Plan Review Details - Permit 07010924
Plan Review Stops For Permit 07010924
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-01 Cont ID  
Sent By shill Date 2008-07-01 Time 09:16 Rev Time  
Received By shill Date 2008-06-30 Time 15:57 Sent To  
Notes
2008-07-01 09:17:13PROVISO
 SEE ATTACHED PARKING DETAIL
 CANOPY PLANS WITH 05080493

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-21 Cont ID  
Sent By shill Date 2008-02-21 Time 09:15 Rev Time 0.00
Received By shill Date 2008-02-21 Time 09:14 Sent To  
Notes
2008-02-21 09:22:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 2.)THE ACCESSIBLE PARKING DETAIL DOES NOT COMPLY WITH
 CITY OF WEST PALM BEACH STANDARDS, SEE ATTACHED.
  
 SEE SHEET C8 DATED JAN 15, 2006.SAME PLANS SUBMITTED.
  
  
 NEW COMMENT:
  
 3.)PROVIDE A STRUCTURAL DETAIL FOR THE CANOPY.IF
 THIS IS A FABRIC CANOPY, PROVIDE CERTIFICATE SHOWING
 COMPLIANCE WITH FBC3105.3.IF THE FABRIC IS
 REMOVEABLE, PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS
 TO SHOW COMPLIANCE WITH FBC3105.4.2.1.THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-23 Cont ID  
Sent By shill Date 2007-03-23 Time 08:38 Rev Time 0.00
Received By shill Date 2007-03-23 Time 08:38 Sent To E
Notes
2007-03-23 08:58:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)DECLARE WIND DESIGN CRITERIA FOR THE LIGHT POLES,
 FBC1603.1.4.
  
 2.)THE ACCESSIBLE PARKING DETAIL DOES NOT COMPLY WITH
 CITY OF WEST PALM BEACH STANDARDS, SEE ATTACHED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-14 Cont ID  
Sent By btrobaug Date 2008-02-14 Time 13:54 Rev Time 0.00
Received By btrobaug Date 2008-02-14 Time 13:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-23 Cont ID  
Sent By btrobaug Date 2007-03-23 Time 10:18 Rev Time 0.50
Received By btrobaug Date 2007-03-23 Time 09:22 Sent To FIRE
Notes
2007-03-23 10:18:17 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} SUBMIT SPECIFICATIONS FOR THE LIGHT POLES AND
 FIXTURES.
  
 2} VERIFY THAT THE SERVICE SHOWN ON SHEET "C-12" IS
 EXISTING, AND INDICATE THE LOCATION OF SAME.
  
 3} SEE BUILDING PLAN REVIEW REGARDING WIND LOAD
 ENGINEERING.
  
 4} INDICATE AREA OF DETAIL ON SHEET C-5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2008-05-23 Cont ID  
Sent By rchokshi Date 2008-05-23 Time 13:44 Rev Time 0.00
Received By rchokshi Date 2008-05-23 Time 13:42 Sent To  
Notes
2008-05-23 13:44:02PLEASE SEE E-MAIL FROM PENA ARTURO DATED 5/23/08,
 1:33PM.
 SO, ENG REVIEW NOT REQUIRD.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-02-25 Cont ID  
Sent By rchokshi Date 2008-02-25 Time 16:00 Rev Time 0.00
Received By rchokshi Date 2008-02-25 Time 15:53 Sent To  
Notes
2008-02-25 15:59:54PLEASE PROVIDE FOLLOWING INFO:
  
 1.FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , SIDEWALK
 ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW ON THE
 DRAWINGS.
 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT,GEO TECH
 REPORT.
 3.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 4. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.
 5. HOW DO YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 6. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 7. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL IN A LETTER & ON
 DRAWING REVISIONS,TO EXPEDITE YOUR PERMITTING
 PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-02-01 Cont ID  
Sent By rchokshi Date 2007-02-01 Time 13:59 Rev Time 0.00
Received By rchokshi Date 2007-02-01 Time 13:46 Sent To B
Notes
2007-02-01 13:59:05PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW THE STANDARDS OFWPB ON DRAWINGSFOR
 SLOPEON SIDEWALK WIDTH , DRIVEWAY, PARKING, HANDICAP
 PARKING, ALSO PAINTPER CITY CODES ETC.,, MUST MEET
 PER ADA,,ETC.,
 2. PLEASE SHOW ON DRAWINGS,DUMPSTER & ITS ENCLOSURE
 LOCATION ON DWG, LOCATION MUST BE ACCESSIBLE FOR PICKUP
 TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FL BLDG CODE, PLEASE SHOW
 ON THE DRAWINGS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,GEO TECH
 REPORT.
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ?PERVIOUS AREA, LIKE GREEN,
 LAKES, ETC,IMPERVIOUS AREA CAL.,
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ? SO, WE CAN CHECK PERVIOUS, IMPERVIOUS
 CAL.
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ?
 8. POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 10. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
  
 PLEASE RESPOND EACH ITEM IN DETAIL IN A LETTER & ON
 DRAWING REVISIONS,TO EXPEDITE YOUR PERMITTING
 PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-07-01 Cont ID  
Sent By mawillia Date 2008-07-01 Time 10:55 Rev Time 0.00
Received By mawillia Date 2008-07-01 Time 10:42 Sent To B1
Notes
2008-07-01 10:53:25*****PROVISO*****
  
 SHEET C-6 STAMPED, INTIALED, AND DATED BASED BATTALION
 CHIEF MIKE CARSILLO'S APPROVAL OF THE FIRE ACCESS
 VARYING 15' - 20'
  
  
 CAPT MICHAEL WILLIAMS
 FIRE PLAN REVIEW
 (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-02-28 Cont ID  
Sent By mawillia Date 2008-02-28 Time 15:50 Rev Time 0.00
Received By mawillia Date 2008-02-28 Time 14:38 Sent To  
Notes
2008-02-28 15:39:01*****PROVISO*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE STAMPED WHEN
 THE OTHER REVIEWERS HAVE BEEN SATISFIED AND THE
 FOLLOWING COMMENT FROM THE PREVIOUS FIRE PLAN REVIEW
 HAS BEEN ADDRESSED:
  
 1.PLEASE EXPLAIN ON SHEET C6 SEC BB FIRE ACCESS
 VARING 15' TO 20'.PER NFPA 1 2003 ED.FIRE DEPT.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WITDTH OF NOT
 LESS THAN 20 FT. AND AN UNOBSTRUCTED VERTICAL CLEARANCE
 OF NOT LESS THAN 13FT 6IN. YOUR RESPONSE REFERENCES
 A CONVERSATION HAD WITH THEN ASST. FIRE MARSHAL MIKE
 CARSILLO ON 05/28/2004 WITH AN ATTACHED SKETCH OF THE
 FIRE ACCESS.THE APPROVAL OF THIS ARRANGEMENT NEEDS TO
 BE VERIFIED WITH BATTALION CHIEF MIKE CARSILLO, FIRE
 MARSHAL, AT 561-804-4724.
  
  
 CAPT MICHAEL WILLIAMS
 FIRE PLAN REVIEW
 (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-05 Cont ID  
Sent By mawillia Date 2007-04-05 Time 13:17 Rev Time 0.00
Received By mawillia Date 2007-04-05 Time 13:07 Sent To  
Notes
2007-04-05 13:17:06*****DENIED*****
  
  
 1.PLEASE EXPLAIN ON SHEET C6 SEC BB FIRE ACCESS
 VARING 15' TO 20'.PER NFPA 1 2003 ED.FIRE DEPT.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WITDTH OF NOT
 LESS THAN 20 FT. AND AN UNOBSTRUCTED VERTICAL CLEARANCE
 OF NOT LESS THAN 13FT 6IN.
  
  
  
  
 CAPT MICHAEL WILLIAMS
 FIRE PLAN REVIEW
 (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-13 Cont ID  
Sent By adarroug Date 2008-06-13 Time 09:07 Rev Time 0.00
Received By adarroug Date 2008-06-13 Time 09:07 Sent To  
Notes
2008-06-13 09:07:39TO "COMM" BD#8

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-07 Cont ID  
Sent By adarroug Date 2008-02-07 Time 16:55 Rev Time 0.00
Received By adarroug Date 2008-02-07 Time 16:55 Sent To  
Notes
2008-02-07 16:58:37TO "COMM" BD#23

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 14:15 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 14:15 Sent To B
Notes
2007-02-01 14:16:23TO "MISC" BOX#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 08:16 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 08:15 Sent To ENG
Notes
2007-02-01 08:16:05TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-14 Cont ID  
Sent By shill Date 2007-04-05 Time 14:54 Rev Time 0.00
Received By shill Date 2007-01-29 Time 14:20 Sent To  
Notes
2007-01-29 14:29:17 
 ROUTED TO INCOMING FOR PROCESSING.
2007-01-17 15:30:38TO "RBROWN" DESK

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-22 Cont ID  
Sent By ajones Date 2008-02-22 Time 16:52 Rev Time 0.00
Received By ajones Date 2008-02-22 Time 16:52 Sent To  
Notes
2008-02-22 16:54:03ALL PARKING SPACES MUST COMPLY WITH THE PARKING DETAILS
 ATTACHED TO THE PERMIT.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-31 Cont ID  
Sent By ajones Date 2007-01-31 Time 16:55 Rev Time 0.00
Received By ajones Date 2007-01-31 Time 16:55 Sent To  
Notes
2007-01-31 16:58:02THE 10 FOOT RESERVATION AREA SHOWN ON THE EAST PORTION
 OF THE SITE PLAN IS NOT PART OF THE PARKING LOT.
 WITHOUT THIS 10 FEET, THE PARKING LOT DOES NOT MEET
 ZONING REGULATIONS.