Plan Review Details - Permit 07020177
Plan Review Stops For Permit 07020177
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-11 Cont ID  
Sent By btrobaug Date 2007-07-11 Time 14:53 Rev Time 0.00
Received By btrobaug Date 2007-07-09 Time 14:11 Sent To PC
Notes
2007-07-11 14:53:46 
  
  
 PROVISO
  
 THIS INSTALLATION MUST MEET ARTICLE'S 230.70(A)(1)
 DISCONNECT AND 110.26 CLEARANCE REQUIREMENTS, OR THE
 EQUIPMENT MUST BE RELOCATED AND RESUBMIT LOCATION FOR
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-22 Cont ID  
Sent By btrobaug Date 2007-02-22 Time 15:03 Rev Time 1.00
Received By btrobaug Date 2007-02-22 Time 11:36 Sent To I
Notes
2007-02-22 14:42:05 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 I COULD NOT DETERMINE WHICH ARTICLE THE LOAD
 CALCULATION WAS BASED ON. I CALCULATED THE LOAD , USING
 THE INFORMATION GIVEN AND ARRIVED AT 317 AMPS TOTAL,
 USING TABLE 220.84. IF THE DESIGNER DISAGREES WITH THIS
 CALCULATION, PLEASE INDICATE THE ARTICLES BEING USED TO
 ARRIVE AT 243.6 AMPS.
  
 1} THE MINIMUM SIZE FOR THE SERVICE ENTRANCE CONDUCTORS
 IS 400 MCM FOR A 400 AMP SERVICE. 310.15(B)(6), OR 350
 MCM FOR 350AMPS, DEPENDING ON THE LOAD CALCULATION.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED, THE
 GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH 250.66
 AND 250.52, PLEASE INDICATE COMPLIANCE ON THE RISER
 DIAGRAM.
  
 4} THE HOUSE PANEL WAS NOT INCLUDED IN THE
 CALCULATIONS, SEE 220.84(B).
  
 5} PROVIDE A FLOOR PLAN LOCATING THE SERVICE EQUIPMENT
 SO THAT COMPLIANCE WITH 230.70(A)(1) CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 11:30 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 11:30 Sent To E
Notes
2007-07-06 11:30:33TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-22 Cont ID  
Sent By btrobaug Date 2007-02-22 Time 15:03 Rev Time 0.00
Received By btrobaug Date 2007-02-09 Time 08:50 Sent To PC
Notes
2007-02-09 08:50:57TO "E" BOX