Plan Review Details - Permit 07020172
Plan Review Stops For Permit 07020172
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-16 Cont ID  
Sent By jgomez Date 2007-02-16 Time 10:35 Rev Time 0.50
Received By jgomez Date 2007-02-16 Time 10:35 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-07 Cont ID  
Sent By jgomez Date 2007-02-07 Time 16:33 Rev Time 0.50
Received By jgomez Date 2007-02-07 Time 16:33 Sent To  
Notes
2007-02-07 16:59:17BUILDING REVIEW CHECKLIST:
  
 ***NOTE:PROVIDE ALL THE INFORMATION REQUIRED BY CITY
 POLICY FOR ROOFING PERMITS. SEE ATTACHED COPY.
  
 1-WOOD DECK:
 A) FROM NOA SUBMITTED,CLEARLY IDENTIFY WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED.
  
 B) FROM NOA SUBMITTED, CLEARLY IDENTIFYSPECIFIC
 BASE SHEET FASTENING OPTION.
  
 B) FROM NOA SUBMITTED. PROVIDERAS 117 CALCULATIONS
 FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7. SEE LAST PAGE OF
 NOA.
  
 2- CONCRETE DECK:
 A) FROM NOA SUBMITTED, CLEARLY IDENTIFY WHICH
 APPROVED ASSEMBLY IS GOING TO BE INSTALLED.
  
 B) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS IF
 ASSEMBLY IS DESIGNED FOR DESIGN PRESSURES LESS THAN
 THOSE SPECIFIED ON TABLE 1609.6.2.1(2) 2004 FBC. SEE
 LAST PAGE OF NOA.
  
 C) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT MAY NOT BE USED IN THIS AREA IF
 ASSEMBLY IS DESIGNED FOR DESIGN PRESSURES LESS THAN
 THOSE SPECIFIED ON TABLE 1609.6.2.1(2) 2004 FBC 2004.
 NAIL ENHANCING IS NOT ALLOWED IN GENERAL LIMITATION #9.
 SEE LAST PAGE OF NOA.
  
 3- SEPARATE PERMITS REQUIRED TO REMOVE AND RE-INSTALL
 ALL ROOF EQUIPMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  