Plan Review Details - Permit 07010804
Plan Review Stops For Permit 07010804
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-05-02 Cont ID  
Sent By mjacobs Date 2007-05-02 Time 12:32 Rev Time 0.00
Received By mjacobs Date 2007-05-02 Time 12:15 Sent To PC
Notes
2007-05-02 12:36:50BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-07 Cont ID  
Sent By mjacobs Date 2007-03-07 Time 16:58 Rev Time 0.00
Received By mjacobs Date 2007-03-07 Time 15:52 Sent To PC
Notes
2007-03-07 16:58:36BUILDING PLAN REVIEW
 PERMIT: 07010804
 ADD: 3601 POINSETTIA AVE
 CONT: CRAFTMASTER CUSTOM POOLS
 TEL: (561)278-3513
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FROM PRIVIOUS REVIEW. THE STRUCTURAL REVIEW IS OK,
 HOWEVER, THE ZONING , PLUMBING AND ELECTRIC
 REQUIREMENTS SHALL BE ADDRESSED BEFORE A PERMIT CAN BE
 ISSUED.
  
 3)THE ELECTRICAL PERMIT IS NOT APPLIED AT THIS TIME,
 WHICH MEANS THE ROUGH ELECTRICAL WORK CANNOT BEGIN
 UNTIL A PERMIT IS ISSUED.
 NOTE: FBC 108.4 ANY PERSON WHO COMMENCES ANY WORK ON A
 BUILDING, STRUCTURE, ELECTRICAL, GAS, MENCANICAL OR
 PLUMBINB SYSTEM BEFORE OBTAINING THE BUILDING'S
 OFFICIAL' APPROVAL OR THE NECESSARY PERMITS SHALL BE
 SUBJECT TO PENALTY OF 300 PERCENT OF THE USUAL PERMIT
 FEES IN ADDITION TO THE REQUIRED PERMIT FEES, AS SET IN
 APPROVED SCHEDULE OF FEES.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-09 Cont ID  
Sent By mjacobs Date 2007-02-09 Time 09:54 Rev Time 0.00
Received By mjacobs Date 2007-02-09 Time 06:41 Sent To  
Notes
2007-02-09 10:19:04BUILDING PLAN REVIEW
 PERMIT: 07010804
 ADD: 3601 POINSETTA AVE
 CONT:CRAFTMAN CUSTOM POOLS
 TEL: (561)278-3515
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)THE STRUCTURAL REVIEW IS OK AT THIS TIME, HOWEVER,
 THE ZONING PLUMBING AND ELECTRIC REQUIREMENTS SHALL BE
 ADDRESSED BEFORE A PERMIT CAN BE ISSUED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2007-04-19 Cont ID  
Sent By btrobaug Date 2007-04-19 Time 12:22 Rev Time 0.25
Received By btrobaug Date 2007-04-19 Time 12:21 Sent To Z
Notes
2007-04-19 12:22:42 
  
 PLAN SHOWS "ELECTRIC BY OTHERS, AND NO ELEC PERMIT #
 ASSIGNED./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2007-03-07 Cont ID  
Sent By btrobaug Date 2007-03-07 Time 12:35 Rev Time 0.25
Received By btrobaug Date 2007-03-07 Time 12:28 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2007-01-31 Cont ID  
Sent By btrobaug Date 2007-01-31 Time 16:29 Rev Time 0.25
Received By btrobaug Date 2007-01-31 Time 15:34 Sent To P
Notes
2007-01-31 16:30:20 
  
 NO ELECTRICAL PLANS SUBMITTED./WRT.

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-04-19 Cont ID  
Sent By mperson Date 2007-04-19 Time 12:06 Rev Time 0.00
Received By mperson Date 2007-04-19 Time 12:06 Sent To E
Notes
2007-04-19 12:08:18CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-02-05 Cont ID  
Sent By mperson Date 2007-02-05 Time 13:52 Rev Time 0.00
Received By mperson Date 2007-02-05 Time 13:52 Sent To B
Notes
2007-02-05 13:56:32CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL POOL INSPECTION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-05-01 Cont ID  
Sent By adarroug Date 2007-05-01 Time 10:22 Rev Time 0.00
Received By adarroug Date 2007-05-01 Time 10:22 Sent To B
Notes
2007-05-01 10:22:23TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-06 Cont ID  
Sent By spalmer Date 2007-04-06 Time 17:34 Rev Time 0.00
Received By spalmer Date 2007-04-06 Time 17:34 Sent To G
Notes
2007-04-06 17:35:05TO MIKE PERSON

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-05 Cont ID  
Sent By adarroug Date 2007-03-05 Time 11:04 Rev Time 0.00
Received By adarroug Date 2007-03-05 Time 11:04 Sent To E
Notes
2007-03-05 11:04:54TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-23 Cont ID  
Sent By adarroug Date 2007-02-23 Time 15:29 Rev Time 0.00
Received By adarroug Date 2007-02-23 Time 15:29 Sent To Z
Notes
2007-02-23 15:30:11TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 11:27 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 11:27 Sent To E
Notes
2007-01-31 11:28:10TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-02-09 Time   Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 10:07 Sent To  
Notes
2007-01-18 10:07:35TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-04-19 Cont ID  
Sent By mperson Date 2007-04-19 Time 12:05 Rev Time 0.33
Received By mperson Date 2007-04-19 Time 12:05 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-03-07 Cont ID  
Sent By mperson Date 2007-03-07 Time 13:45 Rev Time 0.33
Received By mperson Date 2007-03-07 Time 13:44 Sent To B
Notes
2007-03-07 14:07:07DENIED 2ND TIME
 REFERENCE: FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING
 POOLS:
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1) ** NO**,FBC-2004 SEC. 424.2.6.6.5, OR FBCR-2004
 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
 NOTE: PLEASE PROVIDE A MANUFACTURER CUT SHEET OR
 INDICATE THE MAKE AND MODEL NUMBER ON THE RESUBMITTED
 PRINTS. PLEASE REFERENCE THE ATTACHED EXAMPLE OF VACUUM
 OR PRESSURE CLEANER FITTING WITH THE ABOVE
 INFORMATION.
  
 2) **NO**,FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
 NOTE: PLEASE REFERENCE THE ATTACHED EXAMPLE OF AN
 1-1/2" ATMOSPHERIC VENT TABLE COMPLYING WITH 3 SECOND
 RELEASE. PLEASE SUBMIT A TABLE WITH 1" VENT COMPLYING
 WITH 3 SECOND RELEASE ON THE RESUBMITTAL.
  
 3) OK
  
 **IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW:
 WHEN RESUBMITTING, PLEASE REPLACE ONLY SHEETS WHICH
 HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-05 Cont ID  
Sent By mperson Date 2007-02-05 Time 13:39 Rev Time 0.33
Received By mperson Date 2007-02-05 Time 13:39 Sent To G
Notes
2007-02-05 13:52:17DENIED
 REFERENCE: FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING
 POOLS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1) FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
 NOTE: PLEASE PROVIDE A MANUFACTURER CUT SHEET OR
 INDICATE MAKE AND MODEL NUMBER ON RESUBMITTED PRINTS.
  
 2) FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
  
 3) SHEET 5 OF 5 GENERAL NOTES NUMBER 18: PER FBC-2004
 SECTION 424.2.20 AND R4101.20, PLEASE INDICATE THE POOL
 AND SPA TURN OVER TIME ON SHEET 3 OF 5 SPECIFICATIONS
 ON THE RESUBMITTAL.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-04-30 Cont ID  
Sent By adavila Date 2007-04-30 Time 16:07 Rev Time 0.00
Received By adavila Date 2007-04-30 Time 10:49 Sent To I
Notes
2007-04-30 16:07:34PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-03-02 Cont ID  
Sent By adavila Date 2007-03-02 Time 16:40 Rev Time 0.00
Received By adavila Date 2007-03-02 Time 16:40 Sent To I
Notes
2007-03-02 16:45:20PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2.PROVIDE COPY OF RECORDED UNITY OF TITLE FOR THE
 FOLLOWING PARCELS: 74434309050050040 AND
 74434309050050030.
  
 3.PER SECTION 94-304(D)(2)(B), EVERY SWIMMING POOL
 SHALL BE ENCLOSED BY A FENCE OR SIMILAR STRUCTURE WHICH
 IS INSTALLED TO OBSTRUCT ACCESS BY PERSONS OTHER THAN
 THE OWNERS OR OCCUPANTS OF THE RESIDENCE WITHIN WHICH A
 SWIMMING POOL IS LOCATED.
 A.PLEASE SHOW ON THE SURVEY LOCATION OF FENCE.
  
 4.A FENCE PERMIT APPLICATION SHALL BE SUBMITTED PRIOR
 TO POOL PERMIT APPROVAL.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-27 Cont ID  
Sent By mmclean Date 2007-01-27 Time 09:42 Rev Time 0.00
Received By mmclean Date 2007-01-22 Time 16:12 Sent To I
Notes
2007-01-22 16:14:28DENIED,
 1. THE POOL LAYOUT ON THE SURVEYS AND POOL PLANS DOES
 NOT MATCH.POOL PLANS SHOWS THE SPA, WHICH IS 14'11"
 FROM REAR PROPERTY LINE AND SURVEY SHOWS THE POOL AT
 17'-2".
 2. SHALL MOVE THE POOL EQUIPMENT FROM PROPOSED
 LOCATION, DOES NOT MEET THE REQUIRED SETBACK FOR POOL
 EQUIPMENT.
 3. THE POOL EQUIPMENT SHALL NOT BE CLOSER THAN 11FT
 FROM THE REAR PROPERTY LINE. SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE THAN FOUR FEET
 INTO A SETBACK.
  
 NOTE: 35TH STREET IS CONSIDERED THE FRONT OF PROPERTY
 (SHORTESS PORTION OF THE LOT) AND POINSETTIA AVE
 (PLATTED DIXIE HWY) IS THE CONSIDERED THE CORNER/SIDE
 PROPERTY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720