Plan Review Details - Permit 07011091
Plan Review Stops For Permit 07011091
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-30 Cont ID  
Sent By rmcdouga Date 2008-01-30 Time 10:04 Rev Time 0.00
Received By rmcdouga Date 2008-01-30 Time 10:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-03 Cont ID  
Sent By rmcdouga Date 2007-08-03 Time 15:00 Rev Time 0.00
Received By rmcdouga Date 2007-08-03 Time 15:00 Sent To  
Notes
2007-08-03 16:04:192004 FBC
 REPAIRS
  
 DENIED BY BUILDING
  
 1)THE INFORMATION ON THE ENERGY CALCULATION CAN NOT
 BE CHANGED BY USING WHITE-OUT OR MAKING HANDWRITTEN
 CHANGES. THE CORRECT INFORMTION IS REQUIRED TO BE INPUT
 INTO THE PROGRAM WHEN TO CALCULATIONS ARE BE PROCESSED.
 THE ATTIC INSULATION R-VALUE LISTED ON THE ENERGY CALC.
 FORMS DOES NOT CORRESPOND TO THE ONE SPECIFIED ON THE
 PLANS. SUBMIT NEW ENERGY CALC. FORMS. MAKE THE
 NECESSARY CORRECTIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-01 Cont ID  
Sent By rmcdouga Date 2007-03-01 Time 09:46 Rev Time 0.00
Received By rmcdouga Date 2007-03-01 Time 09:45 Sent To  
Notes
2007-03-01 10:51:35DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGNE THE ENERGY
 CALC. FORM PER FBC CHAPTER 13.
  
 3) THE NUMBER OF BEDROOMS ON THE PLANS IS 2 AND THE
 ENERGY CALC. FORM LISTS 1. PLEASE CORRECT.
  
 4) THE CONDITIONED FLOOR AREA FOR THE STRUCTURE IS
 LISTED AS 1058 SQFT ON THE ENERGY CALC. FORM AND BASED
 ON THE PLANS THE STRUCTURE IS 1243 SQFT. PLEASE
 CORRECT.
  
 5) SPECIFY THE THICKNESS OF THE DRYWALL FOR THE WALLS
 AND CEILING ON THE WALL SECTION ON SHEET 2.
  
 6) SPECIFY THE NUMBER, SIZES AND TYPES OF FASTENERS
 THAT WILL BE USED WITH THE CONNECTORS SHOWN IN THE WALL
 SECTION ON SHEET 2.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE USP AND SIMPSON
 CONNECTORS SPECIFIED ON THE PLANS.
  
 8)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 9)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-20 Cont ID  
Sent By btrobaug Date 2007-07-20 Time 07:16 Rev Time 0.00
Received By btrobaug Date 2007-07-20 Time 07:02 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By btrobaug Date 2007-01-30 Time 10:54 Rev Time 1.00
Received By btrobaug Date 2007-01-30 Time 07:32 Sent To M
Notes
2007-01-30 10:54:22 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} PLEASE INDICATE THE SIZE AND TYPE RACEWAY TO BE USED
 FOR THE SERVICE RISER AND PANEL FEEDER.
  
 3} PLEASE IDENTIFY THE 4/0 SERVICE CABLE FEEDING THE
 PANEL. (IG: SE).
  
 4} THE BATH CIRCUIT ,#6, ON THE SCHEDULE MUST BE 20 AMP
 TO COMPLY WITH 210.11(C)(3) AND 310.16.
  
 5} THE DINING ROOM MUST BE ON A SMALL APPLIANCE CIRCUIT
 , OR ITS OWN 20 AMP CIRCUIT PER 210.52(B).
  
 6} CIRCUIT #3 FEEDING THE SMOKE ALARMS MUST BE AFCI PER
 210.12.
  
 7} BOTH BEDROOMS MUST HAVE RECEPTACLES ADDED TO COMPLY
 WITH THE SPACING REQUIREMENTS OF 210.52(A)(1) AND (2).
 SEE REVIEWED SET OF PLANS.
  
 8} NOTE THATTHE REQUIRED RECEPTACLE PER 210.63. LIGHT
 PER 210.70(A) (3),MUST BE INSTALLED FOR THE AIR
 HANDLER IN THE ATTIC.
  
 9} THE WATER HEATER IS SHOWN AS BEING PLUGGED INTO A
 RECEPTACLE. PLEASE SEE 422.16 FOR CORD AND PLUG
 ATTACHED APPLIANCES RESTRICIION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-26 Cont ID  
Sent By adarroug Date 2009-02-26 Time 15:25 Rev Time 0.00
Received By adarroug Date 2009-02-26 Time 15:25 Sent To P
Notes
2009-02-26 15:25:45TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-28 Cont ID  
Sent By adarroug Date 2008-01-28 Time 10:19 Rev Time 0.00
Received By adarroug Date 2008-01-28 Time 10:19 Sent To M
Notes
2008-01-28 10:20:16TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-17 Cont ID  
Sent By adarroug Date 2007-07-17 Time 16:58 Rev Time 0.00
Received By adarroug Date 2007-07-17 Time 16:58 Sent To E
Notes
2007-07-17 16:58:45TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-17 Cont ID  
Sent By rmcdouga Date 2007-03-01 Time 10:51 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 11:11 Sent To  
Notes
2007-01-29 11:11:42TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-01-29 Cont ID  
Sent By tgordon Date 2008-01-29 Time 09:42 Rev Time 0.30
Received By tgordon Date 2008-01-29 Time 09:42 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-02 Cont ID  
Sent By tgordon Date 2007-08-02 Time 14:33 Rev Time 0.30
Received By tgordon Date 2007-08-02 Time 14:33 Sent To B
Notes
2007-08-02 14:40:32*** DENIED ***
 1) PLANS PAGE 2/3 IS SHOWING R-19 INSULATION IN THE
 ATTIC, ENERGY CALCULATIONS LINE 11A STATES R-30. PLEASE
 CORRECT.
  
 2) PLANS PAGE 2/3 SHOWS NO INSULATION TO BE PUT IN
 EXTERIOR WALLS, ENERGY CAL'S. STATE R-11. PLEASE
 CORRECT.
  
 3) PLEASE BE ADVISED NO CHANGES MAY BE DONE WITH
 WHITE-OUT, PEN, OR PENCIL.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-31 Cont ID  
Sent By tgordon Date 2007-01-31 Time 14:01 Rev Time 0.30
Received By tgordon Date 2007-01-31 Time 14:01 Sent To P
Notes
2007-01-31 14:15:47*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) PLEASE SHOW SIZE OF SUPPLY AIR TRUNK LINE TO BEDROOM
 ON MECHANICAL PLANS.
  
 3) IF THE AIR FILTER IS NOT AT THE AHU BUT AT THE 24X12
 RETURN AIR GRILL THEN THE 8X6 RETURN AIR GRILL IN THE
 BEDROOM WILL NEED A FILTER ALSO, PLEASE STATE AIR
 FILTER LOCATION ON MECH. PLANS.
  
 4) 4X12 RETURN AIR TRANSFER GRILL TO BEDROOM IS TO
 SMALL FOR 200 CFM'S.BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-03-06 Cont ID  
Sent By lwagner Date 2009-03-06 Time 11:13 Rev Time 0.00
Received By lwagner Date 2009-03-06 Time 10:55 Sent To  
Notes
2009-03-06 11:13:40REVISION OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-02 Cont ID  
Sent By jleech Date 2007-08-02 Time 13:31 Rev Time 0.00
Received By jleech Date 2007-08-02 Time 13:31 Sent To M
Notes
2007-08-02 13:32:05FIXTURE CHANGE OUT ONLY

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-03 Cont ID  
Sent By jleech Date 2007-02-03 Time 09:49 Rev Time 0.00
Received By jleech Date 2007-02-03 Time 09:49 Sent To B
Notes
2007-02-03 09:57:48DENIED;
 NOT ENOUGH INFORMATION TO DO A PLUMBING PLAN REVIEW.
 ADD NOTES ON PLANS TO SHOW WHAT PLUMBING WORK IS TO BE
 DONE; @ ALL FIXTURES AND VALVES TO BE REPLACED NO
 PIPING TO BE DONE. OR, REPLACE FIXTURE MARKED ON PLAN
 ONLY . REPLACE ANY BROKEN OR CORRODED PIPING AS
 REQUIRED TEST AND INSPECT AS REQUIRED. ETC.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695