Plan Review Details - Permit 07011040
Plan Review Stops For Permit 07011040
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-31 Cont ID  
Sent By lmartine Date 2007-05-31 Time 16:55 Rev Time 0.00
Received By lmartine Date 2007-05-31 Time 16:55 Sent To P
Notes
2007-06-01 09:33:47SUBMIT 2ND SET OF REVISED SHEETS FOR APPROVAL.
2007-05-31 16:56:05REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-05-31 Cont ID  
Sent By lmartine Date 2007-05-31 Time 16:27 Rev Time 0.00
Received By lmartine Date 2007-05-31 Time 16:27 Sent To  
Notes
2007-05-31 16:49:37RESTAMP SUBMITTAL DENIED, REVISION SHOWN ON PAGES A2.1,
 A2.2, AND P1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-22 Cont ID  
Sent By jwitmer Date 2007-02-22 Time 15:39 Rev Time 1.22
Received By jwitmer Date 2007-02-22 Time 15:39 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-31 Cont ID  
Sent By jwitmer Date 2007-01-31 Time 15:24 Rev Time 1.11
Received By jwitmer Date 2007-01-31 Time 15:18 Sent To  
Notes
2007-01-31 16:07:05BUILDING PLAN REVIEW
 PERMIT: 07011040
 ADD: 10130 NORTHLAKE BLVD. # 118
 CONT: RIELLY CONSTRUCTION CORP
 TEL: (561)262-6876
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC UPDATES
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 MISSING THE 2004 EXISSTING BUILDING CODE W/ 2006
 UPDATES
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 PLANS INDICATE A TYPE"IV" CONSTRUCTION. THIS CREATES
 TWO ISSUES:
 C1) HEAVY TIMBER- THIS SHOPPING CENTER IS NOT DESIGNED
 AS HEAVY TIMBER CONSTRUCTION.
 C2) NOTE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6
 IS THE MINIMUM REQUIRED FOR THE ENTIRE SHOPPING CENTER
 , IF
 FIRE SPRINKLER INCREASES ARE TAKEN AND OR FRONTAGE
 INCREASES
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3) TOLIET ROOMS: 1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE.
  
 4) PLANS DO NOT PROVIDE AT WHAT ELEVATION THE ROOF TOP
 MECHANICAL UNITS ARE LOCATED?
 1509.6 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1.THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET
 OR ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2.LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3.LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6
 INCHES (152 MM) DEEP.
 4.THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5.RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6.LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL
 BE PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE
 OF WITHSTANDING 100 POUNDS (488.2 KG/M 2 ) PER SQUARE
 FOOT.
 7.LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS.
  
 5) THE MECHANICAL SHEET M2.1 NOTE# 7 REFERS TO THE HIGH
 WIND VELOCITY ZONE CRITERIA THIS IS TERMINOLOGY FOR
 DADE&BROWARD COUNTIES ONLY.
 PLEASE PROVIDE ANCORAGE OF THE RTU UNIT TO CURB AND
 CURB TO ROOF FRAMING MEMBERS.
 FBC 1604.2
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-06-06 Cont ID  
Sent By btrobaug Date 2007-06-06 Time 11:46 Rev Time 0.33
Received By btrobaug Date 2007-06-06 Time 11:17 Sent To B
Notes
2007-06-06 11:48:04 
  
  
 RESTAMP ONLY, NO REVISION TO THESE "E" SHEETS./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-08 Cont ID  
Sent By btrobaug Date 2007-03-08 Time 12:29 Rev Time 0.50
Received By btrobaug Date 2007-03-08 Time 12:10 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-02-20 Cont ID  
Sent By btrobaug Date 2007-02-20 Time 10:57 Rev Time 1.00
Received By btrobaug Date 2007-02-20 Time 06:31 Sent To  
Notes
2007-02-20 09:10:44 
  
 DENIED/INCOMPLETE INFORMATION.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE FOLLOWING REVIEW COMMENTS WERE NOT ADDRESSED
 FROM THE PREVIOUS REVIEW:
  
 "2} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING".STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.NOTE #1 ADDRESSING THIS ISSUE
 STATES THAT THE "SPACES LESS THAN 5000 SF". PLEASE SEE
 13-101.1.4. A "SPACE" IS NOT A "BUILDING", THE
 "BUILDING" IS MORE THAN 5000 SF, THE "SPACE" MUST
 COMPLY. SHOW COMPLIANCE ON THE DRAWING, NOT IN THE
 NOTES.106.1.1 FBC.
  
 3} PLEASE INDICATE CONDUCTOR SIZE ON THE PANEL SCHEDULE
 SO THAT COMPLIANCE WITH 310.16 CAN BE REVIEWED. THE
 BRANCH CIRCUIT CONDUCTOR SIZES,AS WELL AS THE FEEDER,
 NEED TO BE ON THE SCHEDULE. 106.3.5.1.2(1), FBC AS
 AMENDED.
  
 THESE COMMENTS ARE FROM THIS REVIEW.
  
 4} SHEET #5 OF THE CALCULATIIONS INCORRECTLY INDICATES
 "PASSES", THERE ARE NO LIGHTING CONTROLS SHOWN ON THE
 DRAWING.
  
 5} SHEET #2 OF THE INPUT DATA REPORT INCORRECTLY
 INDICATES 1 FLUORESCENT FIXTURE@ 1300 WATTS FOR THE
 LIGHTING FOR THE SPACE. PLEASE CORRECT INDICATING ALL
 FIXTURES BEING USED.
  
 6} PROVIDE A FIXTURE SCHEDULE THAT MATCHES WHAT THE
 ENERGY CALCULATIONS INDICATES.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW
 ONES, SUBMIT OLD SHEETS TO EXPEDITE
 REVIEW AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-24 Cont ID  
Sent By btrobaug Date 2007-01-24 Time 16:04 Rev Time 1.00
Received By btrobaug Date 2007-01-24 Time 15:52 Sent To  
Notes
2007-01-24 16:04:19 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} COMMERCIAL AND INSTITUTIONAL KITCHENS ? FOR THE
 PURPOSES OF THIS SECTION, A KITCHEN IS AN AREA WITH A
 SINK AND PERMANENT FACILITIES FOR FOOD PREPARATION AND
 COOKING SHALL BE GFI PROTECTED PER 210.8(B).
  
 2} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING.
  
 3} PLEASE INDICATE CONDUCTOR SIZE ON THE PANEL SCHEDULE
 SO THAT COMPLIANCE WITH 310.16 CAN BE REVIEWED.
  
 4} INDICATE COMPLIANCE WITH NFPA-101 FOR EGRESS
 LIGHTING, 7.8.1.1.
  
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW
 ONES, SUBMIT OLD SHEETS TO EXPEDITE
 REVIEW AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 12:43 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 12:43 Sent To  
Notes
2007-02-23 12:49:55*****APPROVED*****
  
  
 ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEW HAVE BEEN
 ADDRESSED.SHEETS A2.1 AND E2.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By mwennerg Date 2007-02-06 Time 14:27 Rev Time 0.00
Received By mwennerg Date 2007-02-06 Time 14:26 Sent To  
Notes
2007-02-06 14:46:51***DENIED***
  
 1) PLEASE INDICATE HOW THE REQUIREMENTS OF NFPA 101,
 SECTION 7.2.1.5 WILL BE COMPLIED WITH IF KEYED LOCKS
 ARE ALLOWED ON DOORS.
  
 2) WHAT WOULD PREVENT THE DOOR TO EXISTING STORAGE 108
 FROM OBSTRUCTING THE EXIT WHEN DOOR IS IN THE OPEN
 POSITION.
  
 3) WILL FOODS THAT PRODUCE GREASE LADEN VAPORS BE
 COOKED AT ANY TIME?
  
 4) AN ADDITIONAL FIRE EXTINGUISHER WILL BE REQUIRED
 NEAR THE FRONT EXIT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 09:11 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 09:11 Sent To B
Notes
2007-05-23 09:11:28TO "JWITMER" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 09:59 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 09:58 Sent To E
Notes
2007-03-06 09:59:20TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-12 Cont ID  
Sent By adarroug Date 2007-02-12 Time 11:11 Rev Time 0.00
Received By adarroug Date 2007-02-12 Time 11:11 Sent To  
Notes
2007-02-12 11:11:16TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-06 Cont ID  
Sent By mwennerg Date 2007-02-06 Time 14:53 Rev Time 0.00
Received By mwennerg Date 2007-01-23 Time 13:33 Sent To  
Notes
2007-01-23 13:33:35TO "BOB"#12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-02-15 Cont ID  
Sent By tgordon Date 2007-02-15 Time 09:38 Rev Time 0.20
Received By tgordon Date 2007-02-15 Time 09:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-01-25 Cont ID  
Sent By tgordon Date 2007-01-25 Time 08:12 Rev Time 0.35
Received By tgordon Date 2007-01-25 Time 08:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-06-07 Cont ID  
Sent By jleech Date 2007-06-07 Time 09:01 Rev Time 0.00
Received By jleech Date 2007-06-07 Time 09:01 Sent To  
Notes
2007-06-07 09:02:34REVISED PLUMBING PLANS, ADDED 3 COMPARTMENT SINK
 REQUIRED BY HEALTH DEPARTMENT.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-06-06 Cont ID  
Sent By jleech Date 2007-06-06 Time 10:03 Rev Time 0.00
Received By jleech Date 2007-06-06 Time 10:03 Sent To  
Notes
2007-06-06 10:05:28PLUMBING REVISION OK WILL STAMP WHEN 2ND SET OF PLANS
 ARE SUBMITED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-02-13 Cont ID  
Sent By jleech Date 2007-02-13 Time 07:14 Rev Time 0.00
Received By jleech Date 2007-02-13 Time 07:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By jleech Date 2007-01-30 Time 08:38 Rev Time 0.00
Received By jleech Date 2007-01-30 Time 08:38 Sent To  
Notes
2007-01-30 09:06:30DENIED;
 1. A STATE OF FLORIDA, DEPARTMENT OF AGRIULTURE &
 CONUMER SERVICE FOOD PERMIT IS REQUIRED.
 CONTACT THE DEPT. OF AGRICULTURE & CONSUMER
 SERVICES
 170 ADMINISTRATION BUILDING
 3125 CONNER BLVD.
 TALLAHASSEE, FL 32399-1650
 (904) 488-3951 OR (800) 435-7352
 DR. JOHN REICHNER
 2. WASTE ORDINANCE #3434 REQUIRES PLANS TO BE REVIEWED
 BYTHE UTILITY DEPARTMENT FOR GREASE INTERCEPTORS.
 CONTACT;
 LYNN MASSON 822-2271
 RODNEY COMPO822-2272
 FAX # 822-2279
 3. A WATER RISER DIAGRAM IS REQUIRED. PLEASE ADD TO
 PLANS. ADMINISTRATIONCODE 2004. SECTION 106.3.5.1.3
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695