Plan Review Stops For Permit 07011070 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2007-12-28 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-12-28 |
Time |
09:58 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-12-28 |
Time |
09:58 |
Sent To |
|
|
Notes |
2007-12-28 09:58:28 | REVISION (WINDOWS) |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2007-12-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-12-05 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-12-05 |
Time |
10:31 |
Sent To |
|
|
Notes |
2007-12-05 10:42:17 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.NON IMPACT WINDOWS ARE NOT PERMITTED ON THE SECOND | | FLOOR. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2007-11-19 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-11-19 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-11-19 |
Time |
13:17 |
Sent To |
|
|
Notes |
2007-11-19 13:19:22 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.IT APPEARS THAT YOU WOULD LIKE TO REVISE THE WINDOW | | PRODUCT; CHANGING FROM THE TRACO COASTAL 240 IMPACT | | SINGLE HUNG TO ANOTHER PRODUCT.PLEASE SUBMIT PRODUCT | | APPROVALS.YOU SUBMITTED A LIST OF AAMA CERTIFICATIONS | | AND INSTALLATION INSTRUCTIONS.A FLORIDA STATE OR | | LOCAL PRODUCT APPROVAL, COMPLETE EVALUATION REPORT AND | | INSTALLATION INSTRUCTIONS ARE REQUIRED FAC9B72. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-06-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-06-21 |
Time |
12:56 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-06-21 |
Time |
12:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-03-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-03-20 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-03-20 |
Time |
08:43 |
Sent To |
|
|
Notes |
2007-03-20 08:58:32 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBEXISTING BUILDING CODE 2004 | | FBC R RESIDENTIAL 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | | | 1.)PROVIDE A ROOF FRAMING PLAN, FBC*106.3.5.SHOW | | THE SCOPE OF WORK.THE EXTENT OF DAMAGE IS NOT CLEAR. | | IT APPEARS THAT YOU ARE INSTALLING NEW ROOF FRAMING, | | BUT THE PLAN SHOWS THAT THE FIRST FLOOR HAS NO DAMAGE. | | IF THERE IS NO ROOF ON THE BUILDING, HOW HAS IT | | REMAINED DRY ON THE FIRST FLOOR WITH NO DAMAGE?IF YOU | | ARE NOT REPLACING ALL ROOF FRAMING, SHOW EXTENT OF THE | | REPAIRS ON A PLAN. | | | | 2.)DECLARE WIND DESIGN CRITERIA, FBC R 301.2 (WIND | | SPEED, EXPOSURE CATEGORY, DESIGN PRESSURE FOR | | COMPONENTS & CLADDING). | | | | 3.)PROVIDE OVERALL DIMENSIONS ON THE FLOOR PLAN. | | | | 4.)THERE IS A NOTE ON THE PLAN TO INCREASE WINDOW TO | | 24 ESCAPE.A 24 WINDOW DOES NOT COMPLY WITH EMERGENCY | | EGRESS REQUIREMENTS OF FBC310.1.HOWEVER, PLEASE SEE | | FBC EB 505.1.DESIGN INTENT IS NOT CLEAR. | | | | 5.)REVISED 4/27 - IMPACT PROTECTION REQUIRED FBC R | | 301.2.1.2.SEE ATTACHED POLICY IN REGARDS TO REMOVABLE | | SHUTTERS ON COMMERCIAL BUILDINGS.THIS IS NOT ALLOWED | | ON THE SECOND FLOOR.IF NONIMPACT GLASS WITH FIXED | | SHUTTERS ARE USED, A PLAN MUST BE SUBMITTED TO THE | | BUILDING OFFICIAL.PLEASE CONTACT ME IF YOU NEED | | ASSISTANCE WITH THIS ITEM. | | | | 6.)DECLARE GOVERNING CODE, INCLUDING FBC EB, AND | | DECLARE LEVEL OF ALTERATION FBC EB CHAPTER 3. | | | | 7.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER | | OF RECORD, FBC*106.3.3. | | | | 8.)SUBMIT PRODUCT APPROVALS FOR THE ROOF, SHUTTERS IF | | APPLICABLE, AND THE DOORS. | | | | 9.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | IN ADDITION TO THE NOAS SUBMITTED, FAC9B72. | | WWW.FLORIDABUILDING.ORG | | | | 10.)THE WINDOW AT THE TUB IS IN A HAZARDOUS LOCATION, | | FBC R308.4.NOTE SAFETY GLAZING REQUIREMENT ON THE | | PLAN. | | | | 11.)SHOW FIRE RESISTANCE REQUIREMENTS AND A DETAIL | | FOR PENETRATIONS FBC R317.1, FBC R317.3. | | | | 12.)ATTIC ACCESS REQUIRED FBC R807. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-02-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-02-07 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-02-07 |
Time |
11:31 |
Sent To |
|
|
Notes |
2007-02-07 11:35:03 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBEXISTING BUILDING CODE 2004 | | FBC R RESIDENTIAL 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | | | 1.)PROVIDE PLANS SHOWING ALL INFORMATION REQUIRED TO | | DETERMINE CODE COMPLIANCE, FBC106.1.1.ONLY A ROOF | | FRAMING SECTION WAS PROVIDED AND SOME PRODUCT | | APPROVALS.UNABLE TO PERFORM PLAN REVIEW DUE TO | | INSUFFICIENT INFORMATION ON THE PLANS. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-07-12 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-03 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-07-03 |
Time |
14:50 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-06-12 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-06-12 |
Time |
07:57 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2007-06-12 |
Time |
07:19 |
Sent To |
M |
|
Notes |
2007-06-12 07:57:00 | | | | | DENIED/INCOMPLETE INFORMATION | | | | 1} THERE MUST BE A DISCONNECTING MEANS FOR THE PANELS | | SHOWN PER 230.70(A)(1) AND 225.32, THE PANEL IS LISTED | | AS MAIN LUG ONLY. INDICATE IF THE PANEL IS AT THE | | SERVICE AND IF SO SHOW COMPLIANCE WITH THE ABOVE | | ARTICLES. | | | | 2} IF THE FIRST FLOOR IS INCLUDED IN THE ELECTRICAL | | WORK UNDER THIS PERMIT, PROVIDE A PANEL SCHEDULE PER | | 408.4 NEC 2005, ALSO CALCULATE THE ENTIRE SERVICE PER | | 220. | | | | 3} THERE ARE NONE OF THE REQUIREDGFI CIRCUITS (210.8) | | SHOWN ON THE FIRST FLOOR. PLEASE SHOW ONLY THE WORK TO | | BE DONE UNDER THIS PERMIT. | | | | THERE IS NO ELECTRICAL WORK INDICATED ON THE | | APPLICATION. CORRECT APPLICATION TO INCLUDE ALL WORK TO | | BE PERMITTED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-03-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-03-08 |
Time |
16:33 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2007-03-02 |
Time |
13:12 |
Sent To |
M |
|
Notes |
2007-03-08 16:32:58 | | | | | DENIED/INCOMPLETE INFORMATION | | | | 1} LOCATE THE PANEL ON THE PLAN, IF THERE IS NO PANEL | | ON THE2ND FLOOR, THEN THE PANEL SHOWN COULD NOT BE | | MLO AS INDICATED. | | | | 2} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW | | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE | | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | DISTINGUISHED FROM ALL OTHERS." SEE 210.52 FOR REQUIRED | | OUTLETS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-13 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-13 |
Time |
09:02 |
Sent To |
B |
|
Notes |
2007-12-13 09:02:28 | TO "SHILL" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2007-11-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-27 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-27 |
Time |
09:50 |
Sent To |
B |
|
Notes |
2007-11-27 09:50:41 | TO "SHILL" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-11-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-14 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-14 |
Time |
16:55 |
Sent To |
B |
|
Notes |
2007-11-14 16:55:28 | TO "SHILL' DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-06-25 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-25 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-25 |
Time |
16:53 |
Sent To |
E |
|
Notes |
2007-06-25 16:54:04 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-06-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-05 |
Time |
11:28 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-05 |
Time |
11:28 |
Sent To |
E |
|
Notes |
2007-06-05 11:30:01 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-02-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-28 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-28 |
Time |
16:42 |
Sent To |
E |
|
Notes |
2007-02-28 16:43:01 | TO "E" BOX--1ST REVIEW--CUSTOMER ONLY SUBMITTED PLANS | | FOR STRUCTURAL FIRST TIME AROUND. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-02-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-02-07 |
Time |
11:37 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-01-24 |
Time |
13:32 |
Sent To |
|
|
Notes |
2007-01-24 13:32:59 | TO "MISC" BOX#1 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-07-03 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-12 |
Time |
10:35 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-07-03 |
Time |
16:26 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-06-13 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-06-13 |
Time |
08:46 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-06-13 |
Time |
08:45 |
Sent To |
B |
|
Notes |
2007-06-13 08:51:11 | *** DENIED *** | | 1) PLEASE SHOW THE SIZE OF THE SUPPLY AIR DUCT TO BED | | ROOM #1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-03-09 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-03-09 |
Time |
16:25 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-03-09 |
Time |
16:25 |
Sent To |
B |
|
Notes |
2007-03-09 16:33:34 | *** DENIED *** | | 1) PLEASE SUBMIT DETAILED MANUFACTURER'S | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR AIR | | HANDLER AND 10 KW HEATER, AS A 10 KW HEATER APPEARS TO | | LARGE FOR A 1 1/2 TON AIR HANDLER. | | | | 2) PLEASE SHOW THE SIZE OF THE RETURN AIR TRANSFER | | GRILLS ON PLANS, SEE 2004 FBC/R M1602.4 (B). | | | | ***2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE | | ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | ACHIEVE PROPER RETURN AIR BALANCE. | | (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF | | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING | | THROUGH-THE-WALL TRANSFER GRILLES AND USING AN | | UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE | | PROPER RETURN AIR BALANCE | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | SHALL BE INCLUDED. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|