Plan Review Details - Permit 07020162
Plan Review Stops For Permit 07020162
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-21 Cont ID  
Sent By shill Date 2007-04-21 Time 14:27 Rev Time 0.00
Received By shill Date 2007-04-21 Time 14:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-02 Cont ID  
Sent By shill Date 2007-03-02 Time 16:20 Rev Time 0.00
Received By shill Date 2007-03-02 Time 16:20 Sent To  
Notes
2007-03-02 16:23:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)OPENINGS 1 AND 2, ANCHOR SPACING NOT COMPLIANT FOR
 TAPCONS.CHECK ALL OPENINGS.
  
 2.)CEILING MOUNT 5 IS CIRCLED ON SHEET 11, BUT NO
 CONCRETE TOP SUBSTRATE IS SHOWN ON THE ANCHOR SCHEDULE.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 08:33 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 08:33 Sent To B
Notes
2007-04-19 08:34:10TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-02 Cont ID  
Sent By shill Date 2007-03-02 Time 16:24 Rev Time 0.00
Received By shill Date 2007-02-08 Time 12:42 Sent To  
Notes
2007-02-08 12:42:43TO "MISC" BOX#1