Plan Review Details - Permit 07011041
Plan Review Stops For Permit 07011041
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-09 Cont ID  
Sent By jwitmer Date 2007-04-09 Time 14:19 Rev Time 0.77
Received By jwitmer Date 2007-04-09 Time 14:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-05 Cont ID  
Sent By jwitmer Date 2007-02-05 Time 16:14 Rev Time 2.22
Received By jwitmer Date 2007-02-05 Time 16:05 Sent To  
Notes
2007-02-05 16:15:42PERMIT: 07011041
 ADD: 444 W RAILROAD AVSUITE# 430
 CONT:PBM DEVELOPMENT
 TEL: (561)715-1800
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC AMENDMENTS(REVISIONS)
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PBM DEVELOPMENT REQUIES A CERTIFICATE OF
 AUTHORIZATION.
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601, THIS IS FOR THE COMPLETE
 BUILDING!.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 F ) SQ. FT. FOOTPRINT
 G) SQ. FT. UNDER ROOF (TOTAL)
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-05-01 Cont ID  
Sent By dpalmer Date 2007-05-01 Time 11:33 Rev Time 0.00
Received By dpalmer Date 2007-05-01 Time 11:33 Sent To PC
Notes
2007-05-01 11:34:07NEW SHEET 2.1 BROUGHT IN.OK , SAME AS PREVIOUS P2.1
 STAMPED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-04-24 Cont ID  
Sent By dpalmer Date 2007-04-24 Time 12:24 Rev Time 0.00
Received By dpalmer Date 2007-04-24 Time 10:26 Sent To PC
Notes
2007-04-24 12:44:02NEEDS NEW SHEET P2.1, AS IT WAS NOT SIGNED IN ONE SET.
 FS 471.025

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-12 Cont ID  
Sent By dpalmer Date 2007-04-12 Time 09:39 Rev Time 0.00
Received By dpalmer Date 2007-04-12 Time 09:00 Sent To  
Notes
2007-04-12 09:39:34** UNSAT **
  
 1) NOTE: PLEASE SEE THE NEW REVISED ENERGY CALCULATIONS
 ARE NOT SEALED BY THE ENGINEER OF RECORD AS REQUIRED
 PER 13-103.1.1.1
 PLEASE SUBMIT SIGNED, DATED AND SEALED. FS 471.025
  
 2) NOTE: PLEASE SEE THE NUMBER OF*B* FIXTURES ON
 PLANS DO NOT CORRELATE WITH THE NUMBER OF FIXTURES ON
 ENERGY CALCULATIONS. PLEASE ADJUST PLANS, OR ENERGY
 CALCULATIONS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-04-04 Cont ID  
Sent By dpalmer Date 2007-04-04 Time 14:41 Rev Time 0.00
Received By dpalmer Date 2007-04-04 Time 14:39 Sent To  
Notes
2007-04-04 14:43:37 
 ** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW. THE
 ENERGY CALCULATIONS AND/OR PERFORMANCE DENSITIES WERE
 NOT SHOWN IN COMPLIANCE. PLEASE SEE THE TYPE, AND
 AMOUNT OF FIXTURES, WATTAGE(S) ETC AS SHOWN ON PLANS DO
 NOT CORRELATE WITH THE ENERGY CALCULATIONS SUBMITTED.
 PLEASE ADJUST AND REVISE 13-415.1.AB.1.1, 13-415.2
 PLEASE SEE THE METHOD OF CONTROL FOR LIGHTING ON ENERGY
 CALCULATIONS NEEDS TO CORRELATE WITH PLANS.
 (AUTOMATED/OCCUPANCY/TIMERS ETC).
  
 2) NOTE: PLEASE SEE THAT NO HAND DRAWN CHANGES ARE
 PERMITTED ON PLANS.
 PLEASE BE SURE TO STATE THE MAXIMUM TIMES FOR OCCUPANCY
 TYPE DEVICES ON PLANS.
 13-415.1.ABC.1.1
  
 3) NOTE: PLEASE SEE THE REQUIRED LICENSE NUMBER FOR
 FIRM IS MISSING FROM SEVERAL SHEETS IN BOTH SETS OF
 PLANS. THIS IS NOT ONLY REQUIRED ON ONE SHEET, THIS IS
 REQUIRED FOR EVERY SHEET WHICH CONTAINS THE SAID TITLE
 BLOCK FOR FIRM. (PBM). FS 481.219, FAC 61G1-16.004 THIS
 IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-01 Cont ID  
Sent By btrobaug Date 2007-02-01 Time 17:25 Rev Time 1.00
Received By btrobaug Date 2007-02-01 Time 16:06 Sent To  
Notes
2007-02-01 17:25:18 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE SHOW COMPLIANCE WITH CHAPTER 13 OF THE
 FLORIDA BUILDING CODE. SPECIFICALLY 13-415, FOR THE
 PURPOSE OF THIS REVIEW. LOCATE ALL DEVICES NEEDED FOR
 COMPLIANCE ON THE PLAN. SUBMIT CALCULATIONS AND
 INDICATE METHOD ON APPROPRIATE FORM.
  
 2} SHEET E0-1, ELECTRICAL SPECIFICATIONS. THE CODE
 ARTICLES INCORRECTLY REFERENCES THE 2002 NEC. THE 2005
 WAS ADOPTED EFFECTIVE 12/8/06. PLEASE CHANGE THIS TO
 ELIMINATE ANY CONFUSION IN THE FIELD.
  
 3} SHEET E3.1, CIRCUIT L4C-8 IS AT THE COPIER.THE PANEL
 SCHEDULE LISTS THIS CIRCUIT AS A PRINTER.
  
 4} PLEASE CORRECT THE BUILDING ADDRESS ON THE PLANS TO
 READ 444 W. RAILROAD AVENUE, AS THERE ARE TWO BUILDINGS
 AT 3RD AND WEST RAILROAD AVENUE.LEAVE THE SUITE NUMBER
 FOR CLARITY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-16 Cont ID  
Sent By mawillia Date 2007-04-16 Time 13:03 Rev Time 0.00
Received By mawillia Date 2007-04-16 Time 12:54 Sent To  
Notes
2007-04-16 13:01:23*****APPROVED*****
  
  
 PLAN SHEETS LS-01, E2.1, FA2.1 AND FS2.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-04-04 Cont ID  
Sent By mawillia Date 2007-04-04 Time 17:32 Rev Time 0.00
Received By mawillia Date 2007-04-04 Time 17:27 Sent To  
Notes
2007-04-04 17:32:15*****APPROVED*****
  
  
  
 ALL COMMENTS FROM THE 02/06/07 FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;THE APPRPIATE PLAN SHEET(S) TO BE
 STAMPED WHEN ALL OTHER PLAN REVIEWS HAVE BEEN
 SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By mawillia Date 2007-02-06 Time 12:39 Rev Time 0.00
Received By mawillia Date 2007-02-06 Time 12:39 Sent To  
Notes
2007-02-06 12:43:16*****DENIED*****
  
  
 01.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 02. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 04.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 05.DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE SO
 THAT IT IS DISTINGUISHABLE FROM OTHER TENANT SITES ON
 THE FLOOR.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT.
  
 06.DOOR(S) LEADING DIRECTLY TO THE FOURTH FLOOR
 CORRIDOR SHALL BE AN APPROVED, LISTED, AND LABELED FIRE
 DOOR & ASSEMBLY IN ACCORDANCE WITH THE REQUIREMENTS OF
 NFPA 80.
  
 07.WHAT IS INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS?
  
 08.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO THE EXIT(S).ALSO ON THIS
 SHEET, INDICATE THE LOCATION OFFIRE EXTINGUISHER(S)
 AT DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 09.ON SHEET FA0.1, FIRE ALARM NOTE #17 SHOULD BE
 CHANGED TO "INITIATE A GENERAL FIRE ALARM".
  
 10.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR
 THIS TENANT SPACE.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED ON THE PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 10:03 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 10:03 Sent To E
Notes
2007-04-23 10:03:53TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-11 Cont ID  
Sent By adarroug Date 2007-04-11 Time 14:59 Rev Time 0.00
Received By adarroug Date 2007-04-11 Time 14:59 Sent To  
Notes
2007-04-11 14:59:26TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 18:45 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 18:45 Sent To  
Notes
2007-04-03 17:31:50TO BOB # 13
2007-03-30 18:45:54WAITING FOR BOB BOARD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-09 Cont ID  
Sent By jleech Date 2007-02-09 Time 08:35 Rev Time 0.00
Received By jleech Date 2007-02-05 Time 10:57 Sent To  
Notes
2007-02-05 10:59:13TO" BOB"#9--APPL TAKEN OUT OF IN-COMING BEFORE THE
 ROUTING PROCESS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-04-04 Cont ID  
Sent By tgordon Date 2007-04-04 Time 15:41 Rev Time 0.30
Received By tgordon Date 2007-04-04 Time 15:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-08 Cont ID  
Sent By tgordon Date 2007-02-08 Time 13:39 Rev Time 0.45
Received By tgordon Date 2007-02-08 Time 13:39 Sent To  
Notes
2007-02-08 13:54:16*** DENIED ***
 1) SEE BUILDING REVIEW NOTE #2, PLEASE CORRECT.
  
 2) PLEASE CORRECT JOB ADDRESS IN TITLE BLOCK (444 W.
 RAILROAD AVE. SUITE 430).
  
 3) BE ADVISED A NOTICE OF COMMENCEMENT WILL NEED TO BE
 FILED AS THIS PERMIT 07011041 FOR TENANT IMPROVEMENT IS
 NOT IN THE SCOPE OF PERMIT 04042022 WHICH CAN NOT BE
 USED AS A MASTER PERMIT, PER ROBERT BROWN SERVICES
 MANAGER.
  
 4) THE RETURN AIR TRANSFER DUCTS TO OFFICES 1, 2, 3, 4,
 AND CONFERENCE ROOM ARE UNDER-SIZED. BALANCED RETURN
 AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE. PER 2004 FBC/R
 M1602.4 . PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-04 Cont ID  
Sent By jleech Date 2007-04-04 Time 07:53 Rev Time 0.00
Received By jleech Date 2007-04-04 Time 07:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-09 Cont ID  
Sent By jleech Date 2007-02-09 Time 08:24 Rev Time 0.00
Received By jleech Date 2007-02-09 Time 08:24 Sent To  
Notes
2007-02-09 08:34:44DENIED;
 1. CHANGE NOTE 11 ,PAGE P0.1 PLUMBING NOTES. DELETE PVC
 AS A TYPE OF PIPE THAT CAN BE USED SINCE THE AREA ABOVE
 THE DROPPED CEILING IS A PLENUM.
 2. WATER HAMMER ARRESTORS SHALL BE INSTALLED PER
 MANUFACTURE'S INSTALLATION INSTRUCTIONS, AS CLOSE TO
 THE SOURSE AS POSSIBLE. SECTION 604.9
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695