Plan Review Details - Permit 07020052
Plan Review Stops For Permit 07020052
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-08 Cont ID  
Sent By jgomez Date 2007-05-08 Time 11:01 Rev Time 0.00
Received By jgomez Date 2007-05-08 Time 11:00 Sent To Z
Notes
2007-05-08 11:31:37BUILDING REVIEW SECOND CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- NEED TO PAY IMPACT FEES TO PALM BEACH COUNTY AND
 BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT.
  
 3- ENERGY CALCULATIONS:
 A) OVERHANG LENGHT AND OVERHANG HEIGHT ARE
 INCORRECT. SEEELEVATIONS AND REVISE AS REQUIRED.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME.
  
 C) ARCHITECT SIGNING ENERGY CALCULATIONS NEED TO
 PROVIDE HIS SEALAS REQUIRED BY SEC. 481 FLORIDA
 STATUTE AND FLORIDA ADMINISTRATIVE CODE SEC.
 61G1-16.003.
  
 D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 4- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS,
 INCLUDING PRODUCT APPROVAL, KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE OF
 INSTALLATION SCHEDULE.
 ***NOTE:DESIGNER OF RECORD TO REVIEW AND APPROVE
 PRODUCT APPROVAL PRIOR TO SUBMITTAL.
  
 5- OWES $2527.82 FOR BUILDING VALUATION UPDATE, RADON
 FEES AND BALANCE DUE BECAUSE TOTAL PERMIT APPLICATION
 FEE WAS NOT PAID AT TIME OF PERMIT APPLICATION.
  
 6-ONE OF THE GARAGE DOORS PRODUCT APPROVALS IS
 MISSING THE ARCHITECT'S REVIEW STAMP. COMPLETE AS
 REQUIRED.
  
 7- SHEET A-4.1:
 A) CLARIFY DETAIL #1. IT'S THIS DETAIL FOR WINDOW OR
 DOOR. TITLE SAYS FOR WINDOW,WHILE DETAILSAYS FOR
 DOOR.
 ON THE OTHER HAND DETAIL DOESN'T MATCH SPECS SHOWN ON
 STRUCTURAL DRAWINGS. REVISE AS REQUIRED.
  
 B) HURRICANE PANEL DETAIL: EDGE DISTANCE IS MEASURED
 WRONG. REVISE AS REQUIRED.
 ***NOTE:THIS DETAIL IS NOT REQUIRED. IT'S EASIER AND
 LESS CONFUSING IF SUBMITTING ONLY THE PRODUCT APPROVAL
 FOR STORM SHUTTERS ALONG WITH COMPLETE INSTALLATION
 SCHEDULE.
  
 8- SHEET S-3:
 A) REVISE ROOF SHEATHING NAILING SPECIFICATIONS. SEE
 SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 MINIMUM SIZE AND TYPE OF NAIL TO BE USED.
 ALSO, DELETE NOTE REGARDING RING SHANK NAILS NOT
 REQUIRED IFMEAN ROOF HEIGHT IS LESS THAN 25'.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-23 Cont ID  
Sent By jgomez Date 2007-03-23 Time 14:00 Rev Time 0.00
Received By jgomez Date 2007-03-23 Time 14:00 Sent To PC
Notes
2007-03-23 14:10:03BUILDING REVIEWCHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC 713.13
 FLORIDA STATUTES.
  
 2- BRING PLANS TO PALM BEACH COUNTY FOR IMPACT FEES.
 BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT.
 ***NOTE: MAKE SURE CORRECT BUILDING AREA IS SHOWN ON
 PLANS.
  
 3- SHEET A-1.0:
 A) REVISE TYPE OF CONSTRUCTION. SEE SEC. 602 FBC
 2004. TYPE OF CONSTRUCTION SHOWN ON PLANS APPLIES TO
 TYPE IIIB.
 B) ADD 2004 FLORIDA RESIDENTIAL CODE, WHICH IS THE
 ONE THAT APPLIES TO SINGLE FAMILY RESIDENCES.
 C) AREA CALCULATIONS ON SHEET A-1.0 ARE DIFFERENT
 THAN THOSE SHOWN ON SHEET A-1.1. REVISE AS REQUIRED.
  
 4- ENERGY CALCULATIONS:
 A) REVISE OVERHANG LENGTH AND HEIGHT. SEE PLANS.
  
 B) MAKE SURE A/C AREA MATCHES PLANS.
 C) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS.
 PROVIDE PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE OF INSTALLATION
 SCHEDULE.
  
 *** NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING PRODUCT APPROVAL AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.
  
 6- BUILDING VALUATION AND RADON FEES WILL BE UPDATED
 WHEN CORRECT FLOOR AREAS ARE PROVIDED.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) INSWING ENTRY DOOR AS SHOWN ON PLANS.
 *** NOTE: PLEASE MAKE SURE DRAWINGS ARE LEGIBLE.
 B) IMPACT SLIDING GLASS DOORS AS SPECIFIED ON
 PLANS.
 *** NOTE: SEE SIZE OF DOORS SPECIFIED ON PLANS.
 C) DOUBLE GARAGE DOOR AS SHOWN ON EXTERIOR
 ELEVATION.
 D) ASPHALT SHINGLES.NOA #04-0305.03 EXPIRED ON
 02/21/07.
 E) SINGLE HUNG WINDOWS. NEED LEGIBLE DRAWINGS. F)
 COLONIAL SHUTTERS SHOWN ON EXTERIOR ELEVATIONS.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 9- ARCHITECT TO PROVIDE ALL HIS INFORMATION AND FIRM'S
 REGISTRATION NUMBERAS REQUIRED BY SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 10- SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 472 FLORIDA STATUTES.
  
 11- SHEET A-2.1:
 A) FLOOR PLAN CALLS FOR ONE 16'X7' GARAGE DOOR.
 ELEVATION SHOWS 2 SMALL GARAGE DOORS. CLARIFY/REVISE AS
 REQUIRED TO MATCH.
 B) REVISE ELEVATIONS CARDINAL ORIENTATION. SEE
 SURVEY FOR CORRECT ORIENTATION.
  
 12- SHEET A-3.1:A) PORCH SECTION AND TYPICAL WALL
 SECTION CALL FOR "ASPHALT TILE ROOF". CLARIFY WHAT IS
 IT?. REVISE AS REQUIRED.
  
 B) SPECIFY FASTENERS FOR 2X4 FRAMED DOWN CEILING AT
 ENTRY PORCH. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 13- SHEET A-4.1:
 A) DETAIL #1 IS FOR WINDOW AND DOOR BUCK DETAIL.
 CLARIFY TITLE SAYS WINDOW, WHILE DETAIL SAYS DOOR
 FRAME.
 B) THERE ARE TWO DIFFERENT SPECS FOR BUCK FASTENING.
 SEE DETAIL 1 AND WINDOW/DOOR BUCK NOTES ON SHEET S-2
 AND REVISE AS REQUIRED.
 C) HURRICANE PANEL DETAIL: EDGE DISTANCE IS
 INCORRECT. STUCCO THICKNESS CAN'T BE CONSIDERED FOR
 EDGE DISTANCE. REVISE AS REQUIRED. SEE ACTUAL STORM
 PANELS PRODUCT APPROVAL.
 ***NOTE: THIS DETAIL IS NOT REQUIRED. IT'S EASIER AND
 WILL AVOID DISCREPANCIES IF ONLY THE PRODUCT APPROVAL
 FOR STORM SHUTTERS IS PROVIDEDANDAPPROVED BY THE
 DESIGNER OF RECORD.
 D) SECTION AT REAR PORCH: SPECIFY LEDGERS FOR ROOF
 SHEATHING SUPPORT AT MASONRY WALL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 ALSO,SPECIFY FIREBLOCKING. SEC. R602.8 2004 FLORIDA
 RESIDENTIAL CODE.
  
 14- SHEET S-2:DETAIL 1/S-2 CALLS FOR (3)2X4 STUDS,
 WHILE 2ND FLOOR FRAMING PLAN CALLS FOR (4)2X4 STUDS.
 CLARIFY/REVISE AS REQUIRED TO MATCH.
  
  
 15- SHEET S-3:
 A) REVISE PLYWOOD SHEATHING NAILING SPECIFICATIONS
 FOR ROOF SHEATHING. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 B) SPECIFICATION GIVENON PLYWOOD SHEATHING NAILING
 SCHEDULE AND OVERHANG DETAIL DON'T MATCH. REVISE AS
 REQUIRED.
 C) CONNECTOR SCHEDULE: REVISE UPLIFT AND FASTENERS
 SPECIFIED FOR SIMPSON HETAL 16 AND SP4. SEE CURRENT
 CATALOG AND UPDATE AS REQUIRED. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING ANALYSIS FOR VALUES AND NUMBERS
 THAT ARE DIFFERENT FROM THOSE TESTED AND PUBLISHED BY
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 D) MAXIMUM DESIGN PRESSURES SHOWN ARE LOW COMPARED
 TO TABLE R301.2((2) OF 2004 FLORIDA RESIDENTIALCODE
 OR TABLES IN ASCE 7-02.PROVIDE ACTUAL CALCULATIONS
 SHOWING HOW THE MAXIMUM POSITIVE AND NEGATIVE LOADS ARE
 DETERMINED. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 16- SOIL TEST REPORT TO HAVE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER IN ALL SHEETS AS
 REQUIRED BY SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-30 Cont ID  
Sent By btrobaug Date 2007-04-30 Time 17:30 Rev Time 0.50
Received By btrobaug Date 2007-04-30 Time 17:13 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-12 Cont ID  
Sent By btrobaug Date 2007-02-12 Time 07:09 Rev Time 0.50
Received By btrobaug Date 2007-02-12 Time 06:53 Sent To Z
Notes
2007-02-12 07:09:12 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT. ELECTRICAL NOTE #15 DOES NOT
 SATISFY THIS REQUIREMENT.
  
 2} THE REFERENCE TO THE 2002 NEC IS ALSO INCORRECT IN
 THAT NOTE. THE 2005 NEC WAS ADOPTED BY THE FLORIDA
 LEGISLATURE EFFECTIVE 8 DECEMBER 2006. THE APPLICATION
 FOR THIS PROJECT WAS AFTER THAT DATE AND THE PLANS ARE
 SUBJECT TO THAT CODE. PLEASE CHANGE ALL NOTES TO
 REFLECT THIS CHANGE.
  
 3} THE RISER DIAGRAM IS UNCLEAR ON HOW THE SERVICE
 ENTRANCE CONDUCTORS ROUTE TO THE MAIN BREAKER. IF THEY
 ROUTE OVERHEAD THROUGH THE GARAGE, THEN A MAIN
 DISCONNECT IS REQUIRED AT THE METER. SEE 230.70(A)(1).
 IF THEY ARE UNDER THE SLAB THE MAIN IN THE PANEL WOULD
 BE ACCEPTABLE. PLEASE CLARIFY AND ADD THE DISCONNECT IF
 NECESSARY.
  
 4} A RECEPTACLE IS REQUIRED IN THE 2ND FLOOR HALL PER
 21052(E).
  
 5} THE WATER HEATER CIRCUIT 21,23, IS LISTED AS A 30
 AMP SINGLE POLE IN THE SCHEDULE, PLEASE CORRECT.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPARTMENT
 561) 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-26 Cont ID  
Sent By adarroug Date 2007-04-26 Time 16:42 Rev Time 0.00
Received By adarroug Date 2007-04-26 Time 16:42 Sent To E
Notes
2007-04-26 16:42:53TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-23 Cont ID  
Sent By jgomez Date 2007-03-23 Time 14:00 Rev Time 0.00
Received By jgomez Date 2007-02-09 Time 09:50 Sent To  
Notes
2007-02-09 09:50:39TO "SFR" "Z"--PLANS IN IN-COMING TODAY

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-01 Cont ID  
Sent By tgordon Date 2007-05-01 Time 09:37 Rev Time 0.45
Received By tgordon Date 2007-05-01 Time 09:37 Sent To B
Notes
2007-05-01 10:00:55*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) ENERGY CALCULATIONS, CONSERVATION CREDITS SHOW
 DEDICATED HEAT PUMP BEING INSTALLED, ELECTRICAL PLANS
 SHOW AN ELECTRIC HEATER BEING INSTALLED, MECHANICAL
 PLANS SHOW NO HEAT BEING INSTALLED, PLEASE CORRECT SO
 ALL THREE ARE THE SAME.
  
 3) MECHANICAL PLANS EQUIPMENT LISTING NEED CONDENSER
 UNIT MODEL NUMBER, ELECTRIC HEATER KW, IF HEAT PUMP
 UNIT PLEASE STATE SO ON PLANS SO SEER MAY BE VERIFIED
 WITH THE ARI DIRECTORY.
  
 4) SEE MECHANICAL PLANS SHOW THE MASTER BATHROOM
 EXHAUST FAN OUTSIDE OF THE WATER CLOSET ROOM, IF TWO
 ARE BEING INSTALLED ADD ONE TO WATER CLOSET ROOM, IF
 NOT MOVE TO WATER CLOSET ROOM.
  
 5) SUPPLY AIR DUCT (FLEX) TO MIXING BOX FIRST FLOOR
 FAMILY ROOM NEEDS TO BE SIZED, SEE YELLOW HIGH LIGHT ON
 MECHANICAL PLANS.
  
 6) 12" RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS
 TO BE 16", SEE 2004 FBC/R M1602.4 (A) AND (C) EXCEPT.
 PLEASE CORRECT.
  
 ** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-16 Cont ID  
Sent By tgordon Date 2007-02-16 Time 11:40 Rev Time 0.30
Received By tgordon Date 2007-02-16 Time 11:40 Sent To P
Notes
2007-02-16 11:48:03*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW.
 PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC
 WPB AMEND. 106.3.5.4 (10).
  
 2) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, PER
 2004 FBC 13-600.3.A .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-02-20 Cont ID  
Sent By jleech Date 2007-02-20 Time 08:32 Rev Time 0.00
Received By jleech Date 2007-02-20 Time 08:32 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-02-23 Cont ID  
Sent By kdfreema Date 2007-02-23 Time 16:52 Rev Time 0.00
Received By kdfreema Date 2007-02-23 Time 16:52 Sent To  
Notes
***NONE***