Plan Review Details - Permit 07020109
Plan Review Stops For Permit 07020109
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-14 Cont ID  
Sent By jwitmer Date 2007-02-14 Time 11:40 Rev Time 0.77
Received By jwitmer Date 2007-02-14 Time 11:40 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-09 Cont ID  
Sent By jwitmer Date 2007-02-09 Time 08:18 Rev Time 0.77
Received By jwitmer Date 2007-02-09 Time 08:18 Sent To  
Notes
2007-02-09 08:21:40BUILDING PLAN REVIEW
 PERMIT: 07020109
 ADD: 3900 N FFLAGLER DR
 CONT: LATITE
 TEL: (9540275-6024
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3)) THIS FLAT OOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 _XX__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By jwitmer Date 2007-02-06 Time 06:51 Rev Time 0.77
Received By jwitmer Date 2007-02-06 Time 06:51 Sent To PC
Notes
2007-02-06 06:54:30BUILDING PLAN REVIEW
 PERMIT: 07020109
 ADD: 3900 N FFLAGLER DR
 CONT: LATITE
 TEL: (9540275-6024
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3) THE PRODUCT APPROVAL (06-0626.03) JOHN MANSVILLE
 MODIFIED BITUMEN ROOFING OVER CONCRETE DECKS WAS
 SUBMITTED AS PART OF THIS PERMIT PACKAGE,
 THE MASTER PERMIT NUMBER ENTERED ON THE PERMIT
 APPLICATION INDICATES SITE AMENITIES PERMIT WHICH
 INCLUDES THE GAURD HOUSE. THE PERMIT APPLIED FOR
 DOESN'T INDICATE WHICH BUILDING THIS ROOF IS TO BE
 APPLIED FOR?THIS REVIEW WILL ASSUME THE ROOF PERMIT
 APPLIED FOR UNDER THIS PERMIT IS FOR THE GAURD HOUSE.
  
 4) THE GAURD HOUSE HAS WOOD TRUSSES AND A PLYWOOD ROOF
 DECK NOT A CONCRETE DECK, WRONG NOA WAS SUBMITTED. NOTE
 THE FOLLOWING INFORMATION IS REQUIRED FOR NAILABLE FLAT
 DECK APPLICATIONS: THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 __X_ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 _NOT KNOWN__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 _NOT KNOWN__THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 5) SUBMITTED IS A MIAMI-DADE NOA POLY STICK
 UNDERLAYMENTS, THERE IS NO INFORMATION AS TO WHICH ROOF
 SYSSTEM IT IS TO BE USED WITH?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]