Plan Review Details - Permit 07020212
Plan Review Stops For Permit 07020212
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-03-05 Cont ID  
Sent By shill Date 2007-03-05 Time 14:11 Rev Time 0.00
Received By shill Date 2007-03-05 Time 14:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-22 Cont ID  
Sent By btrobaug Date 2007-02-22 Time 07:15 Rev Time 0.50
Received By btrobaug Date 2007-02-22 Time 06:35 Sent To B
Notes
2007-02-22 07:10:27 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 PROVIDE ROUTING,JUNCION BOX (IF USED) CONDUCTOR AND
 CONDUIT TYPES FOR THE RELOCATED SIGN.
  
 600.5 BRANCH CIRCUITS.
 (A) REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL BUILDING
 AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET IN AN
 ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE. THE
 OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT RATED
 AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD.
 SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED
 ACCESSIBLE TO PEDESTRIANS.
  
 600.6 DISCONNECTS.
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUTLINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS. SEE 600.6(A)(1) FOR LOCATIION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-15 Cont ID  
Sent By adarroug Date 2007-02-15 Time 10:29 Rev Time 0.00
Received By adarroug Date 2007-02-15 Time 10:29 Sent To DEMO
Notes
2007-02-15 10:29:43TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-05 Cont ID  
Sent By shill Date 2007-03-05 Time 14:11 Rev Time 0.00
Received By shill Date 2007-02-12 Time 08:10 Sent To  
Notes
2007-02-12 08:10:46TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-14 Cont ID  
Sent By adavila Date 2007-02-14 Time 11:24 Rev Time 0.00
Received By adavila Date 2007-02-13 Time 19:30 Sent To I
Notes
2007-02-14 11:25:37PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PLEASE PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) SIGNED AND SEALED SURVEYS.THE
 SURVEY SHALL BE LESS THAN A YEAR OLD.
 A. PLEASE INDICATE LOCATION OF MONUMENT SIGN ON SURVEY,
 TO INCLUDE ALL SETBACK DIMENSIONS.
  
 3. A UNITY OF TITLE SHALL BE PROVIDED FOR THE FOLLOWING
 FOUR PARCELS: 74434333120000060, 74434333130020010,
 74434333120000010, AND 74434333070000027.
  
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.