Plan Review Details - Permit 07010969
Plan Review Stops For Permit 07010969
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-07 Cont ID  
Sent By shill Date 2007-04-07 Time 10:02 Rev Time 0.00
Received By shill Date 2007-04-07 Time 10:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-21 Cont ID  
Sent By shill Date 2007-02-21 Time 15:15 Rev Time 0.00
Received By shill Date 2007-02-21 Time 15:15 Sent To  
Notes
2007-02-21 15:16:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND CLADDING IN A
 BUILDING OR STRUCTURE SHALL BE ANCHORED TO RESIST
 WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES TO THE
 FOUNDATION.WHERE A PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE MINIMUM DEAD LOAD
 LIKELY TO BE IN PLACE DURING A DESIGN WIND EVENT SHALL
 BE USED.
  
 2.)PROVIDE A SITE PLAN SHOWING PROPOSED LOCATION.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-04-26 Cont ID  
Sent By btrobaug Date 2007-04-26 Time 12:43 Rev Time 0.00
Received By btrobaug Date 2007-04-26 Time 12:25 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-28 Cont ID  
Sent By btrobaug Date 2007-03-28 Time 06:54 Rev Time 0.33
Received By btrobaug Date 2007-03-27 Time 18:24 Sent To P
Notes
2007-03-28 06:54:50 
 DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE PROVIDE A CALCULATION FOR THE LOADS TO BE FED
 BY THE GENERATOR. THE CALCULATION GIVEN @ 126 AMPS IS
 OBVIOUSLY FOR THE ENTIRE RESIDENCE, AND MORE THAN THE
 GENERATOR OUTPUT OF 52.5 AMPS. 702.5, 2005 NEC.
  
 IT IS NOTED THAT THE INTENDED CIRCUUITS WERE LISTED,
 BUT A CALCULATION FOR THOSE IS NEEDED.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
 FAX/:561/805-6676

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-02-13 Cont ID  
Sent By btrobaug Date 2007-02-02 Time 14:02 Rev Time 0.50
Received By btrobaug Date 2007-02-02 Time 13:55 Sent To M
Notes
2007-02-02 14:02:54 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS AND
 RECOMMENDATION, REGARDING CLEARANCES FOR THE
 GENERATOR.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE
 PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE
 SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 4} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-04-26 Cont ID  
Sent By mperson Date 2007-04-26 Time 15:34 Rev Time 0.33
Received By mperson Date 2007-04-26 Time 15:33 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-04-04 Cont ID  
Sent By mperson Date 2007-04-04 Time 16:41 Rev Time 0.33
Received By mperson Date 2007-04-04 Time 16:41 Sent To M
Notes
2007-04-04 16:51:29DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **NO** PLEASE PROVIDE ON THE SURVEY DIMENSIONS OF
 THE GENERATOR IN RELATION TO STRUCTURES AND PROPERTY
 LINES.
  
 3. **NO** PLEASE PROVIDE INFORMATION OF GENERATOR
 EXHAUST NOT BEING INSTALLED CLOSER THAN TEN FEET FROM
 ANY OPENING INTO THE DWELLING STRUCTURE. THIS INCLUDES
 DOORS, WINDOWS, AND ATTIC VENTILATION OPENINGS. PLEASE
 PROVIDE THIS INFORMATION ON THE SURVEY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-02-13 Cont ID  
Sent By mperson Date 2007-02-13 Time 09:48 Rev Time 0.33
Received By mperson Date 2007-02-13 Time 09:48 Sent To B
Notes
2007-02-13 10:08:29DENIED INCOMPLETE INFORMATION
 REFERENCE: FBC-2004 FUEL GAS AND CITY OF WEST PALM
 BEACH RESIDENTIAL GENERATOR PERMIT APPLICATION
 REQUIREMENTS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE PROVIDE MANUFACTURER SPECIFICATIONS
 REGAURDING CLEARENCES FOR THE GENERATOR TO STRUCTURES.
  
 2. PLEASE PROVIDE ON THE SURVEY DIMENSIONS OF THE
 GENERATOR IN RELATION TO STRUCTURES AND PROPERTY
 LINES.
  
 3. PLEASE PROVIDE INFORMATION OF GENERATOR EXHAUST NOT
 BEING INSTALLED CLOSER THAN TEN FEET FROM ANY OPENING
 INTO THE DWELLING STRUCTURE. THIS INCLUDES DOORS,
 WINDOWS, AND ATTIC VENTILATION OPENINGS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-04-26 Cont ID  
Sent By adarroug Date 2007-04-26 Time 08:53 Rev Time 0.00
Received By adarroug Date 2007-04-26 Time 08:53 Sent To E
Notes
2007-04-26 08:54:11TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 15:28 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 15:28 Sent To Z
Notes
2007-04-20 15:28:30TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-27 Cont ID  
Sent By spalmer Date 2007-03-27 Time 17:29 Rev Time 0.00
Received By spalmer Date 2007-03-27 Time 17:29 Sent To E
Notes
2007-03-27 17:29:41TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 10:09 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 10:09 Sent To Z
Notes
2007-03-22 10:09:16TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 11:26 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 11:26 Sent To E
Notes
2007-01-31 11:27:01TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-21 Cont ID  
Sent By shill Date 2007-02-21 Time 15:16 Rev Time 0.00
Received By shill Date 2007-01-22 Time 11:06 Sent To  
Notes
2007-01-22 11:06:20TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-04-27 Cont ID  
Sent By tgordon Date 2007-04-27 Time 09:02 Rev Time 0.30
Received By tgordon Date 2007-04-27 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-04-05 Cont ID  
Sent By tgordon Date 2007-04-05 Time 07:54 Rev Time 0.20
Received By tgordon Date 2007-04-05 Time 07:54 Sent To B
Notes
2007-04-05 07:55:49*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-06 Cont ID  
Sent By btrobaug Date 2007-02-13 Time 10:29 Rev Time 0.20
Received By tgordon Date 2007-02-06 Time 15:53 Sent To G
Notes
2007-02-06 15:54:49*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-04-23 Cont ID  
Sent By adavila Date 2007-04-23 Time 17:29 Rev Time 0.00
Received By adavila Date 2007-04-23 Time 17:29 Sent To I
Notes
2007-04-23 17:29:58PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-03-26 Cont ID  
Sent By adavila Date 2007-03-26 Time 15:30 Rev Time 0.00
Received By adavila Date 2007-03-26 Time 15:30 Sent To I
Notes
2007-03-26 15:32:32PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.PROVIDE LOCATION OF PROPOSED GENERATOR WITH SETBACK
 DIMENSIONS FROM PROPERTY LINES ON BOTH COPIES OF
 SURVEY.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-27 Cont ID  
Sent By mmclean Date 2007-01-27 Time 09:43 Rev Time 0.00
Received By mmclean Date 2007-01-27 Time 09:43 Sent To I
Notes
2007-01-29 09:44:57DENIED,
 1. SHALL PROVIDE TWO COPIES OF CURRENT SURVEYS, SHOWING
 THE LOCATION OF THE PROPOSED GENERATOR WITH SETBACKS.
 2. PLEASE PROVIDE THE DIMENSION OF THE PROPOSED
 GENERATOR AND HOW FAR IT WILL BE LOCATED FROM PROPERTY
 LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720