Plan Review Stops For Permit 07011041 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-04-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-04-09 |
Time |
14:19 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2007-04-09 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-02-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-02-05 |
Time |
16:14 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2007-02-05 |
Time |
16:05 |
Sent To |
|
|
Notes |
2007-02-05 16:15:42 | PERMIT: 07011041 | | ADD: 444 W RAILROAD AVSUITE# 430 | | CONT:PBM DEVELOPMENT | | TEL: (561)715-1800 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC AMENDMENTS(REVISIONS) | | * WEST PALM BEACH AMENDMENTS | | | | 1STREVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) PBM DEVELOPMENT REQUIES A CERTIFICATE OF | | AUTHORIZATION. | | 481.219 F.S.CERTIFICATE OF | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | SHEET BEARING THE NAME OF AN ARCHITECT | | PRACTICING UNDER A FICTITIOUS NAME, A | | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL | | SERVICES, SHALL INCLUDE | | THE CERTIFICATE OF AUTHORIZATION | | NUMBER.ADD THE NUMBER TO EACH SHEET. | | THIS MAY BE ADDED BY HAND. | | | | 3) 110.2* W. P. B. ADMINISTRATIVE | | CODE, INFORMATION THAT IS REQUIRED FOR | | RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH | | THE PERMIT WAS ISSUED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | WITH THE PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | IN CHAPTER 6, TABLE 601, THIS IS FOR THE COMPLETE | | BUILDING!. | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | IS REQUIRED. | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | OF THE BUILDING PERMIT. | | F ) SQ. FT. FOOTPRINT | | G) SQ. FT. UNDER ROOF (TOTAL) | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2007-05-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-05-01 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-05-01 |
Time |
11:33 |
Sent To |
PC |
|
Notes |
2007-05-01 11:34:07 | NEW SHEET 2.1 BROUGHT IN.OK , SAME AS PREVIOUS P2.1 | | STAMPED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-04-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-24 |
Time |
12:24 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-24 |
Time |
10:26 |
Sent To |
PC |
|
Notes |
2007-04-24 12:44:02 | NEEDS NEW SHEET P2.1, AS IT WAS NOT SIGNED IN ONE SET. | | FS 471.025 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-04-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-12 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-12 |
Time |
09:00 |
Sent To |
|
|
Notes |
2007-04-12 09:39:34 | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE THE NEW REVISED ENERGY CALCULATIONS | | ARE NOT SEALED BY THE ENGINEER OF RECORD AS REQUIRED | | PER 13-103.1.1.1 | | PLEASE SUBMIT SIGNED, DATED AND SEALED. FS 471.025 | | | | 2) NOTE: PLEASE SEE THE NUMBER OF*B* FIXTURES ON | | PLANS DO NOT CORRELATE WITH THE NUMBER OF FIXTURES ON | | ENERGY CALCULATIONS. PLEASE ADJUST PLANS, OR ENERGY | | CALCULATIONS. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-04-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-04 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-04 |
Time |
14:39 |
Sent To |
|
|
Notes |
2007-04-04 14:43:37 | | | ** UNSAT 2ND REVIEW ** | | | | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW. THE | | ENERGY CALCULATIONS AND/OR PERFORMANCE DENSITIES WERE | | NOT SHOWN IN COMPLIANCE. PLEASE SEE THE TYPE, AND | | AMOUNT OF FIXTURES, WATTAGE(S) ETC AS SHOWN ON PLANS DO | | NOT CORRELATE WITH THE ENERGY CALCULATIONS SUBMITTED. | | PLEASE ADJUST AND REVISE 13-415.1.AB.1.1, 13-415.2 | | PLEASE SEE THE METHOD OF CONTROL FOR LIGHTING ON ENERGY | | CALCULATIONS NEEDS TO CORRELATE WITH PLANS. | | (AUTOMATED/OCCUPANCY/TIMERS ETC). | | | | 2) NOTE: PLEASE SEE THAT NO HAND DRAWN CHANGES ARE | | PERMITTED ON PLANS. | | PLEASE BE SURE TO STATE THE MAXIMUM TIMES FOR OCCUPANCY | | TYPE DEVICES ON PLANS. | | 13-415.1.ABC.1.1 | | | | 3) NOTE: PLEASE SEE THE REQUIRED LICENSE NUMBER FOR | | FIRM IS MISSING FROM SEVERAL SHEETS IN BOTH SETS OF | | PLANS. THIS IS NOT ONLY REQUIRED ON ONE SHEET, THIS IS | | REQUIRED FOR EVERY SHEET WHICH CONTAINS THE SAID TITLE | | BLOCK FOR FIRM. (PBM). FS 481.219, FAC 61G1-16.004 THIS | | IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER | | TRADES. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-02-01 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-02-01 |
Time |
17:25 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2007-02-01 |
Time |
16:06 |
Sent To |
|
|
Notes |
2007-02-01 17:25:18 | | | | | DENIED/INCOMPLETE INFORMATION | | | | 1} PLEASE SHOW COMPLIANCE WITH CHAPTER 13 OF THE | | FLORIDA BUILDING CODE. SPECIFICALLY 13-415, FOR THE | | PURPOSE OF THIS REVIEW. LOCATE ALL DEVICES NEEDED FOR | | COMPLIANCE ON THE PLAN. SUBMIT CALCULATIONS AND | | INDICATE METHOD ON APPROPRIATE FORM. | | | | 2} SHEET E0-1, ELECTRICAL SPECIFICATIONS. THE CODE | | ARTICLES INCORRECTLY REFERENCES THE 2002 NEC. THE 2005 | | WAS ADOPTED EFFECTIVE 12/8/06. PLEASE CHANGE THIS TO | | ELIMINATE ANY CONFUSION IN THE FIELD. | | | | 3} SHEET E3.1, CIRCUIT L4C-8 IS AT THE COPIER.THE PANEL | | SCHEDULE LISTS THIS CIRCUIT AS A PRINTER. | | | | 4} PLEASE CORRECT THE BUILDING ADDRESS ON THE PLANS TO | | READ 444 W. RAILROAD AVENUE, AS THERE ARE TWO BUILDINGS | | AT 3RD AND WEST RAILROAD AVENUE.LEAVE THE SUITE NUMBER | | FOR CLARITY. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-04-16 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-04-16 |
Time |
13:03 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-04-16 |
Time |
12:54 |
Sent To |
|
|
Notes |
2007-04-16 13:01:23 | *****APPROVED***** | | | | | | PLAN SHEETS LS-01, E2.1, FA2.1 AND FS2.1 WERE STAMPED, | | INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2007-04-04 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-04-04 |
Time |
17:32 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-04-04 |
Time |
17:27 |
Sent To |
|
|
Notes |
2007-04-04 17:32:15 | *****APPROVED***** | | | | | | | | ALL COMMENTS FROM THE 02/06/07 FIRE PLAN REVIEW HAVE | | BEEN ADDRESSED;THE APPRPIATE PLAN SHEET(S) TO BE | | STAMPED WHEN ALL OTHER PLAN REVIEWS HAVE BEEN | | SATISFIED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-02-06 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-02-06 |
Time |
12:39 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-02-06 |
Time |
12:39 |
Sent To |
|
|
Notes |
2007-02-06 12:43:16 | *****DENIED***** | | | | | | 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | | 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 04.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK | | WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | 05.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO | | THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON | | THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS | | SHALL BE NO LESS THAN 3" IN HEIGHT. | | | | 06.DOOR(S) LEADING DIRECTLY TO THE FOURTH FLOOR | | CORRIDOR SHALL BE AN APPROVED, LISTED, AND LABELED FIRE | | DOOR & ASSEMBLY IN ACCORDANCE WITH THE REQUIREMENTS OF | | NFPA 80. | | | | 07.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE | | WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, | | AND IN ALL OTHER AREAS? | | | | 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES | | THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS | | SHEET, INDICATE THE LOCATION OFFIRE EXTINGUISHER(S) | | AT DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE | | REQUIREMENT. | | | | 09.ON SHEET FA0.1, FIRE ALARM NOTE #17 SHOULD BE | | CHANGED TO "INITIATE A GENERAL FIRE ALARM". | | | | 10.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR | | THIS TENANT SPACE. | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | ITEM WAS ADDRESSED ON THE PLAN. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-04-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-23 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-23 |
Time |
10:03 |
Sent To |
E |
|
Notes |
2007-04-23 10:03:53 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-04-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-11 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-11 |
Time |
14:59 |
Sent To |
|
|
Notes |
2007-04-11 14:59:26 | TO "BOB"#15 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-03-30 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2007-03-30 |
Time |
18:45 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2007-03-30 |
Time |
18:45 |
Sent To |
|
|
Notes |
2007-04-03 17:31:50 | TO BOB # 13 | 2007-03-30 18:45:54 | WAITING FOR BOB BOARD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-02-09 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-02-09 |
Time |
08:35 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-02-05 |
Time |
10:57 |
Sent To |
|
|
Notes |
2007-02-05 10:59:13 | TO" BOB"#9--APPL TAKEN OUT OF IN-COMING BEFORE THE | | ROUTING PROCESS |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-04-04 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-04-04 |
Time |
15:41 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-04-04 |
Time |
15:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-02-08 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-02-08 |
Time |
13:39 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2007-02-08 |
Time |
13:39 |
Sent To |
|
|
Notes |
2007-02-08 13:54:16 | *** DENIED *** | | 1) SEE BUILDING REVIEW NOTE #2, PLEASE CORRECT. | | | | 2) PLEASE CORRECT JOB ADDRESS IN TITLE BLOCK (444 W. | | RAILROAD AVE. SUITE 430). | | | | 3) BE ADVISED A NOTICE OF COMMENCEMENT WILL NEED TO BE | | FILED AS THIS PERMIT 07011041 FOR TENANT IMPROVEMENT IS | | NOT IN THE SCOPE OF PERMIT 04042022 WHICH CAN NOT BE | | USED AS A MASTER PERMIT, PER ROBERT BROWN SERVICES | | MANAGER. | | | | 4) THE RETURN AIR TRANSFER DUCTS TO OFFICES 1, 2, 3, 4, | | AND CONFERENCE ROOM ARE UNDER-SIZED. BALANCED RETURN | | AIR MAY BE ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | ACHIEVE PROPER RETURN AIR BALANCE. PER 2004 FBC/R | | M1602.4 . PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2007-04-04 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-04-04 |
Time |
07:53 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-04-04 |
Time |
07:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-02-09 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-02-09 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-02-09 |
Time |
08:24 |
Sent To |
|
|
Notes |
2007-02-09 08:34:44 | DENIED; | | 1. CHANGE NOTE 11 ,PAGE P0.1 PLUMBING NOTES. DELETE PVC | | AS A TYPE OF PIPE THAT CAN BE USED SINCE THE AREA ABOVE | | THE DROPPED CEILING IS A PLENUM. | | 2. WATER HAMMER ARRESTORS SHALL BE INSTALLED PER | | MANUFACTURE'S INSTALLATION INSTRUCTIONS, AS CLOSE TO | | THE SOURSE AS POSSIBLE. SECTION 604.9 | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|