Plan Review Details - Permit 07011043
Plan Review Stops For Permit 07011043
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-09 Cont ID  
Sent By jwitmer Date 2007-04-09 Time 14:17 Rev Time 1.22
Received By jwitmer Date 2007-04-09 Time 14:17 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By jwitmer Date 2007-01-30 Time 10:48 Rev Time 0.55
Received By jwitmer Date 2007-01-30 Time 10:47 Sent To  
Notes
2007-01-30 10:59:38PERMIT: 07011043
 ADD: 444 W RAILROAD AVSUITE# 470
 CONT:PBM DEVELOPMENT
 TEL: (561)715-1800
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PBM DEVELOPMENT REQUIES A CERTIFICATE OF
 AUTHORIZATION.
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) SHEET A-03 & A-04 BOTH INDICATE DRAWN TO 1/4" SCALE
 WHEREAS THEY ARE DRAWN TO
 ACTUAL 3/8" SCALE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-04-24 Cont ID  
Sent By dpalmer Date 2007-04-24 Time 09:10 Rev Time 0.00
Received By dpalmer Date 2007-04-24 Time 08:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-12 Cont ID  
Sent By dpalmer Date 2007-04-12 Time 17:01 Rev Time 0.00
Received By dpalmer Date 2007-04-12 Time 16:59 Sent To  
Notes
2007-04-12 17:01:35** UNSAT **
  
 1) NOTE: PLEASE SEE THE NEW REVISED ENERGY CALCULATIONS
 ARE NOT SEALED BY THE ENGINEER OF RECORD AS REQUIRED
 PER 13-103.1.1.1
 PLEASE SUBMIT SIGNED, DATED AND SEALED. FS 471.025
  
 2) NOTE: PLEASE SEE THE NUMBER OF*B* FIXTURES ON
 PLANS DO NOT CORRELATE WITH THE NUMBER OF FIXTURES ON
 ENERGY CALCULATIONS. PLEASE ADJUST PLANS, OR ENERGY
 CALCULATIONS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-04 Cont ID  
Sent By dpalmer Date 2007-04-04 Time 15:07 Rev Time 0.00
Received By dpalmer Date 2007-04-04 Time 15:05 Sent To  
Notes
2007-04-04 15:07:20** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW. THE
 ENERGY CALCULATIONS AND/OR PERFORMANCE DENSITIES WERE
 NOT SHOWN IN COMPLIANCE. PLEASE SEE THE TYPE, AND
 AMOUNT OF FIXTURES, WATTAGE(S) ETC AS SHOWN ON PLANS DO
 NOT CORRELATE WITH THE ENERGY CALCULATIONS SUBMITTED.
 PLEASE ADJUST AND REVISE 13-415.1.AB.1.1, 13-415.2
 PLEASE SEE THE METHOD OF CONTROL FOR LIGHTING ON ENERGY
 CALCULATIONS NEEDS TO CORRELATE WITH PLANS.
 (AUTOMATED/OCCUPANCY/TIMERS ETC).
  
 2) NOTE: PLEASE SEE THAT NO HAND DRAWN CHANGES ARE
 PERMITTED ON PLANS.
 PLEASE BE SURE TO STATE THE MAXIMUM TIMES FOR OCCUPANCY
 TYPE DEVICES ON PLANS AND ANY ITEMS WIRED AHEAD OF
 LOCAL LIGHTING 700.12E
 13-415.1.ABC.1.1
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-25 Cont ID  
Sent By dpalmer Date 2007-01-25 Time 09:36 Rev Time 0.00
Received By dpalmer Date 2007-01-25 Time 08:57 Sent To  
Notes
2007-01-25 09:37:45** UNSAT **
  
  
 1) NOTE: PLEASE SEE MISSING ADDRESS INFORMATION FROM
 TITLE BLOCKS. PLEASE SEE THE SUITE/UNIT NUMBER IS BEING
 SHOWN, HOWEVER NOT THE ADDRESS/ LOCATION.
 FAC 61G1-16.004, FAC61G15-23.002
 PLEASE SEE THE ADDRESS OF THE PROJECT IS MISSING FROM
 TITLE BLOCKS. THE SUITE # OF 470 IS OK FOR SUITE, NEEDS
 ADDRESS OF 444 RAILROAD AVE.
  
 2) NOTE: PLEASE SEE MISSING COMPLETE INFORMATION FOR A
 TITLE BLOCK FOR THE ARCHITECT OF RECORD. PLEASE SEE
 ATTACHED SHEET FROM DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. PLEASE SEE NO ADDRESS
 INFORMATION ETC.
 PLEASE KNOW IF WORKING THROUGH PBM DEVELOPMENT, AND PBM
 IS OFFERING ARCHITECTURAL SERVICES, THEN PBM WOULD BE
 REQUIRED TO LIST THEIR CERTIFICATE OF AUTHORIZATION
 NUMBER. (THIS HAS ALREADY BEEN GONE OVER WITH STAFF
 FROM PBM AND IT IS OUR UNDERSTANDING THAT APPLICATION
 TO THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATIONS HAS/IS TAKING OR TAKEN PLACE.
 PLEASE KNOW IF PERMIT ISSUANCE IS DOWN TO ONLY THIS
 COMMENT AND THE CERTIFICATE OF AUTHORIZATION NUMBER HAS
 NOT YET BEEN ISSUED FROM THE STATE, THE TITLE BLOCKS
 WOULD BE REVISED TO BE LISTED WITH THE ARCHITECT ONLY.
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004, FLORIDA
 STATUTES 481.219
 **THIS IS NOT A COMMENT RELATED TO KAMM CONSULTING,
 HOWEVER TITLE BLOCKS ARE REQUIRED FOR ALL SHEETS PER
 ABOVE AND WHETHER OR NOT COMMENT IS MADE BY ANY OTHER
 TRADE.
  
 3) NOTE: PLEASE LIST THE FOLLOWING MINIMUM CODES
 RELEVANT TO THIS PROJECT AND DESIGN.
 2002 NFPA-72, 2005 NFPA-70, 2003 NFPA-101
 PLEASE SEE AS THE PERMIT WAS APPLIED FOR ON OR AFTER
 DECEMBER 8TH, 2006 THE 2006 REVISIONS TO THE 2004 FBC
 AND THE 2005 NATIONAL ELECTRICAL CODE WAS ADOPTED BY
 THE STATE OF FLORIDA.
 PLEASE ADJUST CODES ON PLANS.
  
 4) NOTE: PLEASE SEE MISSING LIGHTING CONTROL FOR ALL
 PER 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 MISSING CONTROLS FOR COMMON AREAS. PLEASE SEE OVER
 RIDES DEVICES FOR THESE AREAS ALSO DEPENDING ON
 "SYSTEM" OR DEVICES CHOSEN. PLEASE SEE THE SYMBOL
 LEGEND FOR ALL DEVICES SHALL INDICATE ALL MAXIMUM TIMES
 FOR DEVICES. (30MINS FOR OCCUPANCY SENSOR TYPE AND 4HRS
 MAX FOR TIMER TYPE)
 PLEASE PROVIDE SCHEDULING FOR ANY PROPOSED SYSTEM.
 PLEASE SEE ALL AREAS CONTAIN FLOOR TO CEILING HEIGHT
 PARTITIONS SHALL CONTAIN DEVICE(S) FOR CONTROL. (PLEASE
 SEE STORAGE)
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR MISSING MAXIMUM
 PERMITTED LIGHTING POWER DENSITIES.
 PLEASE ALSO SEE 13-415.AB.1 FOR MISSING ENERGY
 CALCULATIONS REQUIRED FOR NEW TENANT BUILD-OUT.
 PERFORMANCE CALCULATIONS PER 13-415.2
 ** PLEASE SUBMIT THE ABOVE. AS THERE ARE ITEMS NOT YET
 SUBMITTED, A REVIEW OF SAID SYSTEM/DEVICES ETC CAN NOT
 BE FULLY ACCOMPLISHED AT THIS TIME.
  
 5) NOTE: PLEASE PROVIDE A DETAIL ON ALL EMERGENCY
 AND/OR EXIT LIGHTING WIRED AHEAD OF ANY OVER RIDE
 CONTROL DEVICES PER 700.12E. PLEASE SEE A
 CLOUDED/HIGHLIGHTED NOTE MAY ALSO BE DONE. THIS AHJ HAS
 BEEN HAVING MANY INSTANCES WHERE EMERGENCY AND EXIT
 LIGHTS ARE BEING WIRED ON THE LOAD SIDE OF OC/ TIMER
 DEVICES.
  
 6) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE KNOW EITHER AT THIS POINT OR BEFORE
 FINAL, A REVISION FOR ALL CIRCUITS TO SPECIFIC ROOMS
 AND AREAS WILL BE REQUIRED. (LIGHTING CIRCUITS ETC.)
 408.4.
 ALL RECEPTACLE CIRCUITS ARE OK AS SHOWN.
  
 8) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW INSTA-HOT TANKLESS WATER HEATER.
 PLEASE SEE PLUMBING REVIEW COMMENTS FOR THIS AND PLEASE
 BE SURE A LISTING FROM A NRTL IS ON PLANS.
  
 9) NOTE: PLEASE CLARIFY HOW THE PANEL SCHEDULE(S)
 INDICATE ALL THE CIRCUITS AS EXISTING FOR ALL THESE
 SPACES WHICH HAVE YET TO BE PERMITTED. PLEASE INDICATE
 NEW CIRCUITING AND WHAT?S EXISTING. PLEASE SEE THAT NO
 OTHER TENANT BUILD OUTS HAVE BEEN PERMITTED AT THIS
 TIME.
  
 10) NOTE:** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDEDSHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.PLEASE KNOW ONLY
 ONE SET OF THE OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-16 Cont ID  
Sent By mawillia Date 2007-04-16 Time 13:55 Rev Time 0.00
Received By mawillia Date 2007-04-16 Time 13:43 Sent To  
Notes
2007-04-16 13:55:04*****APPROVED*****
  
  
 PLAN SHEETS LS-01, E2.1, FA2.1 AND FS2.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-04-04 Cont ID  
Sent By mawillia Date 2007-04-04 Time 17:38 Rev Time 0.00
Received By mawillia Date 2007-04-04 Time 17:34 Sent To  
Notes
2007-04-04 17:38:41*****APPROVED*****
  
  
  
 ALL COMMENTS FROM THE 02/06/07 FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;THE APPROPIATE PLAN SHEET(S) TO BE
 STAMPED WHEN ALL OTHER PLAN REVIEWS HAVE BEEN
 SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By mawillia Date 2007-02-06 Time 13:20 Rev Time 0.00
Received By mawillia Date 2007-02-06 Time 13:20 Sent To  
Notes
2007-02-06 13:20:57*****DENIED*****
  
  
 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 05.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO
 THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON
 THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT.
  
 06.DOOR(S) LEADING DIRECTLY TO THE FOURTH FLOOR
 CORRIDOR SHALL BE AN APPROVED, LISTED, AND LABELED FIRE
 DOOR & ASSEMBLY IN ACCORDANCE WITH THE REQUIREMENTS OF
 NFPA 80.
  
 07.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS?
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS
 SHEET, INDICATE THE LOCATION OFFIRE EXTINGUISHER(S)
 AT DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 09.ON SHEET FA0.1, FIRE ALARM NOTE #17 SHOULD BE
 CHANGED TO "INITIATE A GENERAL FIRE ALARM".
  
 10.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR
 THIS TENANT SPACE.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED ON THE PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 09:30 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 09:30 Sent To E
Notes
2007-04-23 09:30:33TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-11 Cont ID  
Sent By adarroug Date 2007-04-11 Time 15:19 Rev Time 0.00
Received By adarroug Date 2007-04-11 Time 15:19 Sent To  
Notes
2007-04-11 15:20:32TO "BOB"#17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 18:47 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 18:47 Sent To  
Notes
2007-04-03 17:33:21TO BOB # 15
2007-03-30 18:47:29WAITING FOR BOB BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-06 Cont ID  
Sent By mawillia Date 2007-02-06 Time 13:24 Rev Time 0.00
Received By mawillia Date 2007-01-23 Time 13:38 Sent To  
Notes
2007-01-24 09:40:01TO "BOB"#2
2007-01-23 13:38:46WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-04-04 Cont ID  
Sent By tgordon Date 2007-04-04 Time 16:25 Rev Time 0.20
Received By tgordon Date 2007-04-04 Time 16:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-25 Cont ID  
Sent By tgordon Date 2007-01-25 Time 15:53 Rev Time 0.35
Received By tgordon Date 2007-01-25 Time 15:53 Sent To  
Notes
2007-01-25 16:08:03*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES #1 AND 2, PLEASE
 CORRECT.
  
 2)PAGES A-05 AND A-08 SHOW THE SPACE ABOVE THE
 ACCOUSTIC TILE CEILING TO BE AN OPEN PLENUM AND WOULD
 NOT REQUIRE RETURN AIR TRANSFER DUCTS, IF THIS IS SO
 PLEASE DO NOT SHOW RETURN AIR TRANSFER DUCTS ON PAGE
 M-2.1. IF NOT AN OPEN PLENUM RETURN AIR TRANSFER DUCTS
 ARE UNDER-SIZED. BALANCED RETURN AIR MAY BE ACHIEVED
 BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE. PER 2004 FBC/M 601.4. PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-04 Cont ID  
Sent By jleech Date 2007-04-04 Time 10:07 Rev Time 0.00
Received By jleech Date 2007-04-04 Time 10:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-03 Cont ID  
Sent By jleech Date 2007-02-03 Time 07:48 Rev Time 0.00
Received By jleech Date 2007-02-03 Time 07:48 Sent To  
Notes
2007-02-03 07:58:25DENIED;
 1. SEE ELECTRICAL PLAN REVIEW NOTES #1 AND #2.
 2. PAGE M2.1 A.C. DUCT PLAN SHOWS THE AREA ABOVE THE
 DROPED CEILING IS BEING USED AS A PLENUM. PLEASE CHANGE
 PLUMBING NOTE #11 ON PAGE P0.1. PIPING MATERIAL THAT
 CAN BE USED IS CAST IRON OR COPPER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695