Plan Review Details - Permit 07011030
Plan Review Stops For Permit 07011030
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-04-25 Cont ID  
Sent By mawillia Date 2007-04-25 Time 14:33 Rev Time 0.00
Received By mawillia Date 2007-04-25 Time 13:29 Sent To  
Notes
2007-04-25 13:55:35*****APPROVED*****
  
  
 PER THE TELEPHONE CONVERSATION WITH THE CONTRACTOR ON
 04/23/07, WATERFLOW AND TAMPER DEVICES WERE LOCATED ON
 THE PLANS.PLAN SHEETS 3 THRU 7 (OF THE 10) WERE
 STAMPED, INITIALED, AND DATED; READY FOR PERMIT
 ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-04-19 Cont ID  
Sent By mawillia Date 2007-04-19 Time 16:05 Rev Time 0.00
Received By mawillia Date 2007-04-19 Time 15:24 Sent To  
Notes
2007-04-19 15:59:31*****UNSAT*****
  
  
 DURING PLAN REVIEW, UNABLE TO LOCATE WATERFLOW AND
 TAMPER DEVICES FOR THIS SYSTEM.A MEETING WILL BE
 ARRANGED WITH CONTRACTOR TO ASSIST WRITER IN LOCATING
 THESE DEVICES ON THE PLANS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722OFFICE
 561-644-7326CELLULAR

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-15 Cont ID  
Sent By mawillia Date 2007-02-15 Time 12:00 Rev Time 0.00
Received By mawillia Date 2007-02-15 Time 12:00 Sent To  
Notes
2007-02-15 12:26:32*****DENIED*****
  
  
  
 1.SINCE THE SCOPE OF WORK IS GREATER THAN $2500.00,
 THE APPLICANT SHALL FILE WITH THE AHJ EITHER A RECORDED
 NOTICE OF COMMENCEMENT OR A STATEMENT THAT HAS BEEN
 FILED FOR RECORDING, ALONG WITH A COPY THEREOF.
  
 2.THE CORRECT AND/OR ACTUAL ADDRESS (4300 NORTH
 FLAGLER DRIVE) OF WHERE THE WORK IS GOING TO BE
 CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 3.DUCT SMOKE DETECTORS, SUCH AS 2-046 NOTED ON SHEET
 8, SHALL INITIATE A GENERAL FIRE ALARM.AMEND THE
 SEQUENCE OF OPERATION ON SHEET 1 TO REFLECT THIS
 REQUIREMENT AS PER WEST PALM BEACH FIRE PREVENTION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-28 Cont ID  
Sent By spalmer Date 2007-03-28 Time 17:48 Rev Time 0.00
Received By spalmer Date 2007-03-28 Time 17:48 Sent To FIRE
Notes
2007-03-28 17:48:42TO FIRE BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-15 Cont ID  
Sent By mawillia Date 2007-02-15 Time 12:00 Rev Time 0.00
Received By mawillia Date 2007-01-23 Time 09:29 Sent To  
Notes
2007-01-23 09:29:29TO "F" BOX