Review Stop E ELECTRICAL
Rev No 2 Status N Date 2007-04-26 Cont ID  
Sent By dpalmer Date 2007-04-26 Time 10:54 Rev Time 0.00
Received By dpalmer Date 2007-04-26 Time 10:54 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-25 Cont ID  
Sent By dpalmer Date 2007-02-25 Time 09:04 Rev Time 0.00
Received By dpalmer Date 2007-02-25 Time 08:54 Sent To FIRE
Notes
2007-02-25 09:10:11** UNSAT **
  
 1) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK IS
 LOW. PLEASE SEE VALUE SHALL BE ALL LABOR AND MATERIALS
 INCLUDING DEVICES AND WIRING.
 FBC 108.3.
 THIS IS A 20 STORY BUILDING.
  
 2) NOTE: PLEASE SUBMIT ATLEAST ONE COPY OF PLANS WHICH
 CONTAINS THE ORIGINAL STAMPS FROM THE ENGINEER OF
 RECORD WITH HIS ORIGINAL SIGNATURE.
 PLEASE SEE THAT A LETTER FROM THE ENGINEER , SIGNED,
 DATED AND SEALED, REFERENCING THE REVIEWED PLANS DATED
 AS OF 2/14/07 WILL ALSO BE ACCEPTABLE.
  
 PLEASE SUBMTI THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-27 Cont ID  
Sent By mawillia Date 2007-08-27 Time 17:02 Rev Time 0.00
Received By mawillia Date 2007-08-27 Time 16:27 Sent To  
Notes
2007-08-27 17:02:16*****SUBMITTALS RECEIVED*****
  
  
 FIRE ALARM EQUIPMENT RE-SUBMITTALS APPROVED AND
 STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-05-14 Cont ID  
Sent By mawillia Date 2007-05-14 Time 13:45 Rev Time 0.00
Received By mawillia Date 2007-05-14 Time 12:24 Sent To  
Notes
2007-05-14 13:45:03*****APPROVED*****
  
  
 ALL COMMENTS TO THE PREVIOUS FIRE PLAN REVIEW APPEAR TO
 HAVE BEEN ADDRESSED.PLAN SHEETS FA! THRU FA-29 WERE
 STAMPED, INITIALED, AND DATED;READY FOR PERMIT
 ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-20 Cont ID  
Sent By mwennerg Date 2007-03-20 Time 13:49 Rev Time 0.00
Received By mwennerg Date 2007-03-20 Time 13:49 Sent To  
Notes
2007-03-20 14:01:18***DENIED***
  
 1) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. SHT FA-01
 AND FA-02 SEQUENCE OF OPERATION A.
  
 2) FIRE ALARM TO COMPLY WITH THE REQUIREMENTS OF NFPA
 72 IN REGARDS TO SURVIVABILITY.
  
 3) FIRE ALARM SYSTEM SHALL BE CLASS A OR FULLY
 ADDRESSABLE.
  
 4) ONE SMOKE DETECTOR IS CALLED OUT IN THE PARKING
 GARAGE ON SHT FA-3. ?
  
 5) MINI-HORN IN UNIT B7 (13) APPEARS TO BE MISSING. SHT
 FA-8
  
 6) STORAGE ROOM ON SHT FA-9 SHOWS NO SMOKE DETECTORS
 AND (2) STROBES ONLY. OTHER SHEETS ILLUSTRATE (1)
 SPEAKER/HORN AND (1) STROBE.
  
 7) MINI-HORNS APPEAR TO HAVE BEEN LEFT OUT IN GREAT
 ROOMS ON SEVERAL SHEETS.
  
 8) MINI-HORNS ARE MISSING IN UNITS B 11&12, AND MASTER
 BR C1. SHT FA-10
  
 9) PLANS INDICATE CENTRAL STATION. SHOULD READ FIRE
 ALARM TO BE UL CERTIFIED FOR CENTRAL STATION SERVICE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW(561) 805-6722
 FIRE PREVENTION(561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-28 Cont ID  
Sent By adarroug Date 2007-07-28 Time 12:41 Rev Time 0.00
Received By adarroug Date 2007-07-28 Time 12:41 Sent To FIRE
Notes
2007-07-28 12:42:01TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-26 Cont ID  
Sent By adarroug Date 2007-04-26 Time 09:26 Rev Time 0.00
Received By adarroug Date 2007-04-26 Time 09:26 Sent To E
Notes
2007-04-26 09:26:57TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-20 Cont ID  
Sent By mwennerg Date 2007-03-20 Time 14:04 Rev Time 0.00
Received By mwennerg Date 2007-02-20 Time 11:11 Sent To  
Notes
2007-02-20 11:11:23TO "DPALMER" DESK/PER NOTE ATTACHED TO PLANS