Plan Review Details - Permit 07011172
Plan Review Stops For Permit 07011172
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-13 Cont ID  
Sent By shill Date 2007-03-13 Time 18:00 Rev Time 0.00
Received By shill Date 2007-03-13 Time 18:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-07 Cont ID  
Sent By shill Date 2007-03-07 Time 07:56 Rev Time 0.00
Received By shill Date 2007-03-07 Time 07:56 Sent To  
Notes
2007-03-07 07:58:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
 1.)SPANS DO NOT CORRELATE WITH OPENING SIZES.SEE
 OPENING 1, 62" SPAN ON A 64 INCH OPENING HEIGHT?
 OPENING 3, 75" SPAN ON A 28" OPENING?REVISE SPANS FOR
 ALL OPENINGS.
  
 2.)TWO COLLATED SETS OF ALL PERMIT DOCUMENTS
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-09 Cont ID  
Sent By shill Date 2007-02-09 Time 10:41 Rev Time 0.00
Received By shill Date 2007-02-09 Time 10:41 Sent To  
Notes
2007-02-09 10:43:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY
 AN ENGINEER. DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 _XX_8.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4
 ABOVE.
  
 ____9.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2).
 NOTE THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 FBC1609.4.
  
 _XX_10. SEE NOTE 2G OF ENGINEERING.ENCLOSURE
 CLASSIFICATION TO BE DETERMINED BY ARCHITECT OR
 ENGINEER IFF YOU USE THE LESS STRINGENT CONDITION.
 NOTE THAT ENGINEERING IS NOT REQUIRED FOR BUILDINGS
 UNDER 30FEET.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 15:51 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 15:51 Sent To B
Notes
2007-03-10 15:51:23TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 15:22 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 15:22 Sent To B
Notes
2007-03-06 15:22:58TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-09 Cont ID  
Sent By shill Date 2007-02-09 Time 10:43 Rev Time 0.00
Received By shill Date 2007-01-29 Time 18:28 Sent To  
Notes
2007-01-29 18:29:02TO "MISC" BOX#1