Plan Review Stops For Permit 07020266 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2008-09-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-09-05 |
Time |
14:10 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2008-09-05 |
Time |
14:10 |
Sent To |
|
|
Notes |
2008-09-05 14:12:38 | REVISION # 5 OK, | | BUILDING PROVISO: RESTROOM# 2 REVERSE SWING OF DOOR | | 11-4.13.6 A MINIMUM OF 18" REQUIED FOR LATCH SIDE OF | | DOOR. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-07-31 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-07-31 |
Time |
08:09 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2007-07-30 |
Time |
09:50 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-06-13 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-06-13 |
Time |
08:40 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2007-06-13 |
Time |
08:40 |
Sent To |
PC |
|
Notes |
2007-06-13 08:57:39 | BUILDING PLAN REVIEW | | PERMIT: 07020266 | | ADD: 600 N DIXIE HWY# 105 | | CONT: AMERICAN HOME CARE | | TEL: (954)646-2283 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 2NDREVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2 ) FL S S 713.13 | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | THE COURT. | | NOTE: 713.13(2) | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 3) 2ND REQUEST, PLEASE PROVIDE THE MANUFACTUREER'S | | INFORMATION ON THE X-RAY EQUIPMENT INDICATEING THAT | | SHIELDING IS NOT REQUIRED BECAUSE OF THE STRENGHT OF | | THE X-RAYS, SHIELDING REQUIREMENTS ARE NOT REQUIRED. | | PLANS INDICATE THE EITHER X-RAY MACHINES OR FUTURE | | X-RAY MACHINES, PLEASE SEE FBC 435.1 FOR SHIELDING | | REQUIREMENTS. | | | | 4) PERMIT APPLICATION INDICATES WORK TO BE COMPLETED AT | | 600 N DIXIE WHERE AS THE PLANS INDICATE A CHANGE TO 600 | | SOUTH DIXIE? PLEASE CORRECT. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-03-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-03-15 |
Time |
12:40 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2007-03-15 |
Time |
12:40 |
Sent To |
FIRE |
|
Notes |
2007-03-15 14:21:44 | BUILDING PLAN REVIEW | | PERMIT: 07020266 | | ADD: 600 N DIXIE HWY# 105 | | CONT: AMERICAN HOME CARE | | TEL: (954)646-2283 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | 1STREVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2 ) FL S S 713.13 | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | THE COURT. | | NOTE: 713.13(2) | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 3)PLANS INDICATE THE EITHER X-RAY MACHINES OR FUTURE | | X-RAY MACHINES, PLEASE SEE FBC 435.1 FOR SHIELDING | | REQUIREMENTS. | | | | 4) PLANS INDICATE AN "X" WHERE THE X-RAY EQUIPMENT WILL | | BE LOCATED, WHAT DOES THIS SYMBOL STAND FOR? IS THIS | | FRAMING MEMBERS? | | | | | | 5) PLANS INDICATE THE 2004 FBC PLEASE UPDATE TO THE | | 2006 AMENDMENTS. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
F |
Date |
2008-09-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-09-11 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-09-11 |
Time |
09:02 |
Sent To |
|
|
Notes |
2008-09-11 09:02:45 | | | | | | | | | ** DENIED REVIEW OF REVISION** | | | | | | | | 1) NOTE: PLEASE SEE FBC 13-101.1 AS THE METHOD *A* | | SUBMITTED MAY NOT BE USED. THIS IS NOT A WHOLE | | BUILDING. | | | | 2) NOTE: PLEASE SEE REVIEW NOTES FROM 6/13/08 WHICH ARE | | STILL IN NEED OF ADDRESSING. THESE WILL BE ATTACHED. | | | | | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2008-06-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-06-13 |
Time |
16:28 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-06-13 |
Time |
16:28 |
Sent To |
|
|
Notes |
2008-06-13 16:29:50 | ** DENIEDREVISION** | | | | 1) NOTE: PLEASE BE SURE ALL CIRCUITING IS SHOWN ON | | PLANS AND COORDINATE WITH THE SUBMITTED PANEL | | SCHEDULES. | | PLEASE SEE 700.12F FOR CIRCUITING OF EMERGENCY LIGHTS | | AND EXIT LIGHTS. THESE ARE REQUIRED TO BE CIRCUITED TO | | THE LOCAL LIGHTING IN ANY ONE AREA. | | PLEASE SEE MANY OF THESE SHOWN ON PLANS DO NOT CONTAIN | | ANY CIRCUITING. | | PLEASE BE SURE TO SUBMIT REVISE LIGHTING PLANS ALSO AND | | COORDINATE WITH PANEL SCHEDULES. | | PLEASE BE SURE TO REVISE ANY LIGTHING PERFORMANCE | | CALCULATIONS FOR ANY REVISED LIGTHING SINCE PERMIT | | ISSUED PLANS WERE DONE. | | | | 408.4, 310.16, 240.4, 700.12F,ETC | | 13-415.2.ABC.1.1, .1.2, 13-415.2. | | FBC 106.1.2, 106.3.5.1.2, 106.5 FOR ADDITIONAL | | INFORMATION, COORDINATION AND RECORDS RETENTION. | | | | ** IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | HESITATE IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2007-08-23 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-23 |
Time |
13:00 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-23 |
Time |
11:57 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-08-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-09 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-08 |
Time |
20:03 |
Sent To |
PC |
|
Notes |
2007-08-09 09:23:50 | | | 1) NOTE: PLANS IN FAILED STATUS UNTIL THE CERTIFICATION | | SHEETS IN THE ENERGY CALCULATIONS ARE SUBMITTED WITH | | ORIGINAL SIGNATURES. PLEASE SEE BOTH SETS SUBMITTED DO | | NOT CONTAIN ORIGINAL SIGNATURES. PLEASE SEE ONE IS A | | COLOR COPY/PRINT AND THE OTHER IS A PHOTO-COPY. BOTH | | MUST CONTAIN ORIGINAL SIGNATURES FOR CERTIFICATION OF | | DOCUMENTS AS REQUIRED UNDER FBC 13-103.1.1.1. PLEASE BE | | SURE THE ARCHITECT RE-SIGNS, DATES AND SEALS SHEETS. | | | | ** PLANS WILL BE OUT FOR PICK UP FOR NEW CALCULATIONS | | TO BE BROUGHT IN. SPOKE TO CONTRACTOR AND ARCHITECT. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS | | OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | 2007-08-08 20:03:46 | IN ELEC FOR REIVEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-07-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-07-06 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-07-05 |
Time |
17:51 |
Sent To |
I |
|
Notes |
2007-07-06 07:57:11 | 2007-07-06 07:57:11 | | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS STILL DO | | NOT CORRELATE WITH THE FIXTURE LEGEND ON PLANS. PLEASE | | SEE THE RESPONSE HAND WRITTEN ON NOTES SHEETS MENTIONS | | THE CERTAIN FIXTURES ARE EXEMPT UNDER 13-415.2.B.2, | | HOWEVER PLEASE SEE THIS SECTION OF THE CODE DOES NOT | | APPLY TO THE CALCULATIONS SUBMITTED AND THE USE AS | | SHOWN. PLEASE SEE ADDITIONAL ALLOWANCES ARE PERMITTED, | | HOWEVER THAT DOES NOT MEAN THEY ARE EXEMPT. IN EITHER | | CASE THE SECTION REFERENCED IS FOR SPACE BY SPACE | | CALCULATIONS AND PERFORMANCE MEASURES. | | PLEASE SEE 13-415.1.AB.1.,13-415.1.A, 13-415.2 | | | | PLEASE REVISE AND ADJUST. | | | | 2) NOTE: PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS DOWN | | THE LEFT HADN SIDE OF THE PLANS. THESE WERE REMOVED | | FROM PLANS BY THIS OFFICE ON THIS REVIEW AND PLACED | | INTO TWO PACKAGES FOR EACH. | | FBC106.1 | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-07-06 07:02:04 | 2007-07-06 07:02:04 | | REVIEW IN PROGRESS | 2007-07-05 17:51:50 | 2007-07-05 17:51:50 | | PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO | | INCOMING WAITING FOR THE COMM BOARD ONCE ELECTRICLA | | REVIEW IS DONE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-18 |
Time |
18:25 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-18 |
Time |
18:25 |
Sent To |
|
|
Notes |
2007-04-18 18:28:10 | | | ** UNSAT2ND REVIEW** | | | | | | 1) NOTE: PLEASE COORDINATE ADDRESS. PLEASE SEE THE | | PERMIT APPLICATION STILL CONTAINS THE ADDRESS AND | | PARCEL CONTROL NUMBER (PCN) FOR 600 N. DIXIE WHEN THE | | SCOPE OF WORK IS BEING DONE AT 600 SOUTH DIXIE. PLEASE | | BE SURE TO CHANGE APPLICATION AND OWNER INFORMATION AS | | THE OWNER FOR 600 S DIXIE IS NOT GRAND TRUST BANK. | | | | 2) NOTE: PLEASE SEE THAT ALL RAISED SEALS SHALL BE | | CLEAR AND VISIBLE WITH ALL INFORMATION ON SAID SEAL | | WHICH IS REQUIRED READABLE.THE INFORMATIONON MOST | | OF THE SEALS ON SHEETS WILL NOT PROVIDE ALL INFORMATION | | ON SEAL EVEN WHEN USING A LEAD RUB NOT APPLIED WITH | | PENCIL. | | PLEASE BE SURE ALL PLANS SHEETS AND ENERGY CALCULATIONS | | ARE SEALED WITH READABLE RAISED SEAL. | | FS 481.221, FAC61G1-16.002,.3 | | | | 3) NOTE: PLEASE SEE THE NOTE FROM PREVIOUS REVIEW NEEDS | | TO BE CLARIFIED FOR THESE LOCATIONS. A HANDWRITTEN | | RESPONSE MENTIONS THERE IS NO ANESTHETIZING AT THIS | | LOCATION AND TO SEE NOTE #8, HOWEVER NOTE #8 DOES NOT | | SEEM TO CONTAIN ANY MENTIONING OF THIS? | | PLEASE 517.60, 517.62 AND OTHER PARTS OF 517. PLEASE | | SPECIFY AREAS AND USE IN THESE AREAS. PLEASE SPECIFY | | ANY USE OF ANESTHETIZING LOCATIONS IF THIS APPLIES TO | | THIS OFFICE AND USE. | | NOTES WERE LOCATED FOR TYPE OF WIRING METHODS AND | | GROUNDING AS REQUIRED. | | | | 4) NOTE: PLEASE KNOW THAT IN NOTED RESPONSE FROM | | ARCHITECT WHICH WAS WRITTEN ON THE REVIEW NOTES FROM | | PREVIOUS REVIEW IT MENTIONS "THIS REVIEWER IS GETTING | | TOO PICKY", PLEASE KNOW THAT THIS REQUIREMENT WAS | | ADOPTED INTO THE NEW CODE AND THE TEXT IN THE PREVIOUS | | NOTE WAS EXTRACTED DIRECTLY FROM THE CODE. PLEASE | | CONTACT THE CODE PANELIST FOR ANY ROP'S (REQUEST FOR | | PROPOSALS). | | THIS IS A MINIMUM REQUIREMENT WHICH IS SET FORTH FROM | | NFPA AND NOT THIS OFFICE. | | THIS NOTE WILL REMAIN AS THERE ARE SOME ITEMS ON PLANS | | WHICH MAY NOT INDICATE CIRCUITING AND ITEMS ON PLANS | | WHICH HAVE NOT BEEN CLEARED UP AND CLARIFICATION FOR | | DESIGNER ON WHAT WILL BE REQUIRED FOR PROJECTS REVIEWED | | IN TEH CITY OF WEST PALM BEACH. | | | | (NOTE FROM PREVIOUS REVIEW) PLEASE CORRELATE PANEL | | SCHEDULE AND COMPLETE PANEL SCHEDULE(S) SO THAT ALL | | ITEMS ON PANEL SCHEDULE ARE SPECIFIC TO AREAS AND ROOMS | | IN WHICH THEY FEED. PLEASE SEE COMMENTARY BELOW | | EXTRACTED FROM THE CODE. *SECTION 408.4 WAS REVISED FOR | | THE 2005 CODE TO REQUIRE THAT THE IDENTIFICATION FOR | | EVERY CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD | | BE LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR | | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME | | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR | | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY | | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN | | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL | | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, | | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL | | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR | | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' | | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH | | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE | | SUFFICIENT DETAIL REQUIRED BY THIS SECTION. | | | | 5) NOTE: PLEASE SEE THIS NOTE REMAINS. IN FACT THE | | EXACT SAME ENERGY CALCULATIONS WERE RESUBMITTED. PLEASE | | SEE THE ADDRESS WAS CHANGED BY HAND WRITING THIS ON | | COVER SHEETS. WHEN ADDRESSING THE CODE COMPLIANCE | | NOTES, PLEASE CHANGE ADDRESS. | | THE USE AS STATED IN THE ENERGY CALCULATIONS STILL | | INDICATES "SALES" IN MORE THAN ONE LOCATION. | | PLEASE SEE THE SEAL IS STILL NOT CLEAR AND VISIBLE SO | | THAT ALL INFORMATION ON SEAL IS READABLE. SEE NOTE FOR | | SEALS ON PLANS. | | PLEASE SEE THE CONTROLS ON CALCULATIONS STILL INDICATE | | *MANUAL ON/OFF* WHEN IN FACT THE PLANS CONTAINS THE | | OCCUPANCY SENSOR TYPE DEVICES. | | THE REST OF THE COMMENT IS THE SAME FROM PREVIOUS | | REVIEW. | | FIXTURES, WATTAGE ETC DO NOT CORRELATE WITH PLANS. | | PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE | | WITH THE PLANS. PLEASE SEE THE LIGHTING, WATTAGE, | | NUMBER OF FIXTURES ETC. | | PLEASE BE SURE THE FIXTURE LEGEND STATES THE AMOUNT OF | | LIGHTS FOR EACH TYPE OF FIXTURE SPECIFIED AND | | COORDINATE THIS WITH THE ENERGY CALCULATIONS. THESE DO | | NOT CORRELATE AT ALL AT THIS TIME. | | PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS A | | NOTE STATED ON PLANS, HOWEVER DOES NOT SEEM TO | | CORRELATE WITH ACTUAL PLANS AND CALCULATIONS | | SUBMITTED. | | PLEASE ALSO SEE USE ENTERED IN AS *SALES AREA*?? PLEASE | | SEE THE TABLE IN THE FBC CHAPTER 13 FOR USES. PLEASE BE | | SURE THESES CONTAIN A RAISED SEAL, DATE AND SIGNATURE | | OF THE DESIGNER OF RECORD. PLEASE SEE THE SEAL IS NOT | | VISIBLE WITH INFORMATION ON SAID SEAL AS REQUIRED UNDER | | FS 481.221. | | PLEASE SEE THE CONTROL METHODS ON THE ENERGY | | CALCULATIONS DO NOT CORRELATE WITH PLANS. | | PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1, | | 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, 13-415.2 | | ETC. | | | | 6) NOTE:PLEASE SEE THIS NOTE REMAINS THE LEVELS ADDED | | ON PLANS FOR ADA COMPLIANCE DOES NOT MEET THE MINIMUM | | LEVELS FOR ADA. THE FBC LEVELS FOR ADA ARE MORE | | STRINGENT THAN THAT OF NFPA-72 LEVELS. | | PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE | | THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA | | REQUIRED AREAS. DEVICES ARE BEING SHOWN ON | | PLANS/LEGEND. | | | | 7) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) WHICH IS | | ATTACHED TO NOTES. THIS IS ONLY GIVEN AS A NOTICE AT | | THIS TIME. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-03-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-01 |
Time |
07:04 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-02-28 |
Time |
07:45 |
Sent To |
|
|
Notes |
2007-03-01 07:05:18 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST | | ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE | | FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER | | 8TH, 2006. | | 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS | | SUBMITTED | | 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED. | | 2002 NFPA-72 | | 2003 NFPA-101 | | | | ** PLEASE SEE OTHER CODES WHICH MAY BE REQUIRED TO BE | | STATED ON PLANS BY OTHER TRADES WHICH MAY NOT BE STATED | | IN THIS REVIEWER(S) COMMENTS. | | | | 2) NOTE:PLEASE CLARIFY WHAT IS BEING SHOWN ON RISER | | OF TWO METERS AND MAINS FOR THIS SINGLE TENANT. PLEASE | | KNOW AS THIS IS ONE OCCUPANCY AND ONE TENANT, ONE METER | | AND MAIN SHOULD BE SHOWN, HOWEVER IT APPEARS TWO ARE | | BEING SHOWN AT THIS TIME?? | | PLEASE CLARIFY FBC 106.1.2, 106.3.5.1.2 | | 104.6. | | PLEASE SEE THIS WOULD ALSO CREATE ZONING AND POSSIBLE | | BUILDING ISSUES WITH ONE OCCUPANCY STATED. ONLY ONE | | TENANT METER WILL BE PERMITTED BASED ON THE SINGLE | | OCCUPANCY AT THIS TIME. | | | | 3) NOTE: PLEASE 517.60, 517.62 AND OTHER PARTS OF 517. | | PLEASE SPECIFY AREAS AND USE IN THESE AREAS. PLEASE | | SPECIFY ANY USE OF ANESTHETIZING LOCATIONS IF THIS | | APPLIES TO THIS OFFICE AND USE. | | NOTES WERE LOCATED FOR TYPE OF WIRING METHODS AND | | GROUNDING AS REQUIRED. | | | | 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE | | PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE | | ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. | | PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. | | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE | | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS | | SECTION. | | | | 5) NOTE: PLEASE SHOW LOAD CALCULATIONS ON THE EXISTING | | SERVICE (800 AMP DISCONNECT) NEC 220 | | PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER | | 215.3, AND 230.42 PLEASE INDICATE THE SIZE OF WHAT IS | | BEING SHOWN FOR THE EXISTING PANEL AND LOAD ON PANEL | | ALONG WITH NEW LOADS. | | | | | | 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS DO NOT | | CORRELATE WITH THE PLANS. PLEASE SEE THE LIGHTING, | | WATTAGE, NUMBER OF FIXTURES ETC. | | PLEASE BE SURE THE FIXTURE LEGEND STATES THE AMOUNT OF | | LIGHTS FOR EACH TYPE OF FIXTURE SPECIFIED AND | | COORDINATE THIS WITH THE ENERGY CALCULATIONS. THESE DO | | NOT CORRELATE AT ALL AT THIS TIME. | | PLEASE SEE MAXIMUM LIGHTING POWER DENSITIES WHICH HAS A | | NOTE STATED ON PLANS, HOWEVER DOES NOT SEEM TO | | CORRELATE WITH ACTUAL PLANS AND CALCULATIONS | | SUBMITTED. | | PLEASE ALSO SEE USE ENTERED IN AS *SALES AREA*?? PLEASE | | SEE THE TABLE IN THE FBC CHAPTER 13 FOR USES. PLEASE BE | | SURE THESES CONTAIN A RAISED SEAL, DATE AND SIGNATURE | | OF THE DESIGNER OF RECORD. PLEASE SEE THE SEAL IS NOT | | VISIBLE WITH INFORMATION ON SAID SEAL AS REQUIRED UNDER | | FS 481.221. | | PLEASE SEE THE CONTROL METHODS ON THE ENERGY | | CALCULATIONS DO NOT CORRELATE WITH PLANS. | | PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1, | | 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, 13-415.2 | | ETC. | | | | 7) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) | | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR | | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON | | PLANS/LEGEND. | | | | 8) NOTE: PLEASE SEE THERE ARE SEVERAL FIXTURES ON PLANS | | WITHOUT DESIGNATIONS, PLEASE INCLUDE FOR REVIEW OF | | CHAPTER 13 REQUIREMENTS. | | PLEASE ALSO SEE 13-415.1.ABC.3 WHERE APPLICABLE. | | | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2008-09-19 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-09-19 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-09-19 |
Time |
10:05 |
Sent To |
|
|
Notes |
2008-09-19 10:06:12 | REVISION DATED 7/25/08 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-07-26 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-26 |
Time |
18:00 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-07-26 |
Time |
17:48 |
Sent To |
|
|
Notes |
2007-07-26 17:56:07 | ****PROVISO***** | | | | THECOMMENTS TAKEN FROM THE PREVIOUS FIRE PLAN REVIEWS | | HAVE BEEN ADDRESSED;HOWEVER, THE APPROPIATE PLAN | | SHEET(S) WILL BE FIRE-STAMPED WHEN ALL REVIEWS HAVE | | BEEN SATISFIED. | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-05-07 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-05-07 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-05-07 |
Time |
16:14 |
Sent To |
|
|
Notes |
2007-05-07 16:29:49 | *****DENIED***** | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 02.ON SHEET 1, THE MENTIONED CODE OF 2003 NFPA 101 IS | | CORRECT.HOWEVER, ROOM FINISH NOTE #8INCORRECTLY | | REFERENCES 2005 NFPA 101. | | | | 06.SHOW/DISPLAY THESUITE NUMBER ON THE EXTERIOR | | ELEVATION SO THAT THIS TENANT SPACE IS DISTINGUISHABLE | | FROM THE OTHER SUITES.AS PER WEST PALM BEACH CODE, | | THOSE NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO | | LESS THAN 1" IN WIDTH. | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | SHEET INDICATING HOW/WHERE ON THE PLANS EACH COMMENT | | WAS ADDRESSED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-03-19 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-03-19 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-03-19 |
Time |
16:43 |
Sent To |
|
|
Notes |
2007-03-19 16:53:08 | *****DENIED***** | | | | | | 01.THE ACTUAL ADDRESS OF WHERE THE SCOPE OF WORK WILL | | BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET.THE CORRECT ADDRESS FOR THIS | | LOCALE IS 600 SOUTH DIXIE HIGHWAY - SUITE 103. | | | | 02.ON SHEET 1, THE MENTIONED CODE OF 2003 NFPA 101 IS | | CORRECT.HOWEVER, ROOM FINISH NOTE #8INCORRECTLY | | REFERENCES 2005 NFPA 101. | | | | 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 04.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE | | OR HINDER WITH EMERGENCY ACCESS RESPONSE TO THE | | STRUCTURE OR THE VICINITY THEREOF (INCLUDING FIRE | | LANES). | | | | 05.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES | | THE TRAVEL DISTANCE TO THE EXITS. THIS SHEET MAY ALSO | | INCLUDE THE LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS, | | FIRE EXTINGUISHERS,FIRE ALARM DEVICES, AND FIRE | | SPRINKLERS APPLICABLE TO THE PROPOSED STRUCTURE. | | | | 06.SHOW/DISPLAY THESUITE NUMBER ON THE EXTERIOR | | ELEVATION SO THAT THIS TENANT SPACE IS DISTINGUISHABLE | | FROM THE OTHER SUITES.AS PER WEST PALM BEACH CODE, | | THOSE NUMBERS SHALL BE NO LESS THAN 3" IN HEIGHT AND NO | | LESS THAN 1" IN WIDTH. | | | | 07.IF SO EQUIPPED WITH A FIRE ALARM SYSTEM, WILL IT | | BE INDEPENDANT OR WILL IT BE TIED INTO THE PRADO | | CONDOMINIUM'S SYSTEM. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | SHEET INDICATING HOW/WHERE ON THE PLANS EACH COMMENT | | WAS ADDRESSED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2008-11-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-11-18 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-11-18 |
Time |
15:31 |
Sent To |
|
|
Notes |
2008-11-18 15:34:16 | TO "COMM" BD#46 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2008-08-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-08-25 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2008-08-25 |
Time |
10:06 |
Sent To |
|
|
Notes |
2008-08-25 10:07:33 | TO "COMM" BD #5 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-05-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-21 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-21 |
Time |
10:39 |
Sent To |
|
|
Notes |
2008-05-27 16:04:19 | TO "COMM" BD#24 | 2008-05-21 10:40:27 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-08-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-23 |
Time |
11:18 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-23 |
Time |
11:18 |
Sent To |
E |
|
Notes |
2007-08-23 11:19:49 | TO "DPALMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-08-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-03 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-03 |
Time |
16:11 |
Sent To |
E |
|
Notes |
2007-08-03 16:11:57 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-06-25 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-25 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-25 |
Time |
16:36 |
Sent To |
|
|
Notes |
2007-07-12 14:47:16 | TO "COMM" BD#17 | 2007-06-25 16:36:37 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-04-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-16 |
Time |
15:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-16 |
Time |
15:07 |
Sent To |
|
|
Notes |
2007-04-16 15:12:35 | TO "COMM" BD#16 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-03-19 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-03-19 |
Time |
16:43 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-02-12 |
Time |
16:35 |
Sent To |
|
|
Notes |
2007-02-26 11:30:18 | TO "COMM" BD#4 | 2007-02-12 16:36:22 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
P |
Date |
2008-12-13 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-12-13 |
Time |
09:31 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-12-13 |
Time |
09:01 |
Sent To |
|
|
Notes |
2008-12-13 09:31:28 | REVISED M1, M2, COOLING LOAD CALCS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
F |
Date |
2008-09-08 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-09-08 |
Time |
14:11 |
Rev Time |
1.30 |
Received By |
tgordon |
Date |
2008-09-08 |
Time |
14:11 |
Sent To |
|
|
Notes |
2008-09-08 14:26:09 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | REVISION TO MECHANICAL PLANS M-1 AND M-2. | | *** DENIED *** | | | | 1) COOLING LOAD CALCULATIONS SUBMITTED FOR A/C SYSTEM | | #1 IS CALLING FOR 40,502 TOTAL COOLING BTU'S, THE | | MECHANICAL PLANS ARE SHOWING SYSTEM #1 AS 57,000 TOTAL | | COOLING BTU'S. A 5 TON A/C SYSTEM IS TO LARGE PER THE | | COOLING LOAD CAL'S, A 3.5 TON WOULD MEET THE | | REQUIREMENTS (SEE ATTACHED ARI CERTIFICATE), PER 2004 | | FBC/M 13-407.1.ABC.1.1. PLEASE CORRECT. | | | | 2) PLEASE SHOW ON THE MECHANICAL PLANS THE OUTDOOR AIR | | CALCULATIONS, AS THE OUTDOOR AIR BEING PROVIDED APPEARS | | NOT TO BE ENOUGH, PER 2004 FBC/M 403.3. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
F |
Date |
2008-06-17 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-06-17 |
Time |
08:15 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2008-06-17 |
Time |
08:15 |
Sent To |
|
|
Notes |
2008-06-17 08:24:45 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | REVISION TO MECHANICAL PLANS | | *** DENIED *** | | | | 1) AS THE A/C SYSTEMS BEING INSTALLED HAVE CHANGED, THE | | ENERGY CALCULATIONS AND COOLING LOAD CALCULATIONS WILL | | NEED TO BE REVISED, PER 13-400.3.ABC.2 AND | | 13-407.1.ABC.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-07-26 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-07-26 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-07-26 |
Time |
10:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-05-03 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-05-03 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-05-01 |
Time |
09:45 |
Sent To |
|
|
Notes |
2007-05-03 14:50:00 | --------------DENIED----------------- | | | | FBC 2004 CODE FAMILY W/ 2006 REVISIONS | | FBC CH. 1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. INFORMATION WAS REQUESTED IN PREVIOUS REVIEW | | REGARDING THE ALLOWABLE LENGTH AND ELEVATION DIFFERENCE | | BETWEEN AHU AND CU. NO INFORMATION WAS PROVIDED FROM | | THE MANUFACTURER. EQUIPMENT AND APPLIANCES SHALL BE | | INSTALLED AS REQUIRED BY THE TERMS OF THEIR APPROVAL, | | IN ACCORDANCE WITH THE CONDITIONS OF THE LISTING, THE | | MANUFACTURER'S INSTALLATION INSTRUCTIONS AND THIS CODE. | | IF THE DESIGNER WANTS TO PROVIDE ADDITIONAL | | INFORMATION, SUCH AS CALCULATIONS, VERIFYING THE | | FEASIBILITY OF THE INSTALLATION CONDITIONS, PLEASE | | INCLUDE THESE CALCULATIONS ON THE PLAN. FBC,M 106.1.3. | | | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-03-13 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-03-13 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-03-13 |
Time |
09:33 |
Sent To |
|
|
Notes |
2007-03-13 15:10:56 | -----------------DENIED----------------- | | | | 1. PLEASE PROVIDE MANUFACTURER'S SUBMITTAL DATA SHOWING | | MAXIMUM ALLOWABLE ELEVATION DIFFERENCE BETWEEN AHU AND | | ROOFTOP CONDENSING UNIT. ALSO, PLEASE SHOW THE | | ELEVATION DIFFERENCE BETWEEN COMPONENTS AS IT WILL | | OCCUR IN THIS CASE. WILL COPPER LINE SIZES BE AFFECTED | | BY THIS CONDITION? FBC,M 304.1. | | | | 2. PG M1: AIR CONDITIONING CONTROL SEQUENCE | | NOTE #3 - DUCT SMOKE DETECTORS SHALL BE CONNECTED TO | | THE BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1. | | | | 3. PLEASE SHOW MEANS/LOCATION OF CONDENSATE DISPOSAL, | | DEMONSTRATING COMPLIANCE WITH FBC,M 307.2. | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
4 |
Status |
F |
Date |
2008-06-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-06-09 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-06-05 |
Time |
15:00 |
Sent To |
|
|
Notes |
2008-06-09 11:52:00 | REVISION DENIED | | REFERENCE: FBC-2004 PLUMBING | | NFPA | | | | 1. SHT 3 OF 4 INDICATES THE VACUUM EXHAUST TO BE | | TERMINATED OUT THE NORTH WALL. PER SECTION 713.6 THE | | EXHAUST FROM A VACUUM PUMP SERVING A VACUUM (FLUID | | SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO OPEN AIR | | ABOVE THE ROOF. | | | | 2. PIPING SHALL NOT BE THRU THE STAIRWELL PER NFPA-101 | | SECTION 7.1.3.2.1(6). PLEASE SHOW THE ROUTING OF THE | | EXHAUST FOR THE VACUUM AND THE INTAKE FOR THE | | COMPRESSOR. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
3 |
Status |
P |
Date |
2007-07-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-07-20 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-07-20 |
Time |
07:55 |
Sent To |
|
|
Notes |
2007-07-20 11:07:28 | PASSED PROVISO - VACUUM VENT TO COMPLY WITH 713.6 |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
2 |
Status |
F |
Date |
2007-05-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-05-30 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-05-30 |
Time |
16:54 |
Sent To |
|
|
Notes |
2007-05-30 16:58:01 | DENIED | | REFERENCE: NFPA 99C 2002 | | FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | ****FROM PREVIOUS REVIEW: | | | | 1. OK | | 2. OK | | 3. OK | | | | 4. THE EXHAUST VENT FOR THE VACUUM SHALL TERMINATE | | SEPARATELY ABOVE THE ROOF TO OPEN AIR. SECTION 713.6. | | ****RESPONSE NOTED, BUT THE REQUIREMENT IS NOT | | ADDRESSED. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE. | | | | 5. SHT 3 AIR/VACUUM INDICATES A 1/2" FILTERED WATER | | LINE TO THE VACUUM. PLEASE CLARIFY. SECTION 106.1.1. | | ****RESPONSE NOTED. BACKFLOW PROTECTION IS REQUIRED FOR | | THE WATER CONNECTION PER SECTION 608. PLEASE INDICATE | | THE METHOD OF PROTECTION. | | | | 6. OK | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
1 |
Status |
F |
Date |
2007-03-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-03-10 |
Time |
17:15 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-03-10 |
Time |
17:15 |
Sent To |
|
|
Notes |
2007-03-10 17:34:05 | DENIED | | REFERENCE: NFPA 99C 2002 | | FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. 1. AIR COMPRESSORS AND VACUUM PUMPS SHALL BE | | INSTALLED IN A DESIGNATED MECHANICAL EQUIPMENT AREA, | | VENTILATED AND WITH REQUIRED UTILITIES (E.G., | | ELECTRICITY, DRAINS, LIGHTING, ETC.). SUBMIT A DETAIL | | SHOWING THE COMPRESSOR & VACUUM AND ALL OTHER | | REQUIREMENTS AS DESCRIBED. SECTION 5.3.3..3.7.1. | | | | 2. SUBMIT A DETAIL FOR THE COMPRESSOR SHOWING | | COMPLIANCE WITH SECTION 5.3.3.5.3 (1) THRU (17). (SEE | | ATTACHED SHEET - FIGURE A.5.3.3.4). | | | | 3. SUBMIT A DETAIL FOR THE VACUUM SHOWING COMPLIANCE | | WITH SECTION 5.3.3.6 AND ALL SUBSECTIONS. (SEE ATTACHED | | SHEET - FIGURES A.5.3.3.6(A),A5.3.3.6(B), | | A5.3.3.6(C), OR A5.3.3.6(D). | | | | 4. THE EXHAUST VENT FOR THE VACUUM SHALL TERMINATE | | SEPARATELY ABOVE THE ROOF TO OPEN AIR. SECTION 713.6. | | | | 5. SHT 3 AIR/VACUUM INDICATES A 1/2" FILTERED WATER | | LINE TO THE VACUUM. PLEASE CLARIFY. SECTION 106.1.1. | | | | 6. SHT 3 SHOWS WSF (FILTER). THE FILTER SHALL COMPLY | | WITH NSF 42. SECTION 611.1. PLEASE SUBMIT MANUF. | | SPECIFICATION SHEETS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2008-08-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-08-28 |
Time |
09:11 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-08-27 |
Time |
17:54 |
Sent To |
|
|
Notes |
2008-08-28 09:11:59 | PLUMBING REVISION OK--SHT 3 OF 4 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2008-06-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-06-09 |
Time |
11:18 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-06-05 |
Time |
15:00 |
Sent To |
|
|
Notes |
2008-06-09 11:44:37 | REVISION DENIED | | REFERENCE: FBC-2004 PLUMBING | | NFPA | | | | 1. THE REFERENCE SHEET SHOWING THE ROUTING OF THE VENT | | PIPE IS NOT APPROVED. NFPA 101 SECTION 7.1.3.2.1(6). | | PENETRATIONS INTO, AND OPENINGS THROUGH AN EXIT | | ENCLOSURE ASSEMBLY. PIPING CAN NOT BE ROUTED THRU THE | | STAIRWELL. | | | | 2. A RELIEF VENT IS REQUIRED FOR THE AIR ADMITTENCE | | VALVES PER SECTION 917.3.1. | | | | 3. SUBMIT AN ELEVATION FOR THE VENT AND AIR INTAKE | | SHOWING ALL DIMENSIONS FROM ALL OPENINGS. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2007-07-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-07-20 |
Time |
07:54 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-07-19 |
Time |
18:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2007-05-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-05-30 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-05-30 |
Time |
16:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-03-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-03-10 |
Time |
15:35 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-03-10 |
Time |
15:35 |
Sent To |
|
|
Notes |
2007-03-10 16:01:14 | DENIED | | REFERENCE: FBC-2004 W/2006 REV. | | FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC2004 CHAPTER 11 | | FBC-2004 BUILDING | | | | 1. SHT 1 ROOM FINISH SCHEDULE. TOILET ROOMS 1 & 2 WALL | | FINISH INDICATES GWB PAINTED. THIS DOES NOT MEET THE | | REQUIREMENT FOR "SMOOTH, HARD, NONABSORBENT" WALLS AS | | REQUIRED IN SECTION 1210.2. PLEASE INDICATE A HARD | | SURFACE FOR THE WALLS AS REQUIRED. | | | | 2. SHT 1 INDICATES A FLOOR DRAIN IN THE LAB. THE RISER | | DIAGRAM INDICATES THIS AS A FLOOR SINK. PLEASE | | CORRELATE RISER AND FLOOR PLAN INFORMATION. SECTION | | 106.1.1. IF THE FLOOR SINK IS FOR INDIRECT WASTE, THEN | | A FLOOR SINK IS REQUIRED. IF SO PLEASE INDICATE WHAT | | WILL DRAIN INTO THE FLOOR SINK. SECTION 106.1.2. | | | | 3. SHT 2 DETAILS 4 & 5. SHOW COMPLIANCE FOR THE | | FOLLOWING: | | -WATER CLOSETS: | | A. 11-4.16.3 HEIGHT | | B. 11-4.16.5 FLUSH CONTROLS | | -FOR LAVS: | | A. 11-4.19.4 EXPOSED PIPES & SURFACES | | B. 11-4.19.5 FAUCETS | | | | 4. SHT 3 WASTE RISER DIAGRAM DOES NOT REFLECT THE FLOOR | | PLAN. RISER SHOWS 2 FSC'S IN HYG #1, AND THE FUTURE DL | | & FSC IN OFFICE #1 SHALL BE PIPED THE SAME AS IN THE | | OTHER EXAM ROOMS AS THE FLOOR PLAN IS THE SAME FOR ALL | | ROOMS. PLEASE CORRELATE RISER & FLOOR PLAN. SECTION | | 106.1.1. | | | | 5. SHT 3 WATER RISER DIAGRAM, IDENTYFY FITTINGS AT THE | | TOP OF ALL DROPS AS THEY ARE NOT IDENTIFIED ON THE | | SYMBOL LEGEND ON SHT 1. SECTION 106.1.1.--A WATER | | HAMMER ARRESTOR IS REQUIRED ON THE ICE MAKER IN THE | | LOUNGE AND THE WASHER IN THE STERILE ROOM AS WELL AS | | ANY OTHER FIXTURE WITH A QUICK CLOSING VALVE. SECTION | | 604.9. WHA'S SHALL BE INSTALLED NEAR THE FIXTURE IN AN | | "EFFECTIVE RANGE", NOT IN THE CEILING. PDI-WH 201 AND | | MANUF. INSTALLATION INSTRUCTIONS. | | | | 6. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SUPPLY TO | | THE OFFICE AND SHALL BE INSTALLED A MAXIMUM OF 4' AFF | | FOR SERVICE AND CERTIFICATION. SECTION 608.13.2. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2008-09-05 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2008-09-05 |
Time |
08:35 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2008-09-05 |
Time |
08:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2008-06-09 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2008-06-09 |
Time |
15:56 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2008-06-09 |
Time |
15:56 |
Sent To |
|
|
Notes |
2008-06-09 15:57:30 | ZONING REVIEW: FAILED | | | | ** ANY EXTERIOR PLUMBING, VENTS, OR OTHER EQUIPMENT | | SHALL BE INDICATED ON BUILDING ELEVATIONS SHOWING | | LOCATION AND SIZE FOR REVIEW | | ** PLEASE CONTACT ZONING STAFF TO REVIEW POSSIBLE | | LOCATIONS TO MITIGATE IMPACTS TO BUILDING FACADES AND | | VISIBILITY FROM STREET | | | | MATT FLIS - 822-1445 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-03-06 |
|
|
Cont ID |
|
Sent By |
mflis |
Date |
2007-03-06 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
mflis |
Date |
2007-03-06 |
Time |
09:06 |
Sent To |
|
|
Notes |
2007-03-06 09:07:54 | ZONING REVIEW: NOT REQUIRED - BUILD-OUT ONLY. | | | | NOTE: ADDRESS IS INCORRECT; SHOULD READ 600 S. DIXIE | | | | MATT FLIS 822-1445 |
|
|