Plan Review Details - Permit 07020129
Plan Review Stops For Permit 07020129
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-31 Cont ID  
Sent By jjohnsto Date 2007-10-31 Time 15:06 Rev Time 8.00
Received By jjohnsto Date 2007-10-31 Time 15:02 Sent To  
Notes
2007-10-31 15:06:23CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR,
 WEST PALM BEACH, FLORIDA33401
 TEL:561-805-6713FAX:561-805-6731
  
 JAMES JOHNSTON,
 BUILDING PLAN EXAMINER II
 E-MAIL:JJOHNSTON @WPB.ORG
  
  
 PERMIT NO 07020129
 PROJECT CHURCH OF CHRIST
 ADDRESS 909 3RD STREET
 DATE OCTOBER 30, 2007
  
  
 BUILDINGPLANREVIEW
  
 FLORIDA BUILDING CODES 2004 W REVISIONS
  
 1
 NOTICE OF COMMENCEMENT
 AITEM NO. 7BLANK,INFORMATION REQUIRED
 BITEM NO. 8BLANK,INFORMATION REQUIRED
  
 C THE NOTARY INFORMATION DESCRIBED HEREIN IS
 MISSING.
 DNAME OF PERSON, INFORMATION REQUIRED E
 TYPE OF AUTHORITY,INFORMATION REQUIRED F TYPE
 OF IDENTIFICATION,INFORMATION REQUIRED
  
 COMMENTA COPY OF THIS DOCUMENT SHALL BE RETAINED FOR
 USE AS REQUIRED.
 PLEASE SUBMIT A NEW COMPLETED AND RECORDED
 NOTICE OF COMMENCEMENT FOR COMPLIANCE REVIEW
  
 2
 ARCHITECT TITLE BLOCK
 COMMENTTHE ARCHITECT MUST PROVIDE THE DBPR WITH THE
  
 CORRECT ADDRESS THAT MATCHES THE INFORMATION IN THE
 TITLE BLOCK.
 SEE ATTACHED INFORMATION ON FILE W DBPR
  
  
 3
 TITLE BLOCK
 FLORIDA ADMINISTRATIVE CODE61G1-16.004
 A TITLE BLOCK IS REQUIRED ON ALL ARCHITECTURAL
 DRAWINGS.
 THE TITLE BLOCK MUST AT A MINIMUM CONTAIN THE
 FOLLOWING
  
 INFORMATION:
 FIRM NAME,ADDRESS,TELEPHONE NUMBER
 NAME OR IDENTIFICATION OF PROJECT
 DATE PREPARED
 A SPACE FOR THE SIGNATURE AND DATED SEAL
 A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT
  
 COMMENTPLEASE PROVIDE THIS INFORMATION ON ALL PLAN
 SHEETS
  
  
 4
 PROJECT INFORMATION
 FBC2004 BUILDING W/ 2005 AND 6 REVISIONS
 FBC2004 ACCESSIBILITYCHAPTER 11
 FBC2004 EXISTING BUILDING
 LEVEL OF ALTERATION FBC EXISTING LEVEL III
 TYPE OF CONSTRUCTION FBC503
 V-B
 SPRINKLED / UN-SPRINKLED
 UN-SPRINKLED
 BASIC WIND SPEED
 140MPH
 WIND EXPOSUREFBC1609.4B
 WIND IMPORTANCE FACTOR1604.5CATII -
 1.00
 TYPE OF OCCUPANCY
 A
 OCCUPANT LOADFBC 1004 62
  
 COMMENT-NOTE THE FOLLOWING INFORMATION ON
 THE COVER SHEET
  
  
 5
 ACCESSIBLE ROUTE. A CONTINUOUS UNOBSTRUCTED PATH
 CONNECTING ALL ACCESSIBLE ELEMENTS AND SPACES OF A
 BUILDING OR FACILITY. INTERIOR ACCESSIBLE ROUTES MAY
 INCLUDE
 CORRIDORS, FLOORS, RAMPS, ELEVATORS, LIFTS, AND CLEAR
 FLOOR
 SPACE AT FIXTURES. EXTERIOR ACCESSIBLE ROUTES MAY
 INCLUDE
 PARKING ACCESS AISLES, CURB RAMPS, CROSSWALKS AT
 VEHICULAR WAYS, WALKS, RAMPS AND LIFTS.
  
 5A
 FLORIDA BUILDING CODE BUILDING 11-4.3ACCESSIBLE
 ROUTE
 (1)AT LEAST ONE ACCESSIBLE ROUTE WITHIN THE BOUNDARY
 OF THE SITE SHALL BE PROVIDED FROM PUBLIC
 TRANSPORTATION
 STOPS, ACCESSIBLE PARKING, AND ACCESSIBLE PASSENGER
 LOADING ZONES, AND PUBLIC STREETS OR SIDEWALKS TO THE
 ACCESSIBLE BUILDING ENTRANCE THEY SERVE.
 THE ACCESSIBLE ROUTE SHALL, TO THE MAXIMUM EXTENT
 FEASIBLE,
 COINCIDE WITH THE ROUTE FOR THE GENERAL PUBLIC.
  
 5B
 11-4.30.7 SYMBOLS OF ACCESSIBILITY.
 (1) FACILITIES AND ELEMENTS REQUIRED TO BE IDENTIFIED
 AS
 ACCESSIBLE BY SECTION 11-4.1 SHALL USE THE
 INTERNATIONAL
 SYMBOL OF ACCESSIBILITY.
 THE SYMBOL SHALL BE DISPLAYED AS SHOWN IN FIGURE 43 (A)
 AND FIGURE 43 (B).
  
 COMMENT ? PROVIDE A SITE PLAN WITH THE FOLLOWING
 APARKING SPACES W LINES - MEASUREMENTS -COLORS B
 HANDICAP PARKING SPACE WITH DOUBLE LINES, COLOR OF
 STRIPING, HANDICAP SYMBOL ON PAVEMENT,
 CHANDICAP SIGN W POLE. SHOW POLE HEIGHT FROM GRADE TO
 BOTTOM OF SIGN ATTACHED,
 DATTACHED SIGN WITH HC SYMBOL ? STRIPING, COLOR AND
 DOLLAR VALUE OF FINE INSERTED
 EACCESS ISLE WITH STRIPING-WIDTH OF ISLE AND
 CONNECTION
 TO BUILDING EXTERIOR PORCH WALKWAY
  
  
 6
 FBC BUILDING 11-4.1.3 ACCESSIBLE BUILDINGS:
 NEW CONSTRUCTION
 (1)AT LEAST ONE ACCESSIBLE ROUTE COMPLYING WITH
 SECTION
 11-4.3 SHALL CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES WITH ALL ACCESSIBLE SPACES AND ELEMENTS
 WITHIN THE BUILDING OR FACILITY.
  
 COMMENT
 APROVIDE A DETAIL SHOWING THE ELEVATIONS OF THE
 APPROACH
 FROM THE ACCESSIBLE ISLE (5 FEET WIDE)IN THE
 PARKING LOT
 TO THE NEW PORCH SLAB. SHOW PAVING ELEVATION, RAMP
 IF
 REQUIRED AND SLAB ELEVATION
  
 BPROVIDE A DETAIL SHOWING THE ELEVATION OF THE NEW
 PORCH
 SLAB ANDTHE ENTRANCE OF THE BUILDING ADDITION
 SLAB
  
 CPROVIDE A DETAIL SHOWING THE ELEVATIONS OF THE NEW
 PORCH SLAB CONNECTING TO THE EXISTING PORCH SLAB.
  
  
  
  
 7
 FBC BUILDING1609.1.3COMPONENTS & CLADDING ANCHORAGE
 AGAINST OVERTURNING, UPLIFT AND SLIDING. STRUCTURAL
 MEMBERS AND SYSTEMS AND COMPONENTS
 AND CLADDING IN A BUILDING OR STRUCTURE SHALL BE
 ANCHORED
 TO RESIST WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING
  
 AND TO PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES
 TO THE FOUNDATION.
  
 COMMENTS-PROVIDE A WINDOWAND DOOR SCHEDULE WITH THE
 INFORMATION AS FOLLOWS
 A WINDOW SIZE
 BROUGH OPENING SIZE
 CWINDOW TYPE SH ?FIXED-
 DWIND LOADS CHPT 1609.DESIGN PRESSURE NEG AND POS
 FOR EACH WINDOW
 EGLAZINGIMPACT ? NON IMPACT
 FEXTERIOR DOOR TYPE AND SIZE
 GDESIGN PRESSURE FOR EACH DOOR WIND LOADS CHPT 1609.
  
 DESIGN PRESSURE NEG AND POS
  
  
  
 8
 1008.1.8.3 LOCKS AND LATCHES.
 LOCKS AND LATCHES SHALL BE PERMITTED TO PREVENT
 OPERATION
 OF DOORS WHERE ANY OF THE FOLLOWING EXISTS:
 2.IN BUILDINGS IN OCCUPANCY GROUP A HAVING AN
 OCCUPANT LOAD OF 300 OR LESS,AND IN CHURCHES, THE
 MAIN
 EXTERIOR DOOR OR DOORS ARE PERMITTED TO BE EQUIPPED
 WITH
 KEY-OPERATED LOCKING DEVICES FROM THE EGRESS SIDE
 PROVIDED:
 2.1.THE LOCKING DEVICE IS READILY DISTINGUISHABLE
 AS LOCKED,
 2.2.A READILY VISIBLE DURABLE SIGN IS POSTED ON
 THE EGRESS
 SIDE ON OR ADJACENT TO THE DOOR STATING: THIS DOOR TO
 REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.
 THE SIGN SHALL BE IN LETTERS 1 INCH (25 MM) HIGH ON A
 CONTRASTING BACKGROUND,
  
 COMMENTS-
 PROVIDE A HARDWARE SCHEDULE FOR THE EXTERIOR DOORS
 PROVIDE A HARDWARE SCHEDULE FOR THE INTERIOR DOORS
  
  
  
 9
 PRODUCT APPROVALS REQUIRED
 FBC 1609.1.4 AND WPB ADMINISTRATIVE CODE 106.3
 REGULATED BY DCA RULE 9B-72FLORIDA PRODUCT APPROVALS
  
 COMMENTS-
 ATHE NOAPGT SH WINDOW EXPIRED10/8/2006 SUBMIT A
 NEW NOA WITH A FLORIDA PRODUCT APPROVAL
  
 BTHE FLORIDA PRODUCT APPROVAL FOR THESIMPSON STRONG
 TIE
 WAS SUBMITTED WITHOUT THE NOA. THE FLORIDA APPROVAL IS
 THE
 COVER SHEET. THE NOA DESCRIBES THE PRODUCT IN DETAIL
  
  
  
 10
 FBC BUILDING 104.3 EXAMINATION OF DOCUMENTS 104.3.1
 PLAN REVIEW. THE BUILDING OFFICIAL SHALL EXAMINE OR
 CAUSE TO BE EXAMINED EACH APPLICATION FOR A PERMIT AND
 THE ACCOMPANYING DOCUMENTS, CONSISTING OF DRAWINGS
 SPECIFICATIONS, COMPUTATIONS AND ADDITIONAL DATA, AND
 SHALL
 ASCERTAIN BY SUCH EXAMINATIONS WHETHER THE
 CONSTRUCTION
  
 INDICATED AND DESCRIBED IS IN ACCORDANCE WITH THE
 REQUIREMENTS OF THE TECHNICAL CODES AND ALL OTHER
 PERTINENT
 LAWS OR ORDINANCES.
  
 COMMENT
 PROVIDE THE SLAB ELEVATION AND THE TOP OF BEAM
 ELEVATION
 ON SHEET 2
  
  
  
 11
 1807.2.1 FLOORS.
 DAMP PROOFING MATERIALS FOR FLOORS SHALL BE INSTALLED
 BETWEEN
 THE FLOOR AND THE BASE COURSE REQUIRED BY SECTION
 1807.4.1 ,
 EXCEPT WHERE A SEPARATE FLOOR IS PROVIDED ABOVE A
 CONCRETE SLAB.
 WHERE INSTALLED BENEATH THE SLAB, DAMP PROOFING SHALL
 CONSIST OF
 NOT LESS THAN 6-MIL POLYETHYLENE WITH JOINTS LAPPED NOT
 LESS THAN
 6 INCHES
  
 COMMENTPROVIDE THE MATERIAL DESCRIPTION OF THE
 VISQUEEN
  
  
  
 12
 1805.3.4 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL
 EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER AT
 POINT OF
 DISCHARGE OR THE INLET OF AN APPROVED DRAINAGE DEVICE
 A
  
 MINIMUM OF 12 INCHES (305 MM) PLUS 2 PERCENT.
  
 COMMENTPROVIDE THE FINISHED FLOOR ELEVATION FOR THIS
 SLAB
  
  
  
 13
 1609.1 WIND LOADS
 BUILDINGS, STRUCTURES AND PARTS THEREOF SHALL BE
 DESIGNED
 TO WITHSTAND THE MINIMUM WIND LOADS PRESCRIBED HEREIN.
  
 DECREASES IN WIND LOADS SHALL NOT BE MADE FOR THE
 EFFECT
 OF SHIELDING BY OTHER STRUCTURES.
  
 COMMENTEXPOSURE B
 APROVIDE THE WIND LOADS ON THE BUILDING ELEVATIONS
 1609.6BHORIZONTAL AND VERTICAL - END ZONES
 - INTERIOR ZONE
  
 BPROVIDE THE WIND LOADS ON THE ROOF STRUCTURE
 ELEVATION
 SEE TABLE1609.6A
  
 CPROVIDE THE WIND LOADSTHE ROOF OVERHANG
 ELEVATION TABLE 1609.6C
  
  
  
 14
 705.4FIRE WALLS -FIRE RESISTANCE RATING
  
 COMMENT
 SEE TABLE 705.4 GROUP ANOTE A
 WALLS SHALL BE NOT LESS THAN 2-HOUR FIRE-RESISTANCE
 RATED
 WHERE SEPARATING BUILDINGS OF TYPE II OR V
 CONSTRUCTION
  
  
  
 15
 705.5 HORIZONTAL CONTINUITY.
 FIRE WALLS SHALL BE CONTINUOUS FROM EXTERIOR WALL TO
 EXTERIOR
 WALL AND SHALL EXTEND AT LEAST 18 INCHES BEYOND THE
 EXTERIOR
 SURFACE OF EXTERIOR WALLS.
  
 EXCEPTIONS:
 1.FIRE WALLS SHALL BE PERMITTED TO TERMINATE AT
 THE INTERIOR
 SURFACE OF COMBUSTIBLE EXTERIOR SHEATHING OR SIDING
 PROVIDED
 THE EXTERIOR WALL HAS A FIRE-RESISTANCE RATING OF AT
 LEAST 1 HOUR
 FOR A HORIZONTAL DISTANCE OF AT LEAST 4 FEETON BOTH
 SIDES OF
 THE FIRE WALL.
 OPENINGS WITHIN SUCH EXTERIOR WALLS SHALL BE PROTECTED
 BY FIRE
 ASSEMBLIES HAVING A FIRE PROTECTION RATING OF NOT LESS
  
 THAN ? HOUR. \
  
 COMMENTSEE THIS CHAPTER RELATING TO THE FIRE WALL AND
 THE
 UNDERSIDE OF THE COMBUSTIBLE ROOF PANELS
  
  
  
 16
 710.6 PENETRATIONS AND JOINTS.
 THE SPACE AROUND PENETRATING ITEMS AND IN JOINTS SHALL
 BE
 FILLED WITH AN APPROVED MATERIAL TO LIMIT THE FREE
 PASSAGE
 OF SMOKE.
  
 713.2 INSTALLATION.
 FIRE-RESISTANT JOINT SYSTEMS SHALL BE SECURELY
 INSTALLED
 IN OR ON THE JOINT FOR ITS ENTIRE LENGTH SO AS NOT TO
 DISLODGE,
 LOOSEN OR OTHERWISE IMPAIR ITS ABILITY TO ACCOMMODATE
 EXPECTED BUILDING MOVEMENTS AND TO RESIST THE PASSAGE
 OF FIRE AND HOT GASES.
  
 COMMENTPROVIDE THE PRODUCT TO BE USED TO SEAL THE
 MASONRY FIRE WALL UNDER THE ROOF TO THE PLYWOOD PANEL
 SHEATHING
  
  
  
 17
 715.3 FIRE DOOR AND SHUTTER ASSEMBLIES.
 APPROVED FIRE DOOR AND FIRE SHUTTER ASSEMBLIES SHALL
 BE
 CONSTRUCTED OF ANY MATERIAL OR ASSEMBLY OF COMPONENT
 MATERIALS THAT CONFORMS TO THE TEST REQUIREMENTS OF
 SECTION 715.3.1 , 715.3.2 OR 715.3.3 AND THE FIRE
 PROTECTION RATING INDICATED IN TABLE 715.3 .
  
 COMMENT- PROVIDE THE FIRE DOOR RATING AND ASSEMBLY SEE
 TABLE715.3 FOR THE FOUR HOUR FIRE WALL
  
  
  
 18
 ROOF FRAMING PLAN
  
 COMMENT
 PLEASE PROVIDE A ROOF FRAMING PLAN THAT SHOWS THE
 CONNECTION OF THE NEW ROOF TO THE EXISTING ROOF.
 DETAIL THE FRAMING, BRACING, CRICKETS, VALLEYS,
 FRAMING MEMBER SIZES REQUIRED
  
  
  
 PLEASE NOTE
 THEBUILDING IS RATED BY CODE A TYPEV-B .
 AS THE DESIGNER YOU CAN RATE THE BUILDING
 WITH A FOUR HOUR WALL SO THE BUILDING
 STANDS ALONE, BUT IN DOING SO YOU MUST
 COMPLY WITH THE FOLLOWING COMMENTS AND
 CODE SECTIONS REFERENCED IN THIS CRITIQUE.
 ITEM NO,14,15,16,17
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-18 Cont ID  
Sent By jwitmer Date 2007-07-18 Time 21:22 Rev Time 0.77
Received By jwitmer Date 2007-07-18 Time 21:22 Sent To  
Notes
2007-07-18 21:40:02BUILDING PLAN REVIEW
 PERMIT: 07020129
 ADD: 909 3RD ST
 CONT: NEWBOLD CONSTRUCTION
 TEL: (561)644-5764
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) PLEASE PROVIDE THE UNITY OF TITLE FOR LOTS 12 &
 13.THE DOCUMENT SUBMITTED FOR REVIEW HAS NOT BEEN
 SUBMITTED TO THE CLERK OF THE COURT OF PALM BEACH
 COUNTY. ONCE RECORDED PLEASE PROVIDE DOCUMENTATION.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-13 Cont ID  
Sent By jwitmer Date 2007-03-13 Time 09:59 Rev Time 3.33
Received By jwitmer Date 2007-03-13 Time 09:59 Sent To  
Notes
2007-03-13 10:08:12BUILDING PLAN REVIEW
 PERMIT: 07020129
 ADD: 909 3RD ST
 CONT: NEWBOLD CONSTRUCTION
 TEL: (561)644-5764
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 4) PLANS ARE COLOR COPIES, PLEASE CREATE ORIGINAL
 DOCUMENTS, AND GET ORIGINAL SIGN-OFFS FROM THE VARIUOS
 GOVERNMENTAL AGENCIES.
  
 5) PLEASE PROVIDE THE UNITY OF TITLE FOR LOTS 12 &
 13.THE DOCUMENT SUBMITTED FOR REVIEW HAS NOT BEEN
 SUBMITTED TO THE CLERK OFTHE COURT OF PALM BEACH
 COUNTY.
 ONCE RECORDED PLEASE PROVIDE DOCUMENTATION.
  
 6)THE ENERGY CALCULATIONS SUBMITTED ARE ON THE
 2001FBC FORMS, THERE HAS BEEN CHANGES IN THE ENERGY
 CODE AS WELLL AS THE ENERGY FORM SINCE THE 2001 FBC,
 PLEASE CORRECT.
  
 7)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS- SINGLE HUNG SUBMITTED REVISION# 2 STATE
 WEBSITE ON CURRENT REVISION# 7.
 ALSO HIGHLIGHT WHICH WINDOW SERIES
 TO BE INSTALLED.
  
 B) EXTERIOR DOORS- THERMA-TRU DOORS FOR THE DOUBLE
 DOORS TO MEET THE WIND PRESSURE REQUIRES A HIGH RISE
 THRESHOLD, PLEASE SEE 1008.1.6, WHICH ALINE WITH
 ACCESSIBLITY REQUIREMENTS.
 1008.1.6 THRESHOLDS.
 THRESHOLDS AT DOORWAYS SHALL NOT EXCEED 0.75 INCH (19.1
 MM) IN HEIGHT FOR SLIDING DOORS SERVING DWELLING UNITS
 OR 0.5 INCH (12.7 MM) FOR OTHER DOORS. RAISED
 THRESHOLDS AND FLOOR LEVEL CHANGES GREATER THAN 0.25
 INCH (6.4 MM) AT DOORWAYS SHALL BE BEVELED WITH A SLOPE
 NOT GREATER THAN ONE UNIT VERTICAL IN TWO UNITS
 HORIZONTAL (50-PERCENT SLOPE).
  
 C) ROOFING ASSEMBLIES, STATE APPROVAL FOR OWENS CORNING
 ASPHALT SHINGLES,ARE NOT ON REVISION # 1 NO LONGER,
 ALSO THE REPORT SUBMITTED IS A MIAMI-DADE REPORT NUT A
 UL-REPORT. PLEASE PROVIDE THE APPROPRIATE REPORT ,
 STARTER INFORMATION + INFORMATION FOR 3 TAB .
  
 8)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-10-17 Cont ID  
Sent By dpalmer Date 2007-10-17 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2007-10-16 Time 15:51 Sent To I
Notes
2007-10-17 11:55:202007-10-17 11:55:20
  
 *** DENIED 3RD REVIEW *****
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEWS STILL NEED
 TO BE ADDRESSED ALONG WITH NEW COMMENTS AS PLANS/RISER
 HAS BEEN REVISED ONCE AGAIN.
  
  
 1) NOTE: AS REQUESTED ON THE TWO PREVIOUS REVIEWS.
 PLEASE STATE AND SHOW ON PLANS THE RELEVANT CODE IN
 WHICH PROJECT IS DESIGNED UNDER.
 THE YEARS FOR CODES ARE REQUIRED.
 PLEASE ALSO SEE PALM BEACH COUNTY IS BEING NOTED ON
 SHEET E-1 WHEN PROJECT IS IN THE CITY OF WEST PALM
 BEACH.
 PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED
 CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS
 SUBMITTED
 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY
 INDICATE CODES NEEDED.
  
 2) NOTE:PLEASE CORRELATE ELECTRICAL ON PLANS WITH
 THAT OF THE ARCHITECTURAL AND MECHANICAL PLANS. FOR
 EXAMPLE: PLEASE SEE THE LOCATION OF THE NEW SUB PANEL
 ON A AND M SHEETS ARE IN A COMPLETELY SEPARATE LOCATION
 AND THE SIZE OF THE PANEL IS NOT THE SAME AS THE
 ELECTRICAL PLANS.
 PLEASE LABEL ALL ELECTRICAL EQUIPMENT ON PLANS FOR
 ELECTRICAL. * PANEL *A*, ETC.
 NEC 110.26, 240.4, 215.5, 230,ETC
 FBC 106.1.2, 106.3.5.1.2
  
 3) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM AS
 SUBMITTED ALONG WITH LOAD CALCULATIONS AND PLANS DO NOT
 CORRELATE WITH NUMEROUS ITEMS. THIS REVIEWER CAN ONLY
 GIVE A FEW EXAMPLES AS THERE ARE TOO MANY ITEMS WHICH
 DO NO MATCH AND DO NOT THE MINIMUM REQUIREMENTS OF THE
 ELECTRICAL CODE.
  
 FOR EXAMPLE:
 PLEASE SEE E-1 ABOVE ELECTRICAL LEGEND WHICH INDICATES
 A 400AMP MLO PANEL, YET THERE IS NO WHERE ON ELECTRICAL
 RISER WHICH INDICATES A 400MLO PANEL.
 PLEASE SEE LOAD CALCULATIONS WHICH INDICATE PANEL *C*
 AND *LP* AS EXISTING CHURCH AND NEW FELLOWSHIP HALL,
 YET THE PANEL SCHEDULES TO THE RIGHT DO NOT INDICATE
 THE SAME LOADS OR PANEL SIZES.
 PLEASE SEE RISER WHICH SHOWS PANEL *C* AS 125AMP, YET
 PANEL SCHEDULES SHOW BOTH *C* AND *LP* AS 200AMP. HOW
 CAN *C* AND *LP* PANEL SCHEDULE BE THE SAME WHEN THEY
 CLEARLY DO NOT HAVE THE SAME CIRCUITS?
 PLEASE SEE RISER SHOWS 3PHASE EQUIPMENT, PANELS SERVICE
 ETC INCLUDING AS NOTED FOR CONDUCTOR COLOR CODING YET
 THE RISER AND SEVERAL OTHER LOCATIONS ONLY INDICATE A
 SINGLE PHASE SERVICE.
  
 **THE ABOVE ARE ONLY SOME OF THE INCONSISTENCIES ON
 PLANS. THERE ARE SEVERAL OTHER ITEMS WHICH ARE TOO MANY
 TO LIST.
 ** PLEASE SUBMIT ELECTRICAL PLANS, LOAD CALCULATIONS,
 AND RISER DIAGRAM WHICH CORRELATE, ARE CODE COMPLIANT
 AND CAN BE REVIEWED AS AN ELECTRICAL INSTALLATION. MAY
 NOT HAVE A 40 SPACE MLO AS DISTRIBUTION PANEL. NEC,
 100, 230.70,71,72,76,79, 215.5, 310.16, 240.4 ETC
 **2005 NATIONAL ELECTRICAL CODE**
 FBC 106.3.5.1.2, 106.1.2
  
 4) NOTE: PLEASE SEE 700.12F AS ALL EXIT AND EMERGENCY
 LIGHTING FIXTURES AS NOTED ON THE PREVIOUS REVIEWS ARE
 REQUIRED TO BE CIRCUITED TO THE NORMAL BRANCH CIRCUIT
 LIGHTING IN THAT AREA. PLEASE SEE THAT PLANS HAVE
 REVISED AND CORRECTED MOST OF THESE BUT NOT ALL. (END
 OF FELLOWSHIP HALL)
  
 5) NOTE:PLEASE KNOW THAT COMPLETE LOAD CALCULATIONS
 WHICH MEET THE MINIMUM REQUIRED BY CODE. THE SAME
 SECTIONS AS GIVEN IN THE PREVIOUS TWO REVIEWS REMAIN.
 THE CALCULATIONS ARE STILL SHOWING ONE CALCULATION FOR
 NEW PANELS WHICH ARE NOT THE SAME AS PANEL SCHEDULES OR
 PLANS. THIS WAS NOTED ABOVE FOR COORDINATION OF PLAN
 HOWEVER AS THIS WAS SPECIFICALLY NOTED ON PREVIOUS
 REVIEW, IT IS BEING NOTED ONCE AGAIN.
 PLEASE SUBMIT LOAD CALCULATIONS WHICH ARE CODE
 COMPLAINT, CORRELATE WITH PLANS, AND PANEL SCHEDULES.
 FOR EXAMPLE, PLEASE SEE SEVERAL BRANCH CIRCUITS WHICH
 ARE SHOWING LOADS WHICH EXCEED THE RATINGS FOR THE
 BRANCH CIRCUIT. SEE ONE SET OF PLANS ARE REDLINED FOR
 SOME OF THESE CIRCUITS SUCH AS CIRCUIT #15 ON *C*/LP*,
 WHICH SHOWS 3.6KW ON A SINGLE POLE 20AMP CIRCUIT.
 (3600VA DIVIDED BY 120V IS 30AMPS) THIS IS NOT
 PERMITTED ON THE BRANCH CIRCUIT. (TYPICAL MAXIMUM LOAD
 ON A 20AMP BRANCH CIRCUIT IS 1920VA).
 SEE CIRCUITS #6, #15, #24 ETC ON LP-A, #8, #15, #16,
 #17, #18 ETC ON *C* *LP*.
 PLEASE SEE NEC 220, 220.12, 220.14, 220.42, 220.44,
 ETC.
 215.5, 215.3, 230.42 ETC
 310.16, 240.4 ETC.
 210.3, 210.20, 210.23 ETC.
 PLEASE KNOW THERE ARE SEVERAL AND TOO MANY SPECIFIC
 CODE SECTIONS TO STATE ON REVIEW NOTES. PLEASE SEE NEC
 2005.
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE AS PANEL SCHEDULE AND LOAD
 CALCULATIONS FOR PANEL *C*/*LP* SHOWS A PANEL AS
 200AMPS AND LOADS WHICH EXCEEDS THE 125AMP RATING OF
 PANEL ON RISER (AS SHOWN) PLEASE BE SURE TO SEE 250.122
 FOR SIZING ADJUSTMENTS OF THE EQUIPMENT GROUNDING
 CONDUCTOR. PLEASE KNOW IN ANY CASE THE #8 AS SHOWN ON
 RISER FOR THE 125AMP PANEL IS TOO SMALL PER 250.122 **
 THIS WILL BE REQUIRED TO BE COORDINATED WITH THE NOTED
 ABOVE WITH RESPECT TO RISER ETC.
  
 7) NOTE: PLEASE VERIFY 250MCM FROM MAIN DISCONNECT TO
 PANEL *LP* ON RISER.. THIS IS BEING SHOWN AS A 200AMP
 PANEL. PLEASE VERIFY THAT THE LUGS ON THIS EQUIPMENT
 WILL ACCEPT THE 250MCM.
 110.3, 90.7, 110.14 FOR LISTING OF EQUIPMENT.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 8) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR TO PANEL *LP*>
 250.110, 250.24, 250.122
  
 9) NOTE: PLEASE SUBMIT THE PANEL DESIGNATIONS AND PANEL
 SCHEDULES FOR EACH OF THE PANELS WHICH ARE SHOWN ON
 RISER. AS NOTED ABOVE IN NOTES #5 AND #2, THERE IS
 COORDINATION NEEDED.
 PLEASE SEE ONLY TWO PANEL SCHEDULES WERE SUBMITTED AND
 REVIEW FOR CODE COMPLIANCE COULD NOT BE COMPLETED.
 408.4, 215.5,240.4, 310.16 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 10) NOTE: PLEASE SEE NEW NOTE ADDED TO THE LOWER LEFT
 HAND SIDE OF E-2 WHICH STATES *PREVIOUS PERMIT
 #07020129 EXPIRED*. HOW IS THIS POSSIBLE WHEN THIS
 PERMIT WHICH IS CURRENTLY IN REVIEW IS STILL THE SAME
 PERMIT WHICH HAS NOT EXPIRED?
 PLEASE ADJUST PLANS.
 ** THE PREVIOUS PERMIT APPLICATION DID EXPIRE HOWEVER
 WAS NEVER ISSUED FOR PERMIT. THAT PERMIT NUMBER IS
 05010378.
 THIS DOES NOT NEED TO BE ON PLANS AS IT WAS NEVER
 ISSUED AND WORK WAS NOT DONE UNDER THAT PERMIT.
  
 11) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 HAS
 NOT YET BEEN ACHIEVED.
 A) PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO
 NOT CORRELATE WITH PLANS. PLEASE BE SURE TO SEE
 MECHANICAL REVIEW FOR POSSIBLE METHOD OF CALCULATION
 COMMENT.
 PLEASE SEE THERE SEEMS TO BE TWO DIFFERENT TYPES OF
 LIGHTING FIXTURES ON PLANS AS E-1 SHOWS A COMPLETELY
 DIFFERENT TYPE OF LIGHT FIXTURE/SYMBOL THAN ON E-2.
 PLEASE SEE THE FIXTURE LEGEND DOES NOT CONTAIN THE
 COMPLETE WATTAGE INFORMATION FOR ALL LIGHT FIXTURES
 (EXAMPLE RECESSED FLUORESCENT LIGHT). PLEASE BE SURE
 THIS INFORMATION CORRELATES WITH THE INPUT DATA
 REPORT.
 PLEASE SEE THE EXTERIOR LIGHTS ON THE PLANS DO NOT
 CORRELATE WITH THE INPUT DATA REPORT OR THE FIXTURE
 LEGEND. ONE ITEM FOR EXAMPLE IS THAT THE WALL PACK
 FIXTURE WHICH IS ON LEGEND BUT *BLANK*?
 PLEASE SEE THE INPUT DATA REPORT SHOWS TWO TYPES OF
 FIXTURES, YET NEITHER OF THESE IS ON FIXTURE LEGEND.
 PLANS DO SHOW THREE TYPES OF LIGHTING FIXTURES
 OUTSIDE.
 PLEASE COMPLETE FIXTURE TYPE DESIGNATIONS ON PLANS AND
 FIXTURE LEGEND SO THESE CORRELATE. THEN PLEASE
 CORRELATE ALL LIGHTING INFORMATION ON PLANS WITH THAT
 OF THE INPUT DATA REPORT.
 PLEASE SEE 13-415.1.AB.1, 13-415.1.A, .B, .C, 13-415.2,
 13-415.2.ABC.1.3 ETC.
 ** PLEASE SEE ONLY ONE COPY OF THE INPUT DATA REPORT
 WAS SUBMITTED. PLEASE SUBMIT TWO COPIES AS ONE WILL BE
 STAMPED FOR FILE AND THE OTHER IS STAMPED FOR FIELD SET
 OF PLANS.
 B) PLEASE SEE THE PLANS DO NOT INDICATE ANY METHOD OF
 CONTROLS FOR EXTERIOR LIGHTING WHICH COMPLIES WITH
 13-415.1.ABC.1, 13-415.1.ABC.1.4
 PLEASE SEE NO CONTROLS ARE SHOWN FOR 13-415.1.ABC.1,
 13-415.1.ABC.1.2
  
 12) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE. PLEASE SEE THERE ARE SEVERAL CODE SECTIONS
 WHICH WERE REPEATED AND THE FEE HAS BEEN ASSESSED AS
 REQUIRED BY THE FLORIDA STATUTES.
 THIS FEE IS DUE BEFORE PLANS CAN BE RE-SUBMITTED FOR
 THE NEXT REVIEW. THIS FEE IS NOT THE RESPONSIBILITY OF
 THE CONTRACTOR OR OWNER. THIS IS SET-FORTH BY THE
 BOARDS AND THE STATE FOR THE DESIGN PROFESSIONAL. THE
 FEE IS $1860.00
 ** PLEASE KNOW ONE COPY OF ELECTRICAL PLANS AND ENERGY
 CALCULATIONS WILL BE RETAINED BY THIS OFFICE. OTHER
 SHEETS MAY BE RETAINED BY OTHER TRADES.
  
 13) NOTE: PLEASE SEE ONCE AGAIN THE ARCHITECT ON
 ELECTRICAL PLANS DID NOT DATE THE PLANS WHEN THEY WERE
 SIGNED AND SEALED. THIS WAS A NOTE GIVEN ON PREVIOUS
 REVIEWS AND IS STILL REQUIRED AS THIS IS A FLORIDA
 STATUTE.
 PLEASE SEE 481.221
  
 ** AS STATED ON PREVIOUS REVIEW:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-16 15:53:172007-10-17 15:53:17
  
 PLANS REMOVED FROM INCOMING FOR REVIEW DUE TO DATE FOR
 WHICH ELECTRICAL REVIEWER IS UP TO.
 PLANS WILL BE RETURNED TO INCOMING WAITING FOR
 COMMERCIAL BOARD ONCE REVIEW IS COMPLETED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-24 Cont ID  
Sent By dpalmer Date 2007-06-24 Time 12:18 Rev Time 0.00
Received By dpalmer Date 2007-06-24 Time 11:16 Sent To  
Notes
2007-06-24 12:18:15 
  
 *** UNSAT 2ND REVIEW***
  
 ** PLANS FAILED FOR MANY OF THE SAME ITEMS AS STATED ON
 PREVIOUS REVIEW. PLEASE SEE THERE ARE ALSO NEW COMMENTS
 BASED ON REVISIONS AND CHANGES MADE TO PLANS.
 ** PLANS ORIGINALLY SUBMITTED UNDER PERMIT NUMBER
 05010378 WHICH BECAME *EXPIRED*.
  
  
 1) NOTE:THIS REMAINS THE SAME NOTE AS THIS
 INFORMATION WAS NOT PLACED ON PLANS.
 PLEASE BE SURE ALL PLANS REFLECT THE LATEST ADOPTED
 CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS
 SUBMITTED
 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY
 INDICATE CODES NEEDED.
  
 2) NOTE:PLEASE CORRELATE ELECTRICAL ON PLANS WITH
 THAT OF THE PANEL SCHEDULE(S).
 PLEASE SEE THERE ARE COMMENTS BELOW WITH RESPECT TO
 CIRCUITING WHICH IS STILL NOT CORRECT.
 NEC 408.4
 PLEASE CORRELATE AND COORDINATE ALL.
 FBC 106.1.2, 106.3.5.1.2
 PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE PANEL
 SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE ARE
 SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED. PLEASE
 SEE COMMENTARY BELOW EXTRACTED FROM THE CODE. *SECTION
 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE
 IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 "KITCHEN WALL RECEPTACLES,'' "DINING ROOM FLOOR
 RECEPTACLE,'' OR "KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY "LIGHTS'' OR "OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 3) NOTE: PLEASE SEE THIS IS THE SAME NOTE AS PREVIOUS
 REVIEW. PLEASE SEE SEVERAL EMERGENCY LIGHTS AND EXIT
 LIGHTS ARE STILL BEING SHOWN ON DEDICATED CIRCUITS
 WHICH ARE ONLY PERMITTED UNDER CERTAIN CONDITIONS,
 BASED ON PLANS THE EXCEPTIONS AS STATED IN THE NEC DOES
 NOT APPLY AND THESE FIXTURES ARE REQUIRED TO BE
 CIRCUITED TO THE LOCAL LIGHTING CIRCUIT IN ANY ONE
 AREA. PLEASE SEE THE NOTE WITH RESPECT TO LOADS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 700.12F FOR EMERGENCY AND EXIT LIGHTS.
 THIS COMMENT WAS MADE ON ALL OTHER REVIEWS UNDER
 PREVIOUS PERMIT APPLICATION; HOWEVER NO CHANGES TO
 PLANS OR CIRCUITING HAVE BEEN MADE. PLEASE SEE OTHER
 AREA ON PLANS WHICH DO NOT SHOW CIRCUITS FOR THESE,
 NOTE TO CIRCUIT TO PANEL HOWEVER THESE SHALL BE
 CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT.
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 4) NOTE:PLEASE KNOW THAT COMPLETE LOAD CALCULATIONS
 FOR THE PROPOSED SERVICE AND PANELS AS PREVIOUSLY
 REQUESTED HAS NOT BEEN SUBMITTED.
 PLEASE SEE TWO SEPARATE LOAD CALCULATIONS SHOWN FOR
 SAME PANEL?
 FBC 106.1.2, 106.3.5.1.2
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SHOW LOAD CALCULATIONS, PLEASE SHOW PER, 220.12,
 220.14, 220.42, 220.44 ETC.
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER
 215.3, AND 230.42
 PLEASE SEE LOAD CALCULATIONS SUBMITTED DO NOT ALL
 CORRELATE WITH THE LOADS SHOWN ON PANELS. PLEASE SEE
 SUB PANEL *C*.
 PLEASE SHOW LOAD CALCULATIONS FOR SERVICE AS REQUESTED
 ON PREVIOUS REVIEWS UNDER OLD EXPIRED PERMIT. PLEASE
 SEE ITEMS ON LOAD CALCULATIONS WHICH ARE NOT ON PANEL
 SCHEDULE(S). (SIGN CIRCUIT)
  
 5) NOTE: PLEASE SEE ONCE AGAIN THE SERVICE RISER HAS
 BEEN REVISED AND IS STILL NOT CODE COMPLIANT. PLEASE
 SEE NOTES ON E-1 WHICH STATES THIS NEW SERVICE IS A MLO
 PANEL WHEREAS THE RISER INDICATES THIS AS A METER/MAIN
 COMBO? 230.70, 230.71 (MAIN REQUIRED). PLEASE SEE THE
 RISER SHOWS AND NOTES THIS SERVICE AS NEW YET THE RISER
 ALSO CONTAINS NOTES FOR EXISTING? PLEASE SEE THE
 FEEDERS FOR THE NEW 200AMP PANEL ARE NOT CODE COMPLIANT
 PER 310.16
 PLEASE SEE THE RISER WHICH SHOWS TWO MAIN DISCONNECTS:
 ONE 200AMPS AND THE OTHER 150AMPS BOTH FEEDING A SINGLE
 CONDUIT WITH 2/0 FEEDERS TO A GUTTER WHICH TAPS TO
 125AMP PANEL AND A 150AMP PANEL. THIS ENTIRE SCENARIO
 IS NOT CODE COMPLIANT FROM THE FEEDERS, THE TAPS, TO
 TERMINATION IN OPC, THE SINGLE CONDUIT WITH TWO
 BREAKERS SHOWN FEEDING ONE? ETC ETC. PLEASE SEE 215.5,
 310.16, 240.4, 408, 240.21 ETC. THERE ARE TOO MANY CODE
 SECTIONS TO BE REFERENCED.
 PLEASE SUBMIT A CODE COMPLIANT RISER.
 PLEASE SUBMIT THE PANEL SCHEDULES WHICH INDICATE THE
 OCP FEEDING TO SUB PANELS.
 PLEASE SEE THE 2005 NEC AND KNOW IF ANY OF THESE
 CONDITIONS EXIST AT THIS LOCATION AS SHOWN ON PLANS,
 THE ENTIRE ELECTRICAL SERVICE WILL BE REQUIRED TO
 BROUGHT UP TO CODE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE A COMPLETELY NEW RISER DIAGRAM HAS NOW BEEN
 SUBMITTED AND IS MISSING INFORMATION NEEDED FOR CODE
 COMPLIANCE AND FOR REVIEW.
 PLEASE SEE THE NEXT SEVERAL ITEMS ARE BEING STATED IN
 THIS ONE COMMENT.
 A) PLEASE SEE MISSING AIC RATINGS FOR ALL SERVICE
 EQUIPMENT AND MAINS.
 B) PLEASE SHOW LOCATIONS OF ALL SERVICE EQUIPMENT ON
 PLANS.
 C) PLEASE CORRELATE PLANS AND RISER AND PANELS. PLEASE
 SEE PLANS SHOWS 150A PANEL AS EXISTING, PANEL SCHEDULE
 FOR *C* SHOWS 150AMP AND 125AMP. PLEASE SEE LOAD ON
 THIS PANEL DOES NOT CORRELATE WITH LOAD CALCULATIONS.
 PLEASE SEE PANEL *B* WHICH SHOWS DIFFERENT FEEDERS,
 DIFFERENT OVER CURRENT PROTECTION ETC.
 D) PLEASE SEE SERVICE ENTRANCE CONDUCTORS ARE NOT RATED
 FOR SERVICE.
 ETC.
 215.5, 310.16, 408.4, 240.4, 110.9, 240.24, 408.7 ETC
 PLEASE SEE 2005 NEC.
  
 6) NOTE:PLEASE SEE COMPLIANCE WITH CHAPTER 13 HAS NOT
 BEEN MET.
 PLEASE SEE NO DESIGN CHANGES OR CONSIDERATION WAS GIVEN
 TO PREVIOUS NOTES WITH RESPECT TO LIGHTING CONTROLS
 REQUIRED.
 PLEASE SEE NO INFORMATION OR RESPONSE TO THESE COMMENT
 TO PROVIDE INFORMATION FOR REVIEW WAS IN PACKAGE SO THE
 COMMENTS REMAIN.
 PLEASE SEE NO TIMED SCHEDULING SYSTEM IS SHOWN IF IN
 DESIGN, OTHER MEANS OF LIGHTING CONTROLS MAY BE SUED.
 PLEASE SEE NO AUTOMATED DEVICES ARE SHOWN.
 PLEASE SEE NO OVER RIDE TIMES ARE SHOWN.
 PLEASE SEE NO DEVICE LOCATIONS WERE SHOWN.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED FOR
 METHOD OF CONTROLS IS NOT CORRECT.
 PLEASE SEE NO OWNER AGENT WAS SIGNED ON SHEETS AS
 REQUIRED.
 PLEASE SEE THE FIXTURE LEGEND IS NOT COMPLETE WITH ALL
 INFORMATION FOR FIXTURES FOR COORDINATION REVIEW WITH
 THE SUBMITTED ENERGY CALCULATIONS.
 PLEASE SEE NOTE WITH RESPECT TO THE ENGINEER AS SHOWN
 CERTIFYING THE ENERGY CALCULATIONS.
 PLEASE SEE NO SEPARATE SPACE CONTROLS ARE SHOWN. PLEASE
 SEE NOT RESPONSE LETTER WAS SUBMITTED OR INFORMATION
 FOR THIS.
 PLEASE SEE COMPLIANCE WITH THE 2004 FBC CHAPTER 13 FOR
 CONTROL OF LIGHTING PER 13-415.1ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE13-415.1.AB.1.1, 13-415.2 FOR LIGHTING
 PERFORMANCE CALCULATIONS ALONG WITH ENERGY
 CALCULATIONS. PLEASE BE SURE TO HAVE THE DESIGNER OF
 RECORD SIGN, DATE AND SEAL THESE AS REQUIRED PER
 13-103.1.1.1
  
 7) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS WHICH
 INDICATE LOADS WHICH EXCEED THE RATING OF THE BREAKERS
 AS SHOWN. 240
  
 ** PREVIOUS REVIEW NOTES*
 PLEASE CORRELATE ALL LOADS, CONDUCTOR SIZES AND OVER
 CURRENT PROTECTION DEVICES ON PANEL SCHEDULES. PLEASE
 SEE THERE ARE TOO NUMEROUS TO DETAIL EACH,; HOWEVER SEE
 LOADS OF 3.5KW ON 1-POLE 20A BREAKERS, SEE 1-POLE 45AMP
 BREAKERS, SEE #8 AWG ON 20AMP BREAKERS, SEE 30AMP
 BREAKERS ON #12 AWG, 4-POLE BREAKER,ETC ETC. 240.4,
 310.16 ETC.
 SEE 2005 NEC.
  
  
 8) NOTE: PLEASE SEE THE SIGNATURE AS SHOWN ON ENERGY
 CALCULATIONS DOES NOT APPEAR TO BE THE SAME AS THE
 SIGNATURE ON FILE FOR THIS DESIGNER OF RECORD. FS
 471.025/ FAC 61G15-23.002
 PLEASE SUBMIT A SIGNED, DATED, SEALED, AND NOTARIZED
 LETTER FOR LEGAL SIGNATURE VERIFICATION.
 PLEASE BE SURE THE NOTARY PLACES INFORMATION ON LETTER
 WHICH IS REQUIRED UNDER FS 117.05
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 PLEASE KNOW THAT DUE TO THE EXTENT OF COMMENTS AND
 NATURE OF COMMENT,FOR ELECTRICALREVIEW AND FOR THAT
 OF OTHER REQUIREMENTS UNDER FLORIDA STATUTES AND
 FLORIDA ADMINISTRATIVE CODE, ONE SET OF PLANS SUBMITTED
 ARE BEING RETAINED BY THIS OFFICE.
  
 10) NOTE: PLEASE SEE TITLE BLOCK APPEARS TO SHOW
 COMPANY/FIRM AND NOT ONLY THE ARCHITECT AS AN
 INDIVIDUAL. PLEASE PROVIDE CERTIFICATE OF AUTHORIZATION
 NUMBER AS APPLICABLE UNDER FS 481.219, FA C61G1-16.004
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-25 Cont ID  
Sent By dpalmer Date 2007-02-25 Time 13:33 Rev Time 0.00
Received By dpalmer Date 2007-02-25 Time 11:56 Sent To  
Notes
2007-02-25 13:33:51*** UNSAT ***
  
 ** PLANS ORIGINALLY SUBMITTED UNDER PERMIT NUMBER
 05010378 WHICH BECAME *EXPIRED*.
  
 **PLEASE SEE MANY OF THE NOTES ARE THE SAME AS STATED
 IN ORIGINAL REVIEWS AND NUMEROUS NEW COMMENTS DUE TO
 CHANGES MADE TO PLANS WHICH WERE NOT ON PREVIOUS
 REVIEWED PLANS AND NOTES FOR NEW CODE CHANGES.
  
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING WHICH ARE CURRENTLY ADOPTED AS OF DECEMBER
 8TH, 2006.
 2004 FBC W/ 2006 REVISIONS. THIS WILL AFFECT PLANS
 SUBMITTED
 2005 NFPA-70 (NEC). THIS WILL AFFECT PLANS SUBMITTED.
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE THERE ARE SECTIONS OF CODES REFERENCED
 FROM THE 2002 NEC.
  
 2) NOTE: PLEASE SEE THERE ARE NUMEROUS NOTES ON PLANS
 WHICH REFERENCE ITEMS TO THIS BEING A RESIDENTIAL
 DWELLING? PLEASE ADJUST ALL NOTES ACCORDINGLY. THIS
 SCOPE OF WORK IS NOT FOR A RESIDENTIAL DWELLING.
  
 3) NOTE:PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULE(S).
 PLEASE SEE THERE ARE A FEW ITEMS ON PLANS WHICH STILL
 DO NOT SHOW THE CIRCUITING.
 PLEASE SEE ALL CIRCUITS WHICH REFLECT TO A PANEL AND
 CIRCUITS WHICH ARE NOT PART OF THE SUBMITTED PANEL
 SCHEDULES SUBMITTED.
 PLEASE ALSO SEE WATER FOUNTAIN HAS BEEN ADDED TO PLANS;
 HOWEVER PLANS DO NOT INDICATE ANY ELECTRICAL
 RECEPTACLES FOR THIS UNIT.
 PLEASE CORRELATE AND COORDINATE ALL.
 FBC 106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND COMPLETE
 PANEL SCHEDULE(S) SO THAT ALL ITEMS ON PANEL SCHEDULE
 ARE SPECIFIC TO AREAS AND ROOMS IN WHICH THEY FEED.
 PLEASE SEE COMMENTARY BELOW EXTRACTED FROM THE CODE.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 "KITCHEN WALL RECEPTACLES,'' "DINING ROOM FLOOR
 RECEPTACLE,'' OR "KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY "LIGHTS'' OR "OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 5) PLEASE SEE 700.12E FOR EMERGENCY AND EXIT LIGHTS.
 THIS COMMENT WAS MADE ON ALL OTHER REVIEWS UNDER
 PREVIOUS PERMIT APPLICATION; HOWEVER NO CHANGES TO
 PLANS OR CIRCUITING HAVE BEEN MADE. PLEASE SEE OTHER
 AREA ON PLANS WHICH DO NOT SHOW CIRCUITS FOR THESE,
 NOTE TO CIRCUIT TO PANEL HOWEVER THESE SHALL BE
 CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT.
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 6) NOTE: PLEASE SHOW LOAD CALCULATIONS, PLEASE SHOW
 PER, 220.12, 220.14, 220.42, 220.44 ETC.
 PLEASE ALSO SHOW ALL CONTINUOUS LOADS AT 125% PER
 215.3, AND 230.42
 PLEASE SEE LOAD CALCULATIONS SUBMITTED DO NOT ALL
 CORRELATE WITH THE LOADS SHOWN ON PANELS. PLEASE SEE
 SUB PANEL *C*.
 PLEASE SHOW LOAD CALCULATIONS FOR SERVICE AS REQUESTED
 ON PREVIOUS REVIEWS UNDER OLD EXPIRED PERMIT. PLEASE
 SEE ITEMS ON LOAD CALCULATIONS WHICH ARE NOT ON PANEL
 SCHEDULE(S). (SIGN CIRCUIT)
  
 7) NOTE: PLEASE SEE A COMPLETELY NEW RISER DIAGRAM HAS
 NOW BEEN SUBMITTED AND IS MISSING INFORMATION NEEDED
 FOR CODE COMPLIANCE AND FOR REVIEW.
 PLEASE SEE THE NEXT SEVERAL ITEMS ARE BEING STATED IN
 THIS ONE COMMENT.
 A) PLEASE SEE MISSING AIC RATINGS FOR ALL SERVICE
 EQUIPMENT AND MAINS.
 B) PLEASE SHOW LOCATIONS OF ALL SERVICE EQUIPMENT ON
 PLANS.
 C) PLEASE CORRELATE PLANS AND RISER AND PANELS. PLEASE
 SEE PLANS SHOWS 150A PANEL AS EXISTING, PANEL SCHEDULE
 FOR *C* SHOWS 150AMP AND 125AMP. PLEASE SEE LOAD ON
 THIS PANEL DOES NOT CORRELATE WITH LOAD CALCULATIONS.
 PLEASE SEE PANEL *B* WHICH SHOWS DIFFERENT FEEDERS,
 DIFFERENT OVER CURRENT PROTECTION ETC.
 D) PLEASE SEE SERVICE ENTRANCE CONDUCTORS ARE NOT RATED
 FOR SERVICE.
 ETC.
 215.5, 310.16, 408.4, 240.4, 110.9, 240.24, 408.7 ETC
 PLEASE SEE 2005 NEC.
  
 8) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1,
 .1.2 AND .1.3.
 PLEASE SUBMIT ENERGY CALCULATIONS PER THE 2004 FBC W/
 2006 REVISION. PLEASE SEE ENERGY CALCULATIONS SUBMITTED
 ARE FROM THE 2001 FBC.
 PLEASE SEE 13-415.2 FOR LIGHTING PERFORMANCE
 CALCULATIONS ALONG WITH ENERGY CALCULATIONS. PLEASE BE
 SURE TO HAVE THE DESIGNER OF RECORD SIGN, DATE AND SEAL
 THESE AS REQUIRED PER 13-103.1.1.1
  
 9) NOTE: PLEASE SEE FLORIDA STATUES 481.221 WHICH
 REQUIRES TO THE ARCHITECT TO ALSO DATE PLANS WHEN
 SIGNING AND SEALING SAID PLANS.
  
 10) NOTE: PLEASE SEE PLANS SUBMITTED ARE IN FACT
 COLORED PHOTO-COPIES OF PLANS STAMPED PREVIOUSLY BY THE
 CITY ZONING REVIEWER AND PALM BEACH COUNTY FOR IMPACT
 FEES. PLEASE KNOW THAT THESE SHALL BE ORIGINAL AND MAY
 NOT MAKE CHANGES TO PLANS AND COLOR PHOTO-COPY PLANS.
 PLANS WILL BE REQUIRED TO GO BACK TO HISTORIC, ZONING,
 AND PALM BEACH COUNTY AS PERMIT APPLICATION IS NOW
 UNDER NEW PALM BEACH COUNTY IMPACT FEE SCHEDULE AS OF
 JAN 1ST, 2006.
  
 11) NOTE: PLEASE SEE PLANS WHICH STILL STATE *CORAL KEY
 DESIGN*. PLEASE KNOW AS PER FS481.229, A DESIGNER,
 DRAFTING, CADD DESIGN COMPANY MAY NOT DESIGN PLANS
 FORCOMMERICAL/ PUBLIC USE OF THIS NATURE. THIS HAS BEEN
 CONFIRMED WITH THE STATE OF FLORIDA LEGAL COUNSEL TO
 THE BOARD OF ARCHITECTS AND THIS COMMENT WAS MADE ON
 PREVIOUS REVIEWS UNDER THE EXOIRED PERMIT.
 FURTHER CONTACT MAY BE DONE WITH STATE PROSECUTOR
 MR.DAVID MINACCI, OR STATE INVESTIGATOR MR. LES SMITH.
  
 12) NOTE: PLEASE CORRELATE ALL LOADS, CONDUCTOR SIZES
 AND OVER CURRENT PROTECTION DEVICES ON PANEL
 SCHEDULES.
 PLEASE SEE THERE ARE TOO NUMEROUS TO DETAIL EACH,;
 HOWEVER SEE LOADS OF 3.5KW ON 1-POLE 20A BREAKERS, SEE
 1-POLE 45AMP BREAKERS, SEE #8 AWG ON 20AMP BREAKERS,
 SEE 30AMP BREAKERS ON #12 AWG, 4-POLE BREAKER,ETC
 ETC.
 240.4, 310.16 ETC.
 SEE 2005 NEC.
  
 13) NOTE: PLEASE SEE MISSING A/C UNITS AND THERE
 REQUIRED DISCONNECTING MEANS PER 440.11. PLEASE SEE
 MISSING CU DISCONNECT, PLEASE SEE MISSING AHU
 DISCONNECT ETC. PLEASE SEE SOME SHOWN WITH A RECEPTACLE
 FOR UNIT TO PLUG-IN WHICH IS PROHIBITED.
 422.30, 422.31, 440.11 ETC.
  
 14) NOTE: PLEASE SEE AHU'S WITH OVER CURRENT PROTECTION
 WHICH IS TOO HIGH FOR THE 5KW LOAD SHOWN. AHU'S #1 AND
 #2.
 240.4, 310.16, AND FBC 106.1.2, 106.3.5.1.2 FOR
 COORDINATION.
  
  
 15) NOTE: PLEASE KNOW THAT DUE TO THE EXTENT OF
 COMMENTS AND NATURE OF COMMENT,FOR ELECTRICALREVIEW
 AND FOR THAT OF OTHER REQUIREMENTS UNDER FLORIDA
 STATUTES AND FLORIDA ADMINISTRATIVE CODE, ONE SET OF
 PLANS SUBMITTED ARE BEING RETAINED BY THIS OFFICE.
  
 16) NOTE: PLEASE SEE THAT THE NEWLARGER ADA BATHROOM
 SHALL CONTAIN A BATTERY BACK UP LIGHTING FIXTURE FO
 SOME TYPE. LS 101 7.8, 7.9. PLEASE CIRCUIT PER 700.12
 FO TEH NEC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-10-25 Cont ID  
Sent By mawillia Date 2007-10-25 Time 12:41 Rev Time 0.00
Received By mawillia Date 2007-10-25 Time 12:16 Sent To  
Notes
2007-10-25 12:39:59*****UNSAT*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER REVIEWERS AND THE FOLLOWING FIRE REVIEW
 COMMENTS HAVE BEEN SATISFIED:
  
 A.SHOW THE LOCATION OF THE 2A10BC FIRE
 EXTINGUISHER(S).OLD COMMENT
  
 B.ON SHEET 2, ONLY ONE EMERGENCY LIGHT IS SHOWN IN
 THE PROPOSED FELLOWSHIP HALL WHEREAS, TWO EMERGENCY
 LIGHTS ARE SHOWN ON THE M-1 SHEET. PLEASE RECTIFY. NEW
 COMMENT
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-23 Cont ID  
Sent By mawillia Date 2007-07-23 Time 12:48 Rev Time 0.00
Received By mawillia Date 2007-07-23 Time 12:32 Sent To  
Notes
2007-07-23 12:35:06*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS PLAN REVIEW
 STILL NEED TO BE ADDRESSED:
  
  
 4.INDICATE THE OCCUPANT LOAD FOR THE PROPOSED
 STRUCTURE BASED UPON THE OCCUPANT LOAD FACTORS THAT ARE
 CHARACTERISTIC OF THE USE OF THE SPACE OR DETERMINED AS
 THE MAXIMUM PROBABLE POPULATION OF THE SPACE UNDER
 CONSIDERATION, WHICHEVER IS GREATER.
  
 5.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE SHALL BE
 PROVIDED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 6.PLEASE PROVIDE A LAYOUT SHOWING THE ARRANGEMENT OF
 FURNISHINGS, TABLES, SEATS, AND(OR) EQUIPMENT.
  
 7.SHOW THE LOCATION OF THE 2A10BC FIRE
 EXTINGUISHER(S).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-21 Cont ID  
Sent By mawillia Date 2007-03-21 Time 14:20 Rev Time 0.00
Received By mawillia Date 2007-03-21 Time 11:55 Sent To FIRE
Notes
2007-03-21 14:20:14*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 SAID PROPERTY OR VICINITY THEREOF.
  
 4.INDICATE THE OCCUPANT LOAD FOR THE PROPOSED
 STRUCTURE BASED UPON THE OCCUPANT LOAD FACTORS THAT ARE
 CHARACTERISTIC OF THE USE OF THE SPACE OR DETERMINED AS
 THE MAXIMUM PROBABLE POPULATION OF THE SPACE UNDER
 CONSIDERATION, WHICHEVER IS GREATER.
  
 5.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE SHALL BE
 PROVIDED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 6.PLEASE PROVIDE A LAYOUT SHOWING THE ARRANGEMENT OF
 FURNISHINGS, TABLES, SEATS, AND(OR) EQUIPMENT.
  
 7.SHOW THE LOCATION OF THE 2A10BC FIRE
 EXTINGUISHER(S).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-27 Cont ID  
Sent By adarroug Date 2007-09-27 Time 10:18 Rev Time 0.00
Received By adarroug Date 2007-09-27 Time 10:18 Sent To  
Notes
2007-10-17 12:02:25TO "COMM" BD#10
2007-09-27 10:19:04WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 11:11 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 11:11 Sent To  
Notes
2007-06-21 14:56:30TO "COMM" BD#64
2007-06-07 11:12:17WATIING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-21 Cont ID  
Sent By mawillia Date 2007-03-21 Time 11:59 Rev Time 0.00
Received By mawillia Date 2007-02-06 Time 16:35 Sent To  
Notes
2007-02-13 14:50:23TO "COMM" BD#16
2007-02-06 16:35:25WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-11-11 Cont ID  
Sent By rregueir Date 2007-11-11 Time 15:02 Rev Time 0.00
Received By rregueir Date 2007-11-11 Time 14:08 Sent To  
Notes
2007-11-11 15:02:28REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. FLOOR PLAN CALLS FOR A TOTAL OF 930 CFM. A FOUR TON
 AHU WILL PRODUCE 1600 CFM. WHERE WILL THE OTHER 670 CFM
 GO? AN AIR DISTRIBUTION SYSTEM SHALL BE DESIGNED AND
 INSTALLED TO SUPPLY THE REQUIRED DISTRIBUTION OF AIR IN
 ACCORDANCE WITH FBC,M 603.1.
  
 2. THIS COMMENT WAS NOT ADDRESSED. NO OUTSIDE AIR
 CALCULATIONS PROVIDED. NO OUTSIDE AIR VENTILATION SHOWN
 ON PLANS. SHOW COMPLIANCE WITH FBC,M 403.3.
  
 3. THIS COMMENT WAS PARTIALLY ADDRESSED. CFM OF BATH
 EXHAUST FANS STILL NOT SHOWN ON PLANS. SHOW COMPLIANCE
 WITH FBC,M 403.3.
  
 4. THIS COMMENT WAS NOT ADDRESSED. SHOW COMPLIANCE WITH
 FBC,M 602.2.1
  
 5. THIS COMMENT WAS NOT ADEQUATELY ADDRESSED. LOCATION
 OF CONDENSATE DISPOSAL NOT SHOWN. A SHUTOFF SWITCH ON A
 CONDENSATE PUMP IS NOT A CODE COMPLIANT MEANS OF
 AUXILIARY DRAIN PROTECTION. COMPLY WITH ONE OF THE
 ALLOWED METHODS AS LISTED IN FBC,M SECTION 307.2.3.
  
 6. OK
  
 7. NOW ENERGY CALCULATIONS SHOW 4.8 TONS OF AIR AND
 MANUAL N SHOWS 5 TONS OF AIR, BUT EQUIPMENT LISTED IS
 ONLY 4 TONS. PLEASE COORDINATE ALL DOCUMENTATION AND
 EQUIPMENT LISTING.
  
 8. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-29 Cont ID  
Sent By rregueir Date 2007-06-29 Time 15:08 Rev Time 0.00
Received By rregueir Date 2007-06-28 Time 19:57 Sent To  
Notes
2007-06-29 15:08:34-----------------DENIED-----------------
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE PROVIDE CFMS FOR ALL SUPPLY DROPS, REGISTERS
 AND GRILLS. FBC 106.1.2
  
 2. PLEASE PROVIDE OUTDOOR AIR CALCULATIONS SHOWING SIZE
 AND LOCATION OF OUTDOOR AIR SOURCE, OCCUPANCY
 CLASIFICATION, OCCUPANT LOAD AND CFM OF OUTDOOR AIR
 REQUIRED PER FBC,M 403.3 AND FBC 106.3.5.1.4
  
 3. PLEASE SHOW CFM, DUCT SIZE AND DISCHARGE LOCATION
 FOR TOILET ROOM EXHAUST FANS PER FBC,M 401.5, TABLE
 403.3 AND FBC 106.3.5.1.4
  
 4. A/C CLOSET LOOKS TO BE USED AS A PLENUM. DRAIN LINE
 MATERIAL IS SHOWN ON PLAN TO BE 3/4" PVC WHICH MAY NOT
 BE USED IN A PLENUM PER FBC,M 602.2.1.
  
 5. PLEASE SHOW MEANS AND LOCATION OF CONDENSATE
 DISPOSAL PER FBC,M 307.2.1 AND MEANS OF SECONDARY OR
 AUXILIARY DRAIN PROTECTION PER FBC,M 307.2.3. ALSO,
 PLEASE SHOW ROUTING OF REFRIGERANT LINES. ARE THEY
 OVERHEAD OR UNDERGROUND? FBC,M 1107.2.1
  
 6. PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON PLANS
 INCLUDING SIZE, SEER, MODEL NUMBERS, HEAT STRIP AND
 ELQUIPMENT ELECTRICAL RATINGS. FBC 106.3.5.1.3
  
 7. ENERGY CALCULATIONS STATE MAX TONNAGE AT 4, BUT
 PLANS CALL FOR 5 TONS OF COOLING. PLEASE SHOW
 CORRELATION BETWEEN PLANS AND ENERGY CALCULATIONS.
 NOTE: MANUAL N, COOLING LOADS AND ENERGY CALCULATIONS
 MAY NEED TO BE ADJUSTED ONCE ABOVE ADJUSTMENTS ARE
 MADE.
  
 8. WHAT IS THE PURPOSE OF TWO RETURN GRILLS CONNECTED
 BY A 14" DUCT IN THE MIDDLE OF A NON-SEPARATED SPACE?
 WHAT IS THE SIZE OF THE GRILLS? WILL THERE BE SOME SORT
 OF PARTITION DIVIDING THE SPACE? THERE IS NONE SHOWN ON
 A/C OR ARCHITECTURAL PLANS. IF THERE IS TO BE A
 PARTITION, THE RETURN DUCT IS TOO SMALL TO MEET THE
 BALANCED RETURN EXCEPTIONS OF FBC,M 601.4. THE RETURN
 DUCT WOULD NEED TO BE AT LEAST 16" TO CLAIM THE
 EXCEPTION. IF THERE IS TO BE A FOLDING OR ACCORDIAN
 STYLE PARTITION, PLEASE CHECK FOR STRUCTURAL
 REQUIREMEMNTS, AS NONE ARE SHOWN ON PLANS AT THIS
 TIME.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By rregueir Date 2007-03-14 Time 09:07 Rev Time 0.00
Received By rregueir Date 2007-03-14 Time 09:00 Sent To  
Notes
2007-03-14 09:12:57---------------DENIED------------------
  
 NO INFORMATION WAS SUBMITTED FOR MECHANICAL SYSTEMS.
 PLEASE SUBMIT PLANS SHOWING ALL AIR CONDITIONING AND
 VENTILLATION WORK, INCLUDING ANY NECESSARY DETAIL
 DRAWINGS, EQUIPMENT SCHEDULE AND UPDATED ENERGY
 CALCULATIONS.
  
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-12-01 Cont ID  
Sent By kstevens Date 2007-12-01 Time 11:32 Rev Time 0.00
Received By kstevens Date 2007-12-01 Time 11:03 Sent To  
Notes
2007-12-01 11:31:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW****
  
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
  
 7. SHT 2 SHOW THE CLEAR FLOOR SPACE FOR ALL ACCESSIBLE
 FIXTURES ON THE FLOOR PLAN. THE DRINKING FOUNTAIN IS
 REQUIRED TO BE 15" OFF THE WALL AND CENTERED ON THE 30"
 WIDTH OF THE CLEAR FLOOR SPACE. AS SHOW THE SERVICE
 SINK IS ENCROACHING INTO THE CLEAR FLOOR SPACE OF THE
 DRINKING FOUNTAIN.
 ****NO RESPONSE/NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN ON THE FLOOR PLAN FOR THE FIXTURES.
  
 8. THE ACCESSIBLE STALL SHALL COMPLY WITH FIGURE
 11-30E. A LAV IS REQUIRED IN THE STALL AND 5' OF CLEAR
 FLOOR SPACE IS REQUIRED FROM THE WALL ADJACENT TO THE
 WATER CLOSET AND UP TO THE SIDE OF THE LAV. SECTION
 11-4.17.3 EXCEPTIONS (1)(2).
 ****NO RESPONSE/NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE LAV SHALL BE MINIMUM 15"
 OFF THE WALL TO THE CENTER OF THE FIXTURE TO BE
 CENTERED ON THE 30" WIDTH OF THE CLEAR FLOOR SPACE.
 (RECOMMEND CHANGE THE LAYOUT OF THE ACCESSIBLE STALL IN
 THE WOMEN'S TOILET ROOM. THE LAV CAN BE BEHIND THE W/C
 OF THE MEN'S TOILET ROOM AND COMPLY).
  
 9. OK
  
 ***********NEW COMMENTS***********
  
 1B. SUBMIT A DETAIL FOR THE W/C'S SHOW COMPLIANCE WITH
 THE FOLLOWING:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
 ******NO RESPONSE, NOT ADDRESSED
  
 2B. SUBMIT A DETAIL FOR THE STALLS SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.17.3 SIZE & ARRANGEMENT (EXCEPTION NEW
 CONSTRUCTION) (FIG 30E)
 ******RESPONSE NOTED, BUT THE LAV IS NOT SHOWN AS 15"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE AS
 REQUIRED TO BE CENTERED ON THE FIXTURE.
  
 3B. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.5(1) CLEARANCES
 D. 11-4.15.5(2) CLEAR FLOOR SPACE
 E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 ******NO RESPONSE, NOT ADDRESSED.
  
 4B. SUBMIT A DETAIL FOR THE LAVS SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
 ******NO RESPONSE, NOT ADDRESSED.
  
 5B. OK
  
 6B. SUBMIT A DETAIL FOR THE SINK SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. -CABINET DOORS
 ARE NOT ALLOWED.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
 ******RESPONSE NOTED, NOT ADDRESSED.
  
 7B. OK
  
 *****NEW COMMENTS (3RD REVIEW)*****
  
 1C. THE SANITARY AND WATER RISER DIAGRAMS DO NOT
 REFLECT THE FLOOR PLAN. (SEE EXAMPLE OF A SANT RISER
 DIAGRAM THAT REFLECT THE FLOOR PLAN). PLEASE SUBMIT
 SANT AND WATER RISERS THAT REFLECT THE FLOOR PLAN AFTER
 THE LAV CHANGE IN THE ACCESSIBLE STALL IN THE WOMENS
 TOILET ROOM. SECTION 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE/NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-14 Cont ID  
Sent By kstevens Date 2007-07-14 Time 07:06 Rev Time 0.00
Received By kstevens Date 2007-07-14 Time 07:06 Sent To  
Notes
2007-07-14 07:47:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW****
  
 1. OK
  
 2. SHOW THE SQUARE FOOTAGE OF THE BUILDING ON THE
 PLANS. SECTION 106.1.2.
 ****NO RESPONSE/NOT ADDRESSED
  
 3. OK
 4. OK
  
 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES. AS SHOWN
 THERE APPROXIMATELY 1,158SSF NET DIVIDED BY 5 NET AS
 INDICATED IN TABLE 1004.1.2 THERE ARE 232 OCCUPANTS.
 PER TABLE 403.1 232 DIVIDED BY 2 EQUALS 116 MEN - 116
 WOMEN. DIVIDED BY 40 EQUALS 2.9 OR 3 WATER CLOSETS EACH
 REQUIRED FOR MEN AND WOMEN, WITH 2 LAVS EACH FOR MEN
 AND WOMEN.
 ****NO RESPONSE/NOT ADDRESSED
  
 6. OK
  
 7. SHT 2 SHOW THE CLEAR FLOOR SPACE FOR ALL ACCESSIBLE
 FIXTURES ON THE FLOOR PLAN. THE DRINKING FOUNTAIN IS
 REQUIRED TO BE 15" OFF THE WALL AND CENTERED ON THE 30"
 WIDTH OF THE CLEAR FLOOR SPACE. AS SHOW THE SERVICE
 SINK IS ENCROACHING INTO THE CLEAR FLOOR SPACE OF THE
 DRINKING FOUNTAIN.
 ****NO RESPONSE/NOT ADDRESSED
  
 8. THE ACCESSIBLE STALL SHALL COMPLY WITH FIGURE
 11-30E. A LAV IS REQUIRED IN THE STALL AND 5' OF CLEAR
 FLOOR SPACE IS REQUIRED FROM THE WALL ADJACENT TO THE
 WATER CLOSET AND UP TO THE SIDE OF THE LAV. SECTION
 11-4.17.3 EXCEPTIONS (1)(2).
 ****NO RESPONSE/NOT ADDRESSED
  
 9. OK
  
 ***********NEW COMMENTS***********
  
 1B. SUBMIT A DETAIL FOR THE W/C'S SHOW COMPLIANCE WITH
 THE FOLLOWING:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
  
 2B. SUBMIT A DETAIL FOR THE STALLS SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.17.3 SIZE & ARRANGEMENT (EXCEPTION NEW
 CONSTRUCTION) (FIG 30E)
  
 3B. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.5(1) CLEARANCES
 D. 11-4.15.5(2) CLEAR FLOOR SPACE
 E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 4B. SUBMIT A DETAIL FOR THE LAVS SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
  
 5B. PER SECTION 11-4.22.3 SHOW A 5' TURNING AREA IN THE
 TOILET ROOMS.
  
 6B. SUBMIT A DETAIL FOR THE SINK SHOWING COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. -CABINET DOORS
 ARE NOT ALLOWED.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
  
 7B. SUBMIT A PLUMBING FLOOR PLAN INDICATING THE
 CONNECTIONS FOR THE SANITARY BUILDING DRAIN AND THE
 WATER SERVICE FOR THE ADDITION. SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE/NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-10 Cont ID  
Sent By kstevens Date 2007-03-10 Time 05:50 Rev Time 0.00
Received By kstevens Date 2007-03-09 Time 18:59 Sent To  
Notes
2007-03-10 07:13:02DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. INDICATE THE CODE IN EFFECT FOR THE DESIGN OF THE
 BUILDING ON THE PLANS. (FBC-2004 W/06 AMENDMENTS).
 SECTION 106.1.2.
  
 2. SHOW THE SQUARE FOOTAGE OF THE BUILDING ON THE
 PLANS. SECTION 106.1.2.
  
 3. SHT 1 THE SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN. THE FIXTURE LAYOUT OF THE RISER DOES
 NOT REFLECT THE FIXTURE LAYOUT OF THE FLOOR PLAN AND
 THE SERVICE SINK IS NOT INDICATED ON THE RISER
 ISOMETRIC DIAGRAM. PLEASE CORRELATE THE RISER AND THE
 FLOOR PLAN. SECTION 106.1.1. (SEE EXAMPLE OF A RISER
 DIAGRAM THAT REFLECTS THE EXISTING FLOOR PLAN AS
 SHOWN).
  
 4. SHT 1 THE WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. PLEASE CORRELATE THE RISER AND THE FLOOR
 PLAN. SECTION 106.1.1.
  
 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES. AS SHOWN
 THERE APPROXIMATELY 1,158SSF NET DIVIDED BY 5 NET AS
 INDICATED IN TABLE 1004.1.2 THERE ARE 232 OCCUPANTS.
 PER TABLE 403.1 232 DIVIDED BY 2 EQUALS 116 MEN - 116
 WOMEN. DIVIDED BY 40 EQUALS 2.9 OR 3 WATER CLOSETS EACH
 REQUIRED FOR MEN AND WOMEN, WITH 2 LAVS EACH FOR MEN
 AND WOMEN.
  
 6. ALL SHEETS, THE ADDRESS OF THE ARCHITECT IS REQUIRED
 IN THE TITLE BLOCK. FAC 61G1-16.004(1) & FS 481.2055.
 (SEE ATTACHED SHEET).
  
 7. SHT 2 SHOW THE CLEAR FLOOR SPACE FOR ALL ACCESSIBLE
 FIXTURES ON THE FLOOR PLAN. THE DRINKING FOUNTAIN IS
 REQUIRED TO BE 15" OFF THE WALL AND CENTERED ON THE 30"
 WIDTH OF THE CLEAR FLOOR SPACE. AS SHOW THE SERVICE
 SINK IS ENCROACHING INTO THE CLEAR FLOOR SPACE OF THE
 DRINKING FOUNTAIN.
  
 8. THE ACCESSIBLE STALL SHALL COMPLY WITH FIGURE
 11-30E. A LAV IS REQUIRED IN THE STALL AND 5' OF CLEAR
 FLOOR SPACE IS REQUIRED FROM THE WALL ADJACENT TO THE
 WATER CLOSET AND UP TO THE SIDE OF THE LAV. SECTION
 11-4.17.3 EXCEPTIONS (1)(2).
  
 9. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FOR THE
 LAVS:
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2007-10-25 Cont ID  
Sent By mflis Date 2007-10-25 Time 11:34 Rev Time 0.00
Received By mflis Date 2007-10-25 Time 11:35 Sent To  
Notes
2007-10-25 11:37:35ZONING REVIEW: FAILED
  
 ** PREVIOUS APPROVAL INCLUDED PROVISO; RESUBMITTED
 DRAWINGS DID NOT ADDRESS THESE CONDITIONS; NEXT
 SUBMITTAL SHOULD SHOW MODIFICATIONS**
  
 1) PLEASE MODIFY SITE PLAN TO ALIGN CURB CUT AND 24'-0"
 WIDE PARKING LOT DRIVE.
 2) PLANS PRESENTLY ARE INCORRECT, SHOWING CARS ENTERING
 OVER SIDEWALK
 3) CURB CUT SHOULD BE MOVED WEST FOR CORRECT ALIGNMENT
 4) ACCURATE LANDSCAPE PLANS ARE NOT PROVIDED; ZONING
 WILL REVIEW INSTALLATION PER DAC APPROVAL
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-03 Cont ID  
Sent By mflis Date 2007-07-03 Time 08:57 Rev Time 0.00
Received By mflis Date 2007-07-03 Time 08:57 Sent To  
Notes
2007-07-03 09:00:55ZONING REVIEW: APPROVED WITH PROVISO:
  
 1) PLEASE MODIFY SITE PLAN TO ALIGN CURB CUT AND 24'-0"
 WIDE PARKING LOT DRIVE.
  
 * PLANS PRESENTLY ARE INCORRECT, SHOWING CARS ENTERING
 OVER SIDEWALK
 * CURB CUT SHOULD BE MOVED WEST FOR CORRECT ALIGNMENT
 * ACCURATE LANDSCAPE PLANS ARE NOT PROVIDED; ZONING
 WILL REVIEW INSTALLATION
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-23 Cont ID  
Sent By aaponte Date 2007-02-23 Time 16:20 Rev Time 0.00
Received By aaponte Date 2007-02-23 Time 16:19 Sent To  
Notes
2007-02-23 16:20:45PLEASE MODIFY THE PARKING ACCORDING WITH CONDITIONS
 IMPOSED BY DAC APPROVAL.