Plan Review Details - Permit 07020059
Plan Review Stops For Permit 07020059
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2007-06-01 Cont ID  
Sent By lursu Date 2007-06-01 Time 08:25 Rev Time 0.00
Received By lursu Date 2007-06-01 Time 08:25 Sent To  
Notes
2007-06-01 08:28:08THE MINOR SUBDIVISION WAS APPROVED BY PLANING & ZONING
 DEPARTMENT BASED ON THE P&Z E-MAIL DATED 5/29/07 . THE
 NEW SITE ADDRESS FOR THE NEW LOT IS 1030 PALM BEACH
 LAKES BLVD , WEST PALM BEACH , FL 33401.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-02-13 Cont ID  
Sent By lursu Date 2007-02-13 Time 15:57 Rev Time 0.00
Received By lursu Date 2007-02-13 Time 15:57 Sent To  
Notes
2007-02-13 15:59:27PRIOR OF ASSIGNINGA NEW SITE ADDRESS FOR LOT 7 A
 MINOR SUBDIVISION IS NECESSARY TO BE APPROVED BY THE
 PLANING & ZONING DEPT.THE NEW LOT WILL HAVE A NEW
 PARCEL CONTROL NUMBER ( TO BE ISSUED BY THE PROPERTY
 APPRAISER'S OFFICE) AND THEN THE PERMIT WILL BE
 ASSIGNED TO THE NEW LOT AND THE NEW ADDRESS.
  
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-02-12 Cont ID  
Sent By lursu Date 2007-02-12 Time 11:07 Rev Time 0.00
Received By lursu Date 2007-02-05 Time 15:36 Sent To  
Notes
2007-02-12 11:07:41PERMIT UNDER REVIEW
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
2007-02-05 15:37:16COPY OF APPL. SENT TO LILLI

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 2007-05-15 Cont ID  
Sent By jgomez Date 2007-05-15 Time 10:28 Rev Time 0.00
Received By jgomez Date 2007-05-15 Time 07:47 Sent To  
Notes
2007-05-15 10:49:33BUILDING REVIEW SECOND CHECKLIST:
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 2- PAY IMPACT IMPACT FEES. BRING BACK STAMPED PLANS AND
 COPY OF PAID RECEIPT.
  
 3- ENERGY CALCULATIONS:
 A) REVISE OVERHANG LENGTH AND HEIGHT. SEE ELEVATIONS
 AND REVISE AS REQUIRED.
  
 B) COMPLETE ALL INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER AND CORRECT OWNER'S NAME.
  
 4- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS.
 NEED PRODUCT APPROVAL,KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE OF
 INSTALLATION SCHEDULE.
 ALSO, DESIGNER OF RECORD TO REVIEW AND APPROVE PRODUCT
 APPROVAL AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO
 FBC 2004.
  
 5- OWES $2527.82 FOR UPDATED VALUATION AND PERMIT
 APPLICATION BALANCE.
  
 6- REVISE SURVEY.BUILDING IS LOCATED ON FLOOD ZONE
 "B", NOT "C".SEE MARCH 1ST, 1979 MAP.
  
 7- SHEET A-4.1:DELETE ON ORIGINAL DRAWINGS DETAILS
 THAT DON'T APPLY TO THIS PROJECT.CORRECTIONS BY HAND
 ARE NOT ALLOWED.
  
 8- SHEET S-3:REVISE PLYWOOD SHEATHING NAILING
 SCHEDULE. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR MIN. TYPE OF NAIL TO BE USED AND
 REVISE AS REQUIRED.
 ***ALSO, DELETENOTE REGARDING RING SHANK NAILS NOT
 REQUIRED WHEN MEAN ROOF HEIGHT IS LESS THAN 25'-0".
 THEY ARE REQUIRED NOW.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-21 Cont ID  
Sent By jgomez Date 2007-03-20 Time 18:59 Rev Time 0.00
Received By jgomez Date 2007-03-20 Time 18:59 Sent To PC
Notes
2007-03-21 18:52:07BUILDING REVIEWCHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC 713.13
 FLORIDA STATUTES.
  
 2- BRING PLANS TO PALM BEACH COUNTY FOR IMPACT FEES.
 BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT.
 ***NOTE: MAKE SURE CORRECT BUILDING AREA IS SHOWN ON
 PLANS.
  
 3- SHEET A-1.0:
 A) REVISE TYPE OF CONSTRUCTION. SEE SEC. 602 FBC
 2004. TYPE OF CONSTRUCTION SHOWN ON PLANS APPLIES TO
 TYPE IIIB.
 B) ADD 2004 FLORIDA RESIDENTIAL CODE, WHICH IS THE
 ONE THAT APPLIES TO SINGLE FAMILY RESIDENCES.
 C) AREA CALCULATIONS ON SHEET A-1.0 ARE DIFFERENT
 THAN THOSE SHOWN ON SHEET A-1.1. REVISE AS REQUIRED.
  
 4- ENERGY CALCULATIONS:
 A) REVISE OVERHANG LENGTH AND HEIGHT. SEE PLANS.
  
 B) MAKE SURE A/C AREA MATCHES PLANS.
 C) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS.
 PROVIDE PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE OF INSTALLATION
 SCHEDULE.
  
 *** NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.
  
 6- BUILDING VALUATION AND RADON FEES WILL BE UPDATED
 WHEN CORRECT FLOOR AREAS ARE PROVIDED.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) INSWING ENTRY DOOR AS SHOWN ON PLANS.
 *** NOTE: PLEASE MAKE SURE DRAWINGS ARE LEGIBLE.
 B) IMPACT SLIDING GLASS DOORS AS SPECIFIED ON
 PLANS.
 *** NOTE: SEE SIZE OF DOORS SPECIFIED ON PLANS.
 C) DOUBLE GARAGE DOOR AS SHOWN ON EXTERIOR
 ELEVATION.
 D) ASPHALT SHINGLES.NOA #04-0305.03 EXPIRED ON
 02/21/07.
 E) SINGLE HUNG WINDOWS. NEED LEGIBLE DRAWINGS. F)
 COLONIAL SHUTTERS SHOWN ON EXTERIOR ELEVATIONS.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 9- ARCHITECT TO PROVIDE ALL HIS INFORMATION AND FIRM'S
 REGISTRATION NUMBERAS REQUIRED BY SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 10- SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 472 FLORIDA STATUTES.
  
 11- SHEET A-2.1:
 A) FLOOR PLAN CALLS FOR ONE 16'X7' GARAGE DOOR.
 ELEVATION SHOWS 2 SMALL GARAGE DOORS. CLARIFY/REVISE AS
 REQUIRED TO MATCH.
 B) REVISE ELEVATIONS CARDINAL ORIENTATION. SEE
 SURVEY FOR CORRECT ORIENTATION.
  
 12- SHEET A-3.1:A) PORCH SECTION AND TYPICAL WALL
 SECTION CALL FOR "ASPHALT TILE ROOF". CLARIFY WHAT IS
 IT?. REVISE AS REQUIRED.
  
 B) SPECIFY FASTENERS FOR 2X4 FRAMED DOWN CEILING AT
 ENTRY PORCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 13- SHEET A-4.1:
 A) DETAIL #1 IS FOR WINDOW AND DOOR BUCK DETAIL.
 CLARIFY TITLE SAYS WINDOW, WHILE DETAIL SAYS DOOR
 FRAME.
 B) THERE ARE TWO DIFFERENT SPECS FOR BUCK FASTENING.
 SEE DETAIL 1 AND WINDOW/DOOR BUCK NOTES ON SHEET S-2
 AND REVISE AS REQUIRED.
 C) HURRICANE PANEL DETAIL: EDGE DISTANCE IS
 INCORRECT. STUCCO THICKNESS CAN'T BE CONSIDERED FOR
 EDGE DISTANCE. REVISE AS REQUIRED. SEE ACTUAL STORM
 PANELS PRODUCT APPROVAL.
 ***NOTE: THIS DETAIL IS NOT REQUIRED. IT'S EASIER AND
 WILL AVOID DISCREPANCIES IF ONLY THE PRODUCT APPROVAL
 FOR STORM SHUTTERS IS PROVIDEDANDAPPROVED BY THE
 DESIGNER OF RECORD.
 D) SECTION AT REAR PORCH: SPECIFY LEDGERS FOR ROOF
 SHEATHING SUPPORT AT MASONRY WALL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 ALSO,SPECIFY FIREBLOCKING. SEC. R602.8 2004 FLORIDA
 RESIDENTIAL CODE.
  
 14- SHEET S-2:DETAIL 1/S-2 CALLS FOR (3)2X4 STUDS,
 WHILE 2ND FLOOR FRAMING PLAN CALLS FOR (4)2X4 STUDS.
 CLARIFY/REVISE AS REQUIRED TO MATCH.
  
  
 15- SHEET S-3:
 A) REVISE PLYWOOD SHEATHING NAILING SPECIFICATIONS
 FOR ROOF SHEATHING. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 B) SPECIFICATION GIVENON PLYWOOD SHEATHING NAILING
 SCHEDULE AND OVERHANG DETAIL DON'T MATCH. REVISE AS
 REQUIRED.
 C) CONNECTOR SCHEDULE: REVISE UPLIFT AND FASTENERS
 SPECIFIED FOR SIMPSON HETAL 16 AND SP4. SEE CURRENT
 CATALOG AND UPDATE AS REQUIRED. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING ANALYSIS FOR VALUES AND NUMBERS
 THAT ARE DIFFERENT FROM THOSE TESTED AND PUBLISHED BY
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 D) MAXIMUM DESIGN PRESSURES SHOWN ARE LOW COMPARED
 TO TABLE R301.2((2) OF 2004 FLORIDA RESIDENTIALCODE
 OR TABLES IN ASCE 7-02.PROVIDE ACTUAL CALCULATIONS
 SHOWING HOW THE MAXIMUM POSITIVE AND NEGATIVE LOADS ARE
 DETERMINED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 16- SOIL TEST REPORT TO HAVE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER IN ALL SHEETS AS
 REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-10 Cont ID  
Sent By btrobaug Date 2007-05-10 Time 11:18 Rev Time 0.50
Received By btrobaug Date 2007-05-10 Time 10:57 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-08 Cont ID  
Sent By btrobaug Date 2007-02-08 Time 11:41 Rev Time 1.00
Received By btrobaug Date 2007-02-08 Time 06:42 Sent To M
Notes
2007-02-08 11:41:07 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. ELECTRICAL NOTE #15 DOES NOT
 SATISFY THIS REQUIREMENT.
  
 2} THE REFERENCE TO THE 2002NEC IS ALSO INCORRECT IN
 THAT NOTE. THE 2005 NEC WAS ADOPTED BY THE FLORIDA
 LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE APPLICATION
 FOR THIS PROJECT WAS AFTER THAT DATE AND THE PLANS ARE
 SUBJECT TO THAT CODE. PLEASE CHANGE ALL NOTES TO
 REFLECT THIS CHANGE.
  
 3} THE RISER DIAGRAM IS UNCLEAR ON HOW THE SERVICE
 ENTRANCE CONDUCTORS ROUTE TO THE MAIN BRAKER. IF THEY
 ROUTE OVERHEAD THROUGH THE GARAGE, THEN A MAIN
 DISCONNECT IS REQUIRED AT THE METER. SEE 230.70(A)(1).
 IF THEY ARE UNDER THE SLAB THE MAIN IN THE PANEL WOULD
 BE ACCEPTABLE. PLEASE CLARIFY AND ADD THE DISCONNECT IF
 NECESSARY.
  
 4} A RECEPTACLE IS REQUIRED IN THE 2ND FLOOR HALL PER
 21052(E).
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-09 Cont ID  
Sent By adarroug Date 2007-05-09 Time 16:57 Rev Time 0.00
Received By adarroug Date 2007-05-09 Time 16:57 Sent To E
Notes
2007-05-09 16:57:49TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-26 Cont ID  
Sent By adarroug Date 2007-04-26 Time 16:50 Rev Time 0.00
Received By adarroug Date 2007-04-26 Time 16:50 Sent To Z
Notes
2007-04-26 16:51:10TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-20 Cont ID  
Sent By jgomez Date 2007-03-20 Time 18:59 Rev Time 0.00
Received By jgomez Date 2007-02-05 Time 15:38 Sent To  
Notes
2007-02-05 15:39:01TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-10 Cont ID  
Sent By tgordon Date 2007-05-10 Time 11:49 Rev Time 0.30
Received By tgordon Date 2007-05-10 Time 11:49 Sent To B
Notes
2007-05-10 12:07:55*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) COOLING LOAD CALCULATIONS ARE MISSING FROM ENERGY
 CAL'S. PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE
 2004 FBC 13-607.1.ABC.1.
  
 3) A/C EQUIPMENT LISTING ON PLANS DOES NOT SHOW
 INFORMATION REGARDING THE CONDENSER UNIT, PLEASE ADD
 THAT INFORMATION TO PLANS.
  
 4) THE 12" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE
 NEEDS TO BE 18", SEE 2004 FBC/R M1602.4 (A) AND (C)
 EXCEPT, PLEASE CORRECT.
  
 *** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-12 Cont ID  
Sent By tgordon Date 2007-02-12 Time 16:15 Rev Time 0.30
Received By tgordon Date 2007-02-12 Time 16:15 Sent To P
Notes
2007-02-12 16:20:14*** DENIED ***
 1) PLEASE SHOW ON ENERGY CALCULATIONS CORRECT ADDRESS
 (WEST PALM BEACH) AND ALSO SHOW JURISDICTION NUMBER.
  
 2)NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW.
 PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC
 WPB AMEND. 106.3.5.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-02-14 Cont ID  
Sent By btrobaug Date 2007-02-08 Time 12:17 Rev Time 0.00
Received By jleech Date 2007-02-14 Time 15:02 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By astelly Date 2007-05-07 Time 14:30 Rev Time 0.00
Received By astelly Date 2007-05-07 Time 14:30 Sent To I
Notes
2007-05-07 15:10:33AMY F. STELLY, URBAN DESIGN
 822-1440
 1. PLEASE SUBMIT THE PROPER SURVEY FOR THE SUBJECT
 PROPERTY.
 2. PLEASE LOCATE THE PARKING BEHIND THE PRINCIPAL
 FACADE AS PER SEC. 94-103(D)(1). THE ENCLOSED GARAGE
 MUST BE LOCATED BEHIND THE FACADE OF THE PRINCIPAL
 FRONTAGE.
 3. PLEASE INDICATE FRONT AND SIDE SETBACK DIMENSIONS ON
 THE SITE PLAN.
 4. PLEASE SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE
 WITH SECS. 94-1023(G) AND 94-442.
 5. PLEASE CONSIDER ADDING WINDOWS TO THE UPPER STORY OF
 THE RIGHT ELEVATION IN ORDER TO PROVIDE LIGHT AND CROSS
 VENTILATION - ESPECIALLY IN THE BATH AND LAUNDRY
 ROOMS.
 6. PLEASE CONSIDER ADDING WINDOWS ON BOTH THE UPPER AND
 LOWER STORIES OF THE LEFT ELEVATION.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By mmclean Date 2007-02-06 Time 16:40 Rev Time 0.00
Received By mmclean Date 2007-02-06 Time 15:43 Sent To E
Notes
2007-02-06 15:46:44DENIED,
 1. THE PROPOSED A/C IS SHOWN ON THE TWO COPIES OF
 SURVEY IN THE REAR OF THE PROPERTY (SOUTH) AND ON THE
 FLOOR PLAN IT IS SHOWN ON THE EAST SIDE, PLEASE CLARIFY
 TOHE ACTUAL LOCATION OF PROPOSED UNIT. SEC 94-303
 MECHANICAL/POOL EQUIPMENT/GENERATOR MAY NOT PROJECT
 MORE THAN FOUR FEET INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  
  