Plan Review Details - Permit 07011070
Plan Review Stops For Permit 07011070
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-12-28 Cont ID  
Sent By shill Date 2007-12-28 Time 09:58 Rev Time 0.00
Received By shill Date 2007-12-28 Time 09:58 Sent To  
Notes
2007-12-28 09:58:28REVISION (WINDOWS)

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-12-05 Cont ID  
Sent By shill Date 2007-12-05 Time 10:31 Rev Time 0.00
Received By shill Date 2007-12-05 Time 10:31 Sent To  
Notes
2007-12-05 10:42:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.NON IMPACT WINDOWS ARE NOT PERMITTED ON THE SECOND
 FLOOR.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-11-19 Cont ID  
Sent By shill Date 2007-11-19 Time 13:17 Rev Time 0.00
Received By shill Date 2007-11-19 Time 13:17 Sent To  
Notes
2007-11-19 13:19:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.IT APPEARS THAT YOU WOULD LIKE TO REVISE THE WINDOW
 PRODUCT; CHANGING FROM THE TRACO COASTAL 240 IMPACT
 SINGLE HUNG TO ANOTHER PRODUCT.PLEASE SUBMIT PRODUCT
 APPROVALS.YOU SUBMITTED A LIST OF AAMA CERTIFICATIONS
 AND INSTALLATION INSTRUCTIONS.A FLORIDA STATE OR
 LOCAL PRODUCT APPROVAL, COMPLETE EVALUATION REPORT AND
 INSTALLATION INSTRUCTIONS ARE REQUIRED FAC9B72.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-21 Cont ID  
Sent By shill Date 2007-06-21 Time 12:56 Rev Time 0.00
Received By shill Date 2007-06-21 Time 12:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-20 Cont ID  
Sent By shill Date 2007-03-20 Time 08:43 Rev Time 0.00
Received By shill Date 2007-03-20 Time 08:43 Sent To  
Notes
2007-03-20 08:58:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)PROVIDE A ROOF FRAMING PLAN, FBC*106.3.5.SHOW
 THE SCOPE OF WORK.THE EXTENT OF DAMAGE IS NOT CLEAR.
 IT APPEARS THAT YOU ARE INSTALLING NEW ROOF FRAMING,
 BUT THE PLAN SHOWS THAT THE FIRST FLOOR HAS NO DAMAGE.
 IF THERE IS NO ROOF ON THE BUILDING, HOW HAS IT
 REMAINED DRY ON THE FIRST FLOOR WITH NO DAMAGE?IF YOU
 ARE NOT REPLACING ALL ROOF FRAMING, SHOW EXTENT OF THE
 REPAIRS ON A PLAN.
  
 2.)DECLARE WIND DESIGN CRITERIA, FBC R 301.2 (WIND
 SPEED, EXPOSURE CATEGORY, DESIGN PRESSURE FOR
 COMPONENTS & CLADDING).
  
 3.)PROVIDE OVERALL DIMENSIONS ON THE FLOOR PLAN.
  
 4.)THERE IS A NOTE ON THE PLAN TO INCREASE WINDOW TO
 24 ESCAPE.A 24 WINDOW DOES NOT COMPLY WITH EMERGENCY
 EGRESS REQUIREMENTS OF FBC310.1.HOWEVER, PLEASE SEE
 FBC EB 505.1.DESIGN INTENT IS NOT CLEAR.
  
 5.)REVISED 4/27 - IMPACT PROTECTION REQUIRED FBC R
 301.2.1.2.SEE ATTACHED POLICY IN REGARDS TO REMOVABLE
 SHUTTERS ON COMMERCIAL BUILDINGS.THIS IS NOT ALLOWED
 ON THE SECOND FLOOR.IF NONIMPACT GLASS WITH FIXED
 SHUTTERS ARE USED, A PLAN MUST BE SUBMITTED TO THE
 BUILDING OFFICIAL.PLEASE CONTACT ME IF YOU NEED
 ASSISTANCE WITH THIS ITEM.
  
 6.)DECLARE GOVERNING CODE, INCLUDING FBC EB, AND
 DECLARE LEVEL OF ALTERATION FBC EB CHAPTER 3.
  
 7.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 8.)SUBMIT PRODUCT APPROVALS FOR THE ROOF, SHUTTERS IF
 APPLICABLE, AND THE DOORS.
  
 9.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE NOAS SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 10.)THE WINDOW AT THE TUB IS IN A HAZARDOUS LOCATION,
 FBC R308.4.NOTE SAFETY GLAZING REQUIREMENT ON THE
 PLAN.
  
 11.)SHOW FIRE RESISTANCE REQUIREMENTS AND A DETAIL
 FOR PENETRATIONS FBC R317.1, FBC R317.3.
  
 12.)ATTIC ACCESS REQUIRED FBC R807.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-07 Cont ID  
Sent By shill Date 2007-02-07 Time 11:31 Rev Time 0.00
Received By shill Date 2007-02-07 Time 11:31 Sent To  
Notes
2007-02-07 11:35:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBEXISTING BUILDING CODE 2004
 FBC R RESIDENTIAL 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)PROVIDE PLANS SHOWING ALL INFORMATION REQUIRED TO
 DETERMINE CODE COMPLIANCE, FBC106.1.1.ONLY A ROOF
 FRAMING SECTION WAS PROVIDED AND SOME PRODUCT
 APPROVALS.UNABLE TO PERFORM PLAN REVIEW DUE TO
 INSUFFICIENT INFORMATION ON THE PLANS.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-12 Cont ID  
Sent By btrobaug Date 2007-07-03 Time 15:15 Rev Time 0.00
Received By btrobaug Date 2007-07-03 Time 14:50 Sent To M
Notes
2007-07-03 15:05:22 
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-12 Cont ID  
Sent By btrobaug Date 2007-06-12 Time 07:57 Rev Time 0.50
Received By btrobaug Date 2007-06-12 Time 07:19 Sent To M
Notes
2007-06-12 07:57:00 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THERE MUST BE A DISCONNECTING MEANS FOR THE PANELS
 SHOWN PER 230.70(A)(1) AND 225.32, THE PANEL IS LISTED
 AS MAIN LUG ONLY. INDICATE IF THE PANEL IS AT THE
 SERVICE AND IF SO SHOW COMPLIANCE WITH THE ABOVE
 ARTICLES.
  
 2} IF THE FIRST FLOOR IS INCLUDED IN THE ELECTRICAL
 WORK UNDER THIS PERMIT, PROVIDE A PANEL SCHEDULE PER
 408.4 NEC 2005, ALSO CALCULATE THE ENTIRE SERVICE PER
 220.
  
 3} THERE ARE NONE OF THE REQUIREDGFI CIRCUITS (210.8)
 SHOWN ON THE FIRST FLOOR. PLEASE SHOW ONLY THE WORK TO
 BE DONE UNDER THIS PERMIT.
  
 THERE IS NO ELECTRICAL WORK INDICATED ON THE
 APPLICATION. CORRECT APPLICATION TO INCLUDE ALL WORK TO
 BE PERMITTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-08 Cont ID  
Sent By btrobaug Date 2007-03-08 Time 16:33 Rev Time 0.50
Received By btrobaug Date 2007-03-02 Time 13:12 Sent To M
Notes
2007-03-08 16:32:58 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} LOCATE THE PANEL ON THE PLAN, IF THERE IS NO PANEL
 ON THE2ND FLOOR, THEN THE PANEL SHOWN COULD NOT BE
 MLO AS INDICATED.
  
 2} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS." SEE 210.52 FOR REQUIRED
 OUTLETS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 09:02 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 09:02 Sent To B
Notes
2007-12-13 09:02:28TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 09:50 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 09:50 Sent To B
Notes
2007-11-27 09:50:41TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-14 Cont ID  
Sent By adarroug Date 2007-11-14 Time 16:55 Rev Time 0.00
Received By adarroug Date 2007-11-14 Time 16:55 Sent To B
Notes
2007-11-14 16:55:28TO "SHILL' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-25 Cont ID  
Sent By adarroug Date 2007-06-25 Time 16:53 Rev Time 0.00
Received By adarroug Date 2007-06-25 Time 16:53 Sent To E
Notes
2007-06-25 16:54:04TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-05 Cont ID  
Sent By adarroug Date 2007-06-05 Time 11:28 Rev Time 0.00
Received By adarroug Date 2007-06-05 Time 11:28 Sent To E
Notes
2007-06-05 11:30:01TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-28 Cont ID  
Sent By adarroug Date 2007-02-28 Time 16:42 Rev Time 0.00
Received By adarroug Date 2007-02-28 Time 16:42 Sent To E
Notes
2007-02-28 16:43:01TO "E" BOX--1ST REVIEW--CUSTOMER ONLY SUBMITTED PLANS
 FOR STRUCTURAL FIRST TIME AROUND.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-07 Cont ID  
Sent By shill Date 2007-02-07 Time 11:37 Rev Time 0.00
Received By shill Date 2007-01-24 Time 13:32 Sent To  
Notes
2007-01-24 13:32:59TO "MISC" BOX#1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-03 Cont ID  
Sent By btrobaug Date 2007-07-12 Time 10:35 Rev Time 0.25
Received By tgordon Date 2007-07-03 Time 16:26 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-13 Cont ID  
Sent By tgordon Date 2007-06-13 Time 08:46 Rev Time 0.25
Received By tgordon Date 2007-06-13 Time 08:45 Sent To B
Notes
2007-06-13 08:51:11*** DENIED ***
 1) PLEASE SHOW THE SIZE OF THE SUPPLY AIR DUCT TO BED
 ROOM #1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By tgordon Date 2007-03-09 Time 16:25 Rev Time 0.25
Received By tgordon Date 2007-03-09 Time 16:25 Sent To B
Notes
2007-03-09 16:33:34*** DENIED ***
 1) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR AIR
 HANDLER AND 10 KW HEATER, AS A 10 KW HEATER APPEARS TO
 LARGE FOR A 1 1/2 TON AIR HANDLER.
  
 2) PLEASE SHOW THE SIZE OF THE RETURN AIR TRANSFER
 GRILLS ON PLANS, SEE 2004 FBC/R M1602.4 (B).
  
 ***2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.