Plan Review Details - Permit 07010902
Plan Review Stops For Permit 07010902
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-03-02 Cont ID  
Sent By mwennerg Date 2007-03-02 Time 09:54 Rev Time 0.00
Received By mwennerg Date 2007-03-02 Time 09:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By mwennerg Date 2007-01-30 Time 14:15 Rev Time 0.00
Received By mwennerg Date 2007-01-30 Time 14:15 Sent To  
Notes
2007-01-30 14:27:11***DENIED***
  
 1) DUCT SMOKE DETECTOR INSTALLATIONS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
 2) FIRE ALARMS THAT SUPERVISE FIRE SPRINKLER SYSTENS
 SHALL BE UL CERTIFIED FOR CENTRAL STATION SERVICE.
 PROOF OF CERTIFICATE WILL BE REQUIRED AT THE TIME OF
 FINAL INSPECTION OF FIRE ALARM.
  
 3) PLEASE SUBMIT MANUFACTURER SPECIFICATION BOOKS FOR
 FIRE ALARM PANEL AND ALL ASSOCIATED EQUIPMENT AND
 DEVICES.
  
 4) FLOW SWITCHES WHEN ACTIVATED SHALL INITIATE AN ALARM
 WITHIN 45-60 SECONDS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-02-13 Cont ID  
Sent By adarroug Date 2007-02-13 Time 16:44 Rev Time 0.00
Received By adarroug Date 2007-02-13 Time 16:44 Sent To FIRE
Notes
2007-02-13 16:44:39TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-30 Cont ID  
Sent By mwennerg Date 2007-01-30 Time 14:27 Rev Time 0.00
Received By mwennerg Date 2007-01-20 Time 13:02 Sent To  
Notes
2007-01-20 13:02:45TO "F" BOX