2007-02-07 09:37:39 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS; CITY OF WEST PALM BEACH |
| AMENDMENTS TO FBC-2004 CHAPTER 1; FLORIDA STATUTES; |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PERMIT APPLICATION IS INCOMPLETE, PER FBC-2004 |
| CHAPTER 1, SECTION 105.3 AND FLORIDA STATUTES |
| 713.135(6) SIGNATURE OF CONTRACTOR REQUIRED. PLEASE |
| REFREENCE THE ATTACHED FLORIDA STATUTE INDICATING |
| THIS. |
| |
| 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: THIS INCLUDES THE EXISTING SYSTEM. |
| |
| 3. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: THIS INCLUDES THE EXISTING SYSTEM. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| NOTE: THIS INCLUDES THE EXISTING SYSTEM. |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY (EXISTING 2ND STAGE REGULATOR) TO THE MOST |
| REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: THIS INCLUDES THE EXISTING SYSTEM. |
| |
| 6. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| 7. PER FBC-2004, CHAPTER 1, SECTION |
| 108.3, BUILDING PERMIT VALUATION: IF IN |
| THE OPINION OF THE BUILDING OFFICIAL, |
| THE CLAIMED VALUATION OF THE BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, |
| THE PERMIT SHALL BE DENIED. FOR |
| PERMITTING PURPOSES, VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| FINISH, NORMAL SITE WORK (EXCAVATION AND |
| BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| VALUE. VALUATION REFERENCES MAY INCLUDE |
| THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| MEANS ECT.) WITH |
| REGIONAL ADJUSTMENTS FOR LOCATION AS |
| PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. |
| NOTE: VALUE INCLUDES THE NEW RANGE ALONG WITH THE GAS |
| PIPING. PLEASE SUBMIT COPY OF SIGNED CONTRACT TO |
| VERIFY. PLEASE ADJUST AND RESUBMIT. |
| |
| END OF COMMENTS: |
| |