 4) PLANS INDICATE AN "X" WHERE THE X-RAY EQUIPMENT WILL
 BE LOCATED, WHAT DOES THIS SYMBOL STAND FOR? IS THIS
 FRAMING MEMBERS?
  
  
 5) PLANS INDICATE THE 2004 FBC PLEASE UPDATE TO THE
 2006 AMENDMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-09-11 Cont ID  
Sent By dpalmer Date 2008-09-11 Time 09:02 Rev Time 0.00
Received By dpalmer Date 2008-09-11 Time 09:02 Sent To  
Notes
2008-09-11 09:02:45 
  
  
  
 ** DENIED REVIEW OF REVISION**
  
  
  
 1) NOTE: PLEASE SEE FBC 13-101.1 AS THE METHOD *A*
 SUBMITTED MAY NOT BE USED. THIS IS NOT A WHOLE
 BUILDING.
  
 2) NOTE: PLEASE SEE REVIEW NOTES FROM 6/13/08 WHICH ARE
 STILL IN NEED OF ADDRESSING. THESE WILL BE ATTACHED.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-06-13 Cont ID  
Sent By dpalmer Date 2008-06-13 Time 16:28 Rev Time 0.00
Received By dpalmer Date 2008-06-13 Time 16:28 Sent To  
Notes
2008-06-13 16:29:50** DENIEDREVISION**
  
 1) NOTE: PLEASE BE SURE ALL CIRCUITING IS SHOWN ON
 PLANS AND COORDINATE WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY LIGHTS
 AND EXIT LIGHTS. THESE ARE REQUIRED TO BE CIRCUITED TO
 THE LOCAL LIGHTING IN ANY ONE AREA.
 PLEASE SEE MANY OF THESE SHOWN ON PLANS DO NOT CONTAIN
 ANY CIRCUITING.
 PLEASE BE SURE TO SUBMIT REVISE LIGHTING PLANS ALSO AND
 COORDINATE WITH PANEL SCHEDULES.
 PLEASE BE SURE TO REVISE ANY LIGTHING PERFORMANCE
 CALCULATIONS FOR ANY REVISED LIGTHING SINCE PERMIT
 ISSUED PLANS WERE DONE.
  
 408.4, 310.16, 240.4, 700.12F,ETC
 13-415.2.ABC.1.1, .1.2, 13-415.2.
 FBC 106.1.2, 106.3.5.1.2, 106.5 FOR ADDITIONAL
 INFORMATION, COORDINATION AND RECORDS RETENTION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 13:00 Rev Time 0.00
Received By dpalmer Date 2007-08-23 Time 11:57 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-08-09 Cont ID  
Sent By dpalmer Date 2007-08-09 Time 09:17 Rev Time 0.00
Received By dpalmer Date 2007-08-08 Time 20:03 Sent To PC
Notes
2007-08-09 09:23:50 
 1) NOTE: PLANS IN FAILED STATUS UNTIL THE CERTIFICATION
 SHEETS IN THE ENERGY CALCULATIONS ARE SUBMITTED WITH
 ORIGINAL SIGNATURES. PLEASE SEE BOTH SETS SUBMITTED DO
 NOT CONTAIN ORIGINAL SIGNATURES. PLEASE SEE ONE IS A
 COLOR COPY/PRINT AND THE OTHER IS A PHOTO-COPY. BOTH
 MUST CONTAIN ORIGINAL SIGNATURES FOR CERTIFICATION OF
 DOCUMENTS AS REQUIRED UNDER FBC 13-103.1.1.1. PLEASE BE
 SURE THE ARCHITECT RE-SIGNS, DATES AND SEALS SHEETS.
  
 ** PLANS WILL BE OUT FOR PICK UP FOR NEW CALCULATIONS
 TO BE BROUGHT IN. SPOKE TO CONTRACTOR AND ARCHITECT.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
2007-08-08 20:03:46IN ELEC FOR REIVEW.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-06 Cont ID  
Sent By dpalmer Date 2007-07-06 Time 07:55 Rev Time 0.00
Received By dpalmer Date 2007-07-05 Time 17:51 Sent To I
Notes
2007-07-06 07:57:112007-07-06 07:57:11
 ** UNSAT **
  
 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS STILL DO
 NOT CORRELATE WITH THE FIXTURE LEGEND ON PLANS. PLEASE
 SEE THE RESPONSE HAND WRITTEN ON NOTES SHEETS MENTIONS
 THE CERTAIN FIXTURES ARE EXEMPT UNDER 13-415.2.B.2,
 HOWEVER PLEASE SEE THIS SECTION OF THE CODE DOES NOT
 APPLY TO THE CALCULATIONS SUBMITTED AND THE USE AS
 SHOWN. PLEASE SEE ADDITIONAL ALLOWANCES ARE PERMITTED,
 HOWEVER THAT DOES NOT MEAN THEY ARE EXEMPT. IN EITHER
 CASE THE SECTION REFERENCED IS FOR SPACE BY SPACE
 CALCULATIONS AND PERFORMANCE MEASURES.
 PLEASE SEE 13-415.1.AB.1.,13-415.1.A, 13-415.2
  
 PLEASE REVISE AND ADJUST.
  
 2) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS DOWN
 THE LEFT HADN SIDE OF THE PLANS. THESE WERE REMOVED
 FROM PLANS BY THIS OFFICE ON THIS REVIEW AND PLACED
 INTO TWO PACKAGES FOR EACH.
 FBC106.1
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-06 07:02:042007-07-06 07:02:04
 REVIEW IN PROGRESS
2007-07-05 17:51:502007-07-05 17:51:50
 PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO
 INCOMING WAITING FOR THE COMM BOARD ONCE ELECTRICLA
 REVIEW IS DONE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-18 Cont ID  
Sent By dpalmer Date 2007-04-18 Time 18:25 Rev Time 0.00
Received By dpalmer Date 2007-04-18 Time 18:25 Sent To  
Notes
2007-04-18 18:28:10 
 ** UNSAT2ND REVIEW**
  
  
 1) NOTE: PLEASE COORDINATE ADDRESS. PLEASE SEE THE
 PERMIT APPLICATION STILL CONTAINS THE ADDRESS AND
 PARCEL CONTROL NUMBER (PCN) FOR 600 N. DIXIE WHEN THE
 SCOPE OF WORK IS BEING DONE AT 600 SOUTH DIXIE. PLEASE
 BE SURE TO CHANGE APPLICATION AND OWNER INFORMATION AS
 THE OWNER FOR 600 S DIXIE IS NOT GRAND TRUST BANK.
  
 2) NOTE: PLEASE SEE THAT ALL RAISED SEALS SHALL BE
 CLEAR AND VISIBLE WITH ALL INFORMATION ON SAID SEAL
 WHICH IS REQUIRED READABLE.THE INFORMATIONON MOST
 OF THE SEALS ON SHEETS WILL NOT PROVIDE ALL INFORMATION
 ON SEAL EVEN WHEN USING A LEAD RUB NOT APPLIED WITH
 PENCIL.
 PLEASE BE SURE ALL PLANS SHEETS AND ENERGY CALCULATIONS
 ARE SEALED WITH READABLE RAISED SEAL.
 FS 481.221, FAC61G1-16.002,.3
  
 3) NOTE: PLEASE SEE THE NOTE FROM PREVIOUS REVIEW NEEDS
 TO BE CLARIFIED FOR THESE LOCATIONS. A HANDWRITTEN
 RESPONSE MENTIONS THERE IS NO ANESTHETIZING AT THIS
 LOCATION AND TO SEE NOTE #8, HOWEVER NOTE #8 DOES NOT
 SEEM TO CONTAIN ANY MENTIONING OF THIS?
 PLEASE 517.60, 517.62 AND OTHER PARTS OF 517. PLEASE
 SPECIFY AREAS AND USE IN THESE AREAS. PLEASE SPECIFY
 ANY USE OF ANESTHETIZING LOCATIONS IF THIS APPLIES TO
 THIS OFFICE AND USE.
 NOTES WERE LOCATED FOR TYPE OF WIRING METHODS AND
 GROUNDING AS REQUIRED.
  
 4) NOTE: PLEASE KNOW THAT IN NOTED RESPONSE FROM
 ARCHITECT WHICH WAS WRITTEN ON THE REVIEW NOTES FROM
 PREVIOUS REVIEW IT MENTIONS "THIS REVIEWER IS GETTING
 TOO PICKY", PLEASE KNOW THAT THIS REQUIREMENT WAS
 ADOPTED INTO THE NEW CODE AND THE TEXT IN THE PREVIOUS
 NOTE WAS EXTRACTED DIRECTLY FROM THE CODE. PLEASE
 CONTACT THE CODE PANELIST FOR ANY ROP'S (REQUEST FOR
 PROPOSALS).
 THIS IS A MINIMUM REQUIREMENT WHICH IS SET FORTH FROM
 NFPA AND NOT THIS OFFICE.
 THIS NOTE WILL REMAIN AS THERE ARE SOME ITEMS ON PLANS
 WHICH MAY NOT INDICATE CIRCUITING AND ITEMS ON PLANS
 WHICH HAVE NOT BEEN CLEARED UP AND CLARIFICATION FOR
 DESIGNER ON WHAT WILL BE REQUIRED FOR PROJECTS REVIEWED
 IN TEH CITY OF WEST PALM BEACH.
  
 (NOTE FROM PREVIOUS REVIEW) PLEASE CORRELATE PANEL
 SCHEDULE AND COMPLETE PANEL SCHEDULE(S) SO THAT ALL
 ITEMS ON PANEL SCHEDULE ARE SPECIFIC TO AREAS AND ROOMS
 IN WHICH THEY FEED. PLEASE SEE COMMENTARY BELOW
 EXTRACTED FROM THE CODE. *SECTION 408.4 WAS REVISED FOR
 THE 2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR
 EVERY CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD
 BE LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
  
 5) NOTE: PLEASE SEE THIS NOTE REMAINS. IN FACT THE
 EXACT SAME ENERGY CALCULATIONS WERE RESUBMITTED. PLEASE
 SEE THE ADDRESS WAS CHANGED BY HAND WRITING THIS ON
 COVER SHEETS. WHEN ADDRESSING THE CODE COMPLIANCE
 NOTES, PLEASE CHANGE ADDRESS.
 THE USE AS STATED IN THE ENERGY CALCULATIONS STILL
 INDICATES "SALES" IN MORE THAN ONE LOCATION.
 PLEASE SEE THE SEAL IS STILL NOT CLEAR AND VISIBLE SO
 THAT ALL INFORMATION ON SEAL IS READABLE. SEE NOTE FOR
 SEALS ON PLANS.
 PLEASE SEE THE CONTROLS ON CALCULATIONS STILL INDICATE
 *MANUAL ON/OFF* WHEN IN FACT THE PLANS CONTAINS THE
 OCCUPANCY SENSOR TYPE DEVICES.
 THE REST OF THE COMMENT IS THE SAME FROM PREVIOUS
 REVIEW.
 FIXTURES, WATTAGE ETC DO NOT CORRELATE WITH PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE
 WITH THE PLANS. PLEASE SEE THE LIGHTING, WATTAGE,
 NUMBER OF FIXTURES ETC.
 PLEASE BE SURE THE FIXTURE LEGEND STATES THE AMOUNT OF
 LIGHTS FOR EACH TYPE OF FIXTURE SPECIFIED AND
 COORDINATE THIS WITH THE ENERGY CALCULATIONS. THESE DO
 NOT CORRELATE AT ALL AT THIS TIME.
 PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS A
 NOTE STATED ON PLANS, HOWEVER DOES NOT SEEM TO
 CORRELATE WITH ACTUAL PLANS AND CALCULATIONS
 SUBMITTED.
 PLEASE ALSO SEE USE ENTERED IN AS *SALES AREA*?? PLEASE
 SEE THE TABLE IN THE FBC CHAPTER 13 FOR USES. PLEASE BE
 SURE THESES CONTAIN A RAISED SEAL, DATE AND SIGNATURE
 OF THE DESIGNER OF RECORD. PLEASE SEE THE SEAL IS NOT
 VISIBLE WITH INFORMATION ON SAID SEAL AS REQUIRED UNDER
 FS 481.221.
 PLEASE SEE THE CONTROL METHODS ON THE ENERGY
 CALCULATIONS DO NOT CORRELATE WITH PLANS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, 13-415.2
 ETC.
  
 6) NOTE:PLEASE SEE THIS NOTE REMAINS THE LEVELS ADDED
 ON PLANS FOR ADA COMPLIANCE DOES NOT MEET THE MINIMUM
 LEVELS FOR ADA. THE FBC LEVELS FOR ADA ARE MORE
 STRINGENT THAN THAT OF NFPA-72 LEVELS.
 PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE
 THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA
 REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND.
  
 7) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) WHICH IS
 ATTACHED TO NOTES. THIS IS ONLY GIVEN AS A NOTICE AT
 THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-01 Cont ID  
Sent By dpalmer Date 2007-03-01 Time 07:04 Rev Time 0.00
Received By dpalmer Date 2007-02-28 Time 07:45 Sent To  
Notes
2007-03-01 07:05:18** UNSAT **
  
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS
 SUBMITTED
 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE
 STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED
 IN THIS REVIEWER(S) COMMENTS.
  
 2) NOTE:PLEASE CLARIFY WHAT IS BEING SHOWN ON RISER
 OF TWO METERS AND MAINS FOR THIS SINGLE TENANT. PLEASE
 KNOW AS THIS IS ONE OCCUPANCY AND ONE TENANT, ONE METER
 AND MAIN SHOULD BE SHOWN, HOWEVER IT APPEARS TWO ARE
 BEING SHOWN AT THIS TIME??
 PLEASE CLARIFY FBC 106.1.2, 106.3.5.1.2
 104.6.
 PLEASE SEE THIS WOULD ALSO CREATE ZONING AND POSSIBLE
 BUILDING ISSUES WITH ONE OCCUPANCY STATED. ONLY ONE
 TENANT METER WILL BE PERMITTED BASED ON THE SINGLE
 OCCUPANCY AT THIS TIME.
  
 3) NOTE: PLEASE 517.60, 517.62 AND OTHER PARTS OF 517.
 PLEASE SPECIFY AREAS AND USE IN THESE AREAS. PLEASE
 SPECIFY ANY USE OF ANESTHETIZING LOCATIONS IF THIS
 APPLIES TO THIS OFFICE AND USE.
 NOTES WERE LOCATED FOR TYPE OF WIRING METHODS AND
 GROUNDING AS REQUIRED.
  
 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE
 PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE
 ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED.
 PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 5) NOTE: PLEASE SHOW LOAD CALCULATIONS ON THE EXISTING
 SERVICE (800 AMP DISCONNECT) NEC 220
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER
 215.3, AND 230.42 PLEASE INDICATE THE SIZE OF WHAT IS
 BEING SHOWN FOR THE EXISTING PANEL AND LOAD ON PANEL
 ALONG WITH NEW LOADS.
  
  
 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT
 CORRELATE WITH THE PLANS. PLEASE SEE THE LIGHTING,
 WATTAGE, NUMBER OF FIXTURES ETC.
 PLEASE BE SURE THE FIXTURE LEGEND STATES THE AMOUNT OF
 LIGHTS FOR EACH TYPE OF FIXTURE SPECIFIED AND
 COORDINATE THIS WITH THE ENERGY CALCULATIONS. THESE DO
 NOT CORRELATE AT ALL AT THIS TIME.
 PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS A
 NOTE STATED ON PLANS, HOWEVER DOES NOT SEEM TO
 CORRELATE WITH ACTUAL PLANS AND CALCULATIONS
 SUBMITTED.
 PLEASE ALSO SEE USE ENTERED IN AS *SALES AREA*?? PLEASE
 SEE THE TABLE IN THE FBC CHAPTER 13 FOR USES. PLEASE BE
 SURE THESES CONTAIN A RAISED SEAL, DATE AND SIGNATURE
 OF THE DESIGNER OF RECORD. PLEASE SEE THE SEAL IS NOT
 VISIBLE WITH INFORMATION ON SAID SEAL AS REQUIRED UNDER
 FS 481.221.
 PLEASE SEE THE CONTROL METHODS ON THE ENERGY
 CALCULATIONS DO NOT CORRELATE WITH PLANS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, 13-415.2
 ETC.
  
 7) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND.
  
 8) NOTE: PLEASE SEE THERE ARE SEVERAL FIXTURES ON PLANS
 WITHOUT DESIGNATIONS, PLEASE INCLUDE FOR REVIEW OF
 CHAPTER 13 REQUIREMENTS.
 PLEASE ALSO SEE 13-415.1.ABC.3 WHERE APPLICABLE.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-09-19 Cont ID  
Sent By mwennerg Date 2008-09-19 Time 10:05 Rev Time 0.00
Received By mwennerg Date 2008-09-19 Time 10:05 Sent To  
Notes
2008-09-19 10:06:12REVISION DATED 7/25/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 18:00 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 17:48 Sent To  
Notes
2007-07-26 17:56:07****PROVISO*****
  
 THECOMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN REVIEWS
 HAVE BEEN ADDRESSED;HOWEVER, THE APPROPIATE PLAN
 SHEET(S) WILL BE FIRE-STAMPED WHEN ALL REVIEWS HAVE
 BEEN SATISFIED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 16:30 Rev Time 0.00
Received By mawillia Date 2007-05-07 Time 16:14 Sent To  
Notes
2007-05-07 16:29:49*****DENIED*****
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 02.ON SHEET 1, THE MENTIONED CODE OF 2003 NFPA 101 IS
 CORRECT.HOWEVER, ROOM FINISH NOTE #8INCORRECTLY
 REFERENCES 2005 NFPA 101.
  
 06.SHOW/DISPLAY THESUITE NUMBER ON THE EXTERIOR
 ELEVATION SO THAT THIS TENANT SPACE IS DISTINGUISHABLE
 FROM THE OTHER SUITES.AS PER WEST PALM BEACH CODE,
 THOSE NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO
 LESS THAN 1" IN WIDTH.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE ON THE PLANS EACH COMMENT
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By mawillia Date 2007-03-19 Time 16:53 Rev Time 0.00
Received By mawillia Date 2007-03-19 Time 16:43 Sent To  
Notes
2007-03-19 16:53:08*****DENIED*****
  
  
 01.THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK WILL
 BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.THE CORRECT ADDRESS FOR THIS
 LOCALE IS 600 SOUTH DIXIE HIGHWAY - SUITE 103.
  
 02.ON SHEET 1, THE MENTIONED CODE OF 2003 NFPA 101 IS
 CORRECT.HOWEVER, ROOM FINISH NOTE #8INCORRECTLY
 REFERENCES 2005 NFPA 101.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER WITH EMERGENCY ACCESS RESPONSE TO THE
 STRUCTURE OR THE VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 05.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXITS. THIS SHEET MAY ALSO
 INCLUDE THE LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS,
 FIRE EXTINGUISHERS,FIRE ALARM DEVICES, AND FIRE
 SPRINKLERS APPLICABLE TO THE PROPOSED STRUCTURE.
  
 06.SHOW/DISPLAY THESUITE NUMBER ON THE EXTERIOR
 ELEVATION SO THAT THIS TENANT SPACE IS DISTINGUISHABLE
 FROM THE OTHER SUITES.AS PER WEST PALM BEACH CODE,
 THOSE NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO
 LESS THAN 1" IN WIDTH.
  
 07.IF SO EQUIPPED WITH A FIRE ALARM SYSTEM, WILL IT
 BE INDEPENDANT OR WILL IT BE TIED INTO THE PRADO
 CONDOMINIUM'S SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE ON THE PLANS EACH COMMENT
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-11-18 Cont ID  
Sent By adarroug Date 2008-11-18 Time 15:31 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 15:31 Sent To  
Notes
2008-11-18 15:34:16TO "COMM" BD#46

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-08-25 Cont ID  
Sent By tgordon Date 2008-08-25 Time 10:06 Rev Time 0.00
Received By tgordon Date 2008-08-25 Time 10:06 Sent To  
Notes
2008-08-25 10:07:33TO "COMM" BD #5

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-05-21 Cont ID  
Sent By adarroug Date 2008-05-21 Time 10:39 Rev Time 0.00
Received By adarroug Date 2008-05-21 Time 10:39 Sent To  
Notes
2008-05-27 16:04:19TO "COMM" BD#24
2008-05-21 10:40:27WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 11:18 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 11:18 Sent To E
Notes
2007-08-23 11:19:49TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 16:11 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 16:11 Sent To E
Notes
2007-08-03 16:11:57TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-25 Cont ID  
Sent By adarroug Date 2007-06-25 Time 16:36 Rev Time 0.00
Received By adarroug Date 2007-06-25 Time 16:36 Sent To  
Notes
2007-07-12 14:47:16TO "COMM" BD#17
2007-06-25 16:36:37WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 15:07 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 15:07 Sent To  
Notes
2007-04-16 15:12:35TO "COMM" BD#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-19 Cont ID  
Sent By mawillia Date 2007-03-19 Time 16:43 Rev Time 0.00
Received By mawillia Date 2007-02-12 Time 16:35 Sent To  
Notes
2007-02-26 11:30:18TO "COMM" BD#4
2007-02-12 16:36:22WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-12-13 Cont ID  
Sent By rregueir Date 2008-12-13 Time 09:31 Rev Time 0.00
Received By rregueir Date 2008-12-13 Time 09:01 Sent To  
Notes
2008-12-13 09:31:28REVISED M1, M2, COOLING LOAD CALCS

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2008-09-08 Cont ID  
Sent By tgordon Date 2008-09-08 Time 14:11 Rev Time 1.30
Received By tgordon Date 2008-09-08 Time 14:11 Sent To  
Notes
2008-09-08 14:26:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS M-1 AND M-2.
 *** DENIED ***
  
 1) COOLING LOAD CALCULATIONS SUBMITTED FOR A/C SYSTEM
 #1 IS CALLING FOR 40,502 TOTAL COOLING BTU'S, THE
 MECHANICAL PLANS ARE SHOWING SYSTEM #1 AS 57,000 TOTAL
 COOLING BTU'S. A 5 TON A/C SYSTEM IS TO LARGE PER THE
 COOLING LOAD CAL'S, A 3.5 TON WOULD MEET THE
 REQUIREMENTS (SEE ATTACHED ARI CERTIFICATE), PER 2004
 FBC/M 13-407.1.ABC.1.1. PLEASE CORRECT.
  
 2) PLEASE SHOW ON THE MECHANICAL PLANS THE OUTDOOR AIR
 CALCULATIONS, AS THE OUTDOOR AIR BEING PROVIDED APPEARS
 NOT TO BE ENOUGH, PER 2004 FBC/M 403.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-06-17 Cont ID  
Sent By tgordon Date 2008-06-17 Time 08:15 Rev Time 0.45
Received By tgordon Date 2008-06-17 Time 08:15 Sent To  
Notes
2008-06-17 08:24:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS
 *** DENIED ***
  
 1) AS THE A/C SYSTEMS BEING INSTALLED HAVE CHANGED, THE
 ENERGY CALCULATIONS AND COOLING LOAD CALCULATIONS WILL
 NEED TO BE REVISED, PER 13-400.3.ABC.2 AND
 13-407.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-26 Cont ID  
Sent By rregueir Date 2007-07-26 Time 10:38 Rev Time 0.00
Received By rregueir Date 2007-07-26 Time 10:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-03 Cont ID  
Sent By rregueir Date 2007-05-03 Time 14:50 Rev Time 0.00
Received By rregueir Date 2007-05-01 Time 09:45 Sent To  
Notes
2007-05-03 14:50:00--------------DENIED-----------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH. 1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. INFORMATION WAS REQUESTED IN PREVIOUS REVIEW
 REGARDING THE ALLOWABLE LENGTH AND ELEVATION DIFFERENCE
 BETWEEN AHU AND CU. NO INFORMATION WAS PROVIDED FROM
 THE MANUFACTURER. EQUIPMENT AND APPLIANCES SHALL BE
 INSTALLED AS REQUIRED BY THE TERMS OF THEIR APPROVAL,
 IN ACCORDANCE WITH THE CONDITIONS OF THE LISTING, THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AND THIS CODE.
 IF THE DESIGNER WANTS TO PROVIDE ADDITIONAL
 INFORMATION, SUCH AS CALCULATIONS, VERIFYING THE
 FEASIBILITY OF THE INSTALLATION CONDITIONS, PLEASE
 INCLUDE THESE CALCULATIONS ON THE PLAN. FBC,M 106.1.3.
  
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-13 Cont ID  
Sent By rregueir Date 2007-03-13 Time 14:57 Rev Time 0.00
Received By rregueir Date 2007-03-13 Time 09:33 Sent To  
Notes
2007-03-13 15:10:56-----------------DENIED-----------------
  
 1. PLEASE PROVIDE MANUFACTURER'S SUBMITTAL DATA SHOWING
 MAXIMUM ALLOWABLE ELEVATION DIFFERENCE BETWEEN AHU AND
 ROOFTOP CONDENSING UNIT. ALSO, PLEASE SHOW THE
 ELEVATION DIFFERENCE BETWEEN COMPONENTS AS IT WILL
 OCCUR IN THIS CASE. WILL COPPER LINE SIZES BE AFFECTED
 BY THIS CONDITION? FBC,M 304.1.
  
 2. PG M1: AIR CONDITIONING CONTROL SEQUENCE
 NOTE #3 - DUCT SMOKE DETECTORS SHALL BE CONNECTED TO
 THE BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1.
  
 3. PLEASE SHOW MEANS/LOCATION OF CONDENSATE DISPOSAL,
 DEMONSTRATING COMPLIANCE WITH FBC,M 307.2.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 4 Status F Date 2008-06-09 Cont ID  
Sent By kstevens Date 2008-06-09 Time 11:44 Rev Time 0.00
Received By kstevens Date 2008-06-05 Time 15:00 Sent To  
Notes
2008-06-09 11:52:00REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 NFPA
  
 1. SHT 3 OF 4 INDICATES THE VACUUM EXHAUST TO BE
 TERMINATED OUT THE NORTH WALL. PER SECTION 713.6 THE
 EXHAUST FROM A VACUUM PUMP SERVING A VACUUM (FLUID
 SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO OPEN AIR
 ABOVE THE ROOF.
  
 2. PIPING SHALL NOT BE THRU THE STAIRWELL PER NFPA-101
 SECTION 7.1.3.2.1(6). PLEASE SHOW THE ROUTING OF THE
 EXHAUST FOR THE VACUUM AND THE INTAKE FOR THE
 COMPRESSOR.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop MEDGAS MEDICAL GAS
Rev No 3 Status P Date 2007-07-20 Cont ID  
Sent By kstevens Date 2007-07-20 Time 07:55 Rev Time 0.00
Received By kstevens Date 2007-07-20 Time 07:55 Sent To  
Notes
2007-07-20 11:07:28PASSED PROVISO - VACUUM VENT TO COMPLY WITH 713.6

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status F Date 2007-05-30 Cont ID  
Sent By kstevens Date 2007-05-30 Time 16:54 Rev Time 0.00
Received By kstevens Date 2007-05-30 Time 16:54 Sent To  
Notes
2007-05-30 16:58:01DENIED
 REFERENCE: NFPA 99C 2002
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. THE EXHAUST VENT FOR THE VACUUM SHALL TERMINATE
 SEPARATELY ABOVE THE ROOF TO OPEN AIR. SECTION 713.6.
 ****RESPONSE NOTED, BUT THE REQUIREMENT IS NOT
 ADDRESSED. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE.
  
 5. SHT 3 AIR/VACUUM INDICATES A 1/2" FILTERED WATER
 LINE TO THE VACUUM. PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED. BACKFLOW PROTECTION IS REQUIRED FOR
 THE WATER CONNECTION PER SECTION 608. PLEASE INDICATE
 THE METHOD OF PROTECTION.
  
 6. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2007-03-10 Cont ID  
Sent By kstevens Date 2007-03-10 Time 17:15 Rev Time 0.00
Received By kstevens Date 2007-03-10 Time 17:15 Sent To  
Notes
2007-03-10 17:34:05DENIED
 REFERENCE: NFPA 99C 2002
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. 1. AIR COMPRESSORS AND VACUUM PUMPS SHALL BE
 INSTALLED IN A DESIGNATED MECHANICAL EQUIPMENT AREA,
 VENTILATED AND WITH REQUIRED UTILITIES (E.G.,
 ELECTRICITY, DRAINS, LIGHTING, ETC.). SUBMIT A DETAIL
 SHOWING THE COMPRESSOR & VACUUM AND ALL OTHER
 REQUIREMENTS AS DESCRIBED. SECTION 5.3.3..3.7.1.
  
 2. SUBMIT A DETAIL FOR THE COMPRESSOR SHOWING
 COMPLIANCE WITH SECTION 5.3.3.5.3 (1) THRU (17). (SEE
 ATTACHED SHEET - FIGURE A.5.3.3.4).
  
 3. SUBMIT A DETAIL FOR THE VACUUM SHOWING COMPLIANCE
 WITH SECTION 5.3.3.6 AND ALL SUBSECTIONS. (SEE ATTACHED
 SHEET - FIGURES A.5.3.3.6(A),A5.3.3.6(B),
 A5.3.3.6(C), OR A5.3.3.6(D).
  
 4. THE EXHAUST VENT FOR THE VACUUM SHALL TERMINATE
 SEPARATELY ABOVE THE ROOF TO OPEN AIR. SECTION 713.6.
  
 5. SHT 3 AIR/VACUUM INDICATES A 1/2" FILTERED WATER
 LINE TO THE VACUUM. PLEASE CLARIFY. SECTION 106.1.1.
  
 6. SHT 3 SHOWS WSF (FILTER). THE FILTER SHALL COMPLY
 WITH NSF 42. SECTION 611.1. PLEASE SUBMIT MANUF.
 SPECIFICATION SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-08-28 Cont ID  
Sent By kstevens Date 2008-08-28 Time 09:11 Rev Time 0.00
Received By kstevens Date 2008-08-27 Time 17:54 Sent To  
Notes
2008-08-28 09:11:59PLUMBING REVISION OK--SHT 3 OF 4

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-06-09 Cont ID  
Sent By kstevens Date 2008-06-09 Time 11:18 Rev Time 0.00
Received By kstevens Date 2008-06-05 Time 15:00 Sent To  
Notes
2008-06-09 11:44:37REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 NFPA
  
 1. THE REFERENCE SHEET SHOWING THE ROUTING OF THE VENT
 PIPE IS NOT APPROVED. NFPA 101 SECTION 7.1.3.2.1(6).
 PENETRATIONS INTO, AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ASSEMBLY. PIPING CAN NOT BE ROUTED THRU THE
 STAIRWELL.
  
 2. A RELIEF VENT IS REQUIRED FOR THE AIR ADMITTENCE
 VALVES PER SECTION 917.3.1.
  
 3. SUBMIT AN ELEVATION FOR THE VENT AND AIR INTAKE
 SHOWING ALL DIMENSIONS FROM ALL OPENINGS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-07-20 Cont ID  
Sent By kstevens Date 2007-07-20 Time 07:54 Rev Time 0.00
Received By kstevens Date 2007-07-19 Time 18:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-05-30 Cont ID  
Sent By kstevens Date 2007-05-30 Time 16:58 Rev Time 0.00
Received By kstevens Date 2007-05-30 Time 16:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-10 Cont ID  
Sent By kstevens Date 2007-03-10 Time 15:35 Rev Time 0.00
Received By kstevens Date 2007-03-10 Time 15:35 Sent To  
Notes
2007-03-10 16:01:14DENIED
 REFERENCE: FBC-2004 W/2006 REV.
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC2004 CHAPTER 11
 FBC-2004 BUILDING
  
 1. SHT 1 ROOM FINISH SCHEDULE. TOILET ROOMS 1 & 2 WALL
 FINISH INDICATES GWB PAINTED. THIS DOES NOT MEET THE
 REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT" WALLS AS
 REQUIRED IN SECTION 1210.2. PLEASE INDICATE A HARD
 SURFACE FOR THE WALLS AS REQUIRED.
  
 2. SHT 1 INDICATES A FLOOR DRAIN IN THE LAB. THE RISER
 DIAGRAM INDICATES THIS AS A FLOOR SINK. PLEASE
 CORRELATE RISER AND FLOOR PLAN INFORMATION. SECTION
 106.1.1. IF THE FLOOR SINK IS FOR INDIRECT WASTE, THEN
 A FLOOR SINK IS REQUIRED. IF SO PLEASE INDICATE WHAT
 WILL DRAIN INTO THE FLOOR SINK. SECTION 106.1.2.
  
 3. SHT 2 DETAILS 4 & 5. SHOW COMPLIANCE FOR THE
 FOLLOWING:
 -WATER CLOSETS:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.5 FLUSH CONTROLS
 -FOR LAVS:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
  
 4. SHT 3 WASTE RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN. RISER SHOWS 2 FSC'S IN HYG #1, AND THE FUTURE DL
 & FSC IN OFFICE #1 SHALL BE PIPED THE SAME AS IN THE
 OTHER EXAM ROOMS AS THE FLOOR PLAN IS THE SAME FOR ALL
 ROOMS. PLEASE CORRELATE RISER & FLOOR PLAN. SECTION
 106.1.1.
  
 5. SHT 3 WATER RISER DIAGRAM, IDENTYFY FITTINGS AT THE
 TOP OF ALL DROPS AS THEY ARE NOT IDENTIFIED ON THE
 SYMBOL LEGEND ON SHT 1. SECTION 106.1.1.--A WATER
 HAMMER ARRESTOR IS REQUIRED ON THE ICE MAKER IN THE
 LOUNGE AND THE WASHER IN THE STERILE ROOM AS WELL AS
 ANY OTHER FIXTURE WITH A QUICK CLOSING VALVE. SECTION
 604.9. WHA'S SHALL BE INSTALLED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
  
 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO
 THE OFFICE AND SHALL BE INSTALLED A MAXIMUM OF 4' AFF
 FOR SERVICE AND CERTIFICATION. SECTION 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-09-05 Cont ID  
Sent By mflis Date 2008-09-05 Time 08:35 Rev Time 0.00
Received By mflis Date 2008-09-05 Time 08:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-09 Cont ID  
Sent By mflis Date 2008-06-09 Time 15:56 Rev Time 0.00
Received By mflis Date 2008-06-09 Time 15:56 Sent To  
Notes
2008-06-09 15:57:30ZONING REVIEW: FAILED
  
 ** ANY EXTERIOR PLUMBING, VENTS, OR OTHER EQUIPMENT
 SHALL BE INDICATED ON BUILDING ELEVATIONS SHOWING
 LOCATION AND SIZE FOR REVIEW
 ** PLEASE CONTACT ZONING STAFF TO REVIEW POSSIBLE
 LOCATIONS TO MITIGATE IMPACTS TO BUILDING FACADES AND
 VISIBILITY FROM STREET
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status N Date 2007-03-06 Cont ID  
Sent By mflis Date 2007-03-06 Time 09:06 Rev Time 0.00
Received By mflis Date 2007-03-06 Time 09:06 Sent To  
Notes
2007-03-06 09:07:54ZONING REVIEW: NOT REQUIRED - BUILD-OUT ONLY.
  
 NOTE: ADDRESS IS INCORRECT; SHOULD READ 600 S. DIXIE
  
 MATT FLIS 822-1445


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved