Plan Review Stops For Permit 07010804 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-05-02 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-05-02 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-05-02 |
Time |
12:15 |
Sent To |
PC |
|
Notes |
2007-05-02 12:36:50 | BUILDING PROVISO: | | TO BE IN PLACE AT C.O.: | | | | 1) 424.2.17.1 OUTDOOR SWIMMING POOLS. | | OUTDOOR SWIMMING POOLS SHALL BE PROVIDED | | WITH A BARRIER COMPLYING WITH | | 424.2.17.1.1 THROUGH 424.2.17.1.14. | | | | 424.2.17.1.5 CHILD SAFETY BARRIER | | ASTM D5034 100 LB TENSILE STRNGTH | | ASTM D3787 150 LB BALL BURST | | STRENGTH | | | | 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED. | | SPAS AND HEATED SWIMMING POOLS SHALL BE | | EQUIPPED WITH A COVER DESIGNED TO | | MINIMIZE HEAT LOSS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-03-07 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-03-07 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-03-07 |
Time |
15:52 |
Sent To |
PC |
|
Notes |
2007-03-07 16:58:36 | BUILDING PLAN REVIEW | | PERMIT: 07010804 | | ADD: 3601 POINSETTIA AVE | | CONT: CRAFTMASTER CUSTOM POOLS | | TEL: (561)278-3513 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 2ND | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2)FROM PRIVIOUS REVIEW. THE STRUCTURAL REVIEW IS OK, | | HOWEVER, THE ZONING , PLUMBING AND ELECTRIC | | REQUIREMENTS SHALL BE ADDRESSED BEFORE A PERMIT CAN BE | | ISSUED. | | | | 3)THE ELECTRICAL PERMIT IS NOT APPLIED AT THIS TIME, | | WHICH MEANS THE ROUGH ELECTRICAL WORK CANNOT BEGIN | | UNTIL A PERMIT IS ISSUED. | | NOTE: FBC 108.4 ANY PERSON WHO COMMENCES ANY WORK ON A | | BUILDING, STRUCTURE, ELECTRICAL, GAS, MENCANICAL OR | | PLUMBINB SYSTEM BEFORE OBTAINING THE BUILDING'S | | OFFICIAL' APPROVAL OR THE NECESSARY PERMITS SHALL BE | | SUBJECT TO PENALTY OF 300 PERCENT OF THE USUAL PERMIT | | FEES IN ADDITION TO THE REQUIRED PERMIT FEES, AS SET IN | | APPROVED SCHEDULE OF FEES. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-02-09 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-02-09 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-02-09 |
Time |
06:41 |
Sent To |
|
|
Notes |
2007-02-09 10:19:04 | BUILDING PLAN REVIEW | | PERMIT: 07010804 | | ADD: 3601 POINSETTA AVE | | CONT:CRAFTMAN CUSTOM POOLS | | TEL: (561)278-3515 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | 1)THE STRUCTURAL REVIEW IS OK AT THIS TIME, HOWEVER, | | THE ZONING PLUMBING AND ELECTRIC REQUIREMENTS SHALL BE | | ADDRESSED BEFORE A PERMIT CAN BE ISSUED. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2007-04-19 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-04-19 |
Time |
12:22 |
Rev Time |
0.25 |
Received By |
btrobaug |
Date |
2007-04-19 |
Time |
12:21 |
Sent To |
Z |
|
Notes |
2007-04-19 12:22:42 | | | | | PLAN SHOWS "ELECTRIC BY OTHERS, AND NO ELEC PERMIT # | | ASSIGNED./WRT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2007-03-07 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-03-07 |
Time |
12:35 |
Rev Time |
0.25 |
Received By |
btrobaug |
Date |
2007-03-07 |
Time |
12:28 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
N |
Date |
2007-01-31 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-01-31 |
Time |
16:29 |
Rev Time |
0.25 |
Received By |
btrobaug |
Date |
2007-01-31 |
Time |
15:34 |
Sent To |
P |
|
Notes |
2007-01-31 16:30:20 | | | | | NO ELECTRICAL PLANS SUBMITTED./WRT. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
N |
Date |
2007-04-19 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-04-19 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-04-19 |
Time |
12:06 |
Sent To |
E |
|
Notes |
2007-04-19 12:08:18 | CONTRACTOR INFORMATION | | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | BEFORE FINAL POOL INSPECTION. | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2007-02-05 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-02-05 |
Time |
13:52 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-02-05 |
Time |
13:52 |
Sent To |
B |
|
Notes |
2007-02-05 13:56:32 | CONTRACTOR INFORMATION | | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | BEFORE FINAL POOL INSPECTION. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2007-05-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-01 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-01 |
Time |
10:22 |
Sent To |
B |
|
Notes |
2007-05-01 10:22:23 | TO "MJACOBS" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-04-06 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2007-04-06 |
Time |
17:34 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2007-04-06 |
Time |
17:34 |
Sent To |
G |
|
Notes |
2007-04-06 17:35:05 | TO MIKE PERSON |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-03-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-05 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-05 |
Time |
11:04 |
Sent To |
E |
|
Notes |
2007-03-05 11:04:54 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-02-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-23 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-23 |
Time |
15:29 |
Sent To |
Z |
|
Notes |
2007-02-23 15:30:11 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-01-31 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-31 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-31 |
Time |
11:27 |
Sent To |
E |
|
Notes |
2007-01-31 11:28:10 | TO "E" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2007-02-09 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-18 |
Time |
10:07 |
Sent To |
|
|
Notes |
2007-01-18 10:07:35 | TO "Z" BOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2007-04-19 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-04-19 |
Time |
12:05 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2007-04-19 |
Time |
12:05 |
Sent To |
G |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-03-07 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-03-07 |
Time |
13:45 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2007-03-07 |
Time |
13:44 |
Sent To |
B |
|
Notes |
2007-03-07 14:07:07 | DENIED 2ND TIME | | REFERENCE: FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING | | POOLS: | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, | | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING | | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT | | MADE ON PREVIOUS REVIEWS. | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM | | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. | | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE | | PREVIOUS REVIEW NOTES. | | | | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR | | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS | | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER | | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. | | | | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL | | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. | | | | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN | | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW | | COMMENT MAY HAVE BEEN FULLY ADDRESSED. | | | | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF | | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. | | | | 1) ** NO**,FBC-2004 SEC. 424.2.6.6.5, OR FBCR-2004 | | SEC. R4101.6.6.5 WHERE | | PROVIDED, THE VACUUM OR PRESSURE CLEANER | | FITTING SHALL BE LOCATED AT LEAST 6" AND | | NOT GREATER THAN 12" BELOW THE MINIMUM | | OPERATING WATER LEVEL OR AS AN | | ATTACHMENT TO THE SKIMMER. | | NOTE: PLEASE PROVIDE A MANUFACTURER CUT SHEET OR | | INDICATE THE MAKE AND MODEL NUMBER ON THE RESUBMITTED | | PRINTS. PLEASE REFERENCE THE ATTACHED EXAMPLE OF VACUUM | | OR PRESSURE CLEANER FITTING WITH THE ABOVE | | INFORMATION. | | | | 2) **NO**,FBC-2004 SEC. 424.6.6 OR FBC-2004 | | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT | | PROTECTION FOR SUCTION INLETS. PLEASE | | SUBMIT AN ENGINEERED TABLE FOR "VENT | | PIPE MAXIMUM LENGTH" INDICATING PUMP | | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH | | OF THE 1" PVC VENT PIPE, FROM | | WHERE IT STARTS TO WHERE IT ENDS UP, | | COMPLYING WITH THE THREE SECOND RELEASE. | | NOTE: PLEASE REFERENCE THE ATTACHED EXAMPLE OF AN | | 1-1/2" ATMOSPHERIC VENT TABLE COMPLYING WITH 3 SECOND | | RELEASE. PLEASE SUBMIT A TABLE WITH 1" VENT COMPLYING | | WITH 3 SECOND RELEASE ON THE RESUBMITTAL. | | | | 3) OK | | | | **IMPORTANT INFORMATION | | IN ORDER TO EXPIDITE PLAN REVIEW: | | WHEN RESUBMITTING, PLEASE REPLACE ONLY SHEETS WHICH | | HAVE CHANGED AND PROVIDE ONE COPY | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | ONLY. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-02-05 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-02-05 |
Time |
13:39 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2007-02-05 |
Time |
13:39 |
Sent To |
G |
|
Notes |
2007-02-05 13:52:17 | DENIED | | REFERENCE: FBC-2004 SECTIONS 424.2 AND R4101 SWIMMING | | POOLS | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING | | PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | 1) FBC-2004 SEC. 424.2.6.6.5, OR | | FBCR-2004 SEC. R4101.6.6.5 WHERE | | PROVIDED, THE VACUUM OR PRESSURE CLEANER | | FITTING SHALL BE LOCATED AT LEAST 6" AND | | NOT GREATER THAN 12" BELOW THE MINIMUM | | OPERATING WATER LEVEL OR AS AN | | ATTACHMENT TO THE SKIMMER. | | NOTE: PLEASE PROVIDE A MANUFACTURER CUT SHEET OR | | INDICATE MAKE AND MODEL NUMBER ON RESUBMITTED PRINTS. | | | | 2) FBC-2004 SEC. 424.6.6 OR FBC-2004 | | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT | | PROTECTION FOR SUCTION INLETS. PLEASE | | SUBMIT AN ENGINEERED TABLE FOR "VENT | | PIPE MAXIMUM LENGTH" INDICATING PUMP | | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH | | OF THE 1" PVC VENT PIPE, FROM | | WHERE IT STARTS TO WHERE IT ENDS UP, | | COMPLYING WITH THE THREE SECOND RELEASE. | | | | 3) SHEET 5 OF 5 GENERAL NOTES NUMBER 18: PER FBC-2004 | | SECTION 424.2.20 AND R4101.20, PLEASE INDICATE THE POOL | | AND SPA TURN OVER TIME ON SHEET 3 OF 5 SPECIFICATIONS | | ON THE RESUBMITTAL. | | | | **********IMPORTANT INFORMATION | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | PLEASE REPLACE ONLY SHEETS | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | ONLY. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2007-04-30 |
|
|
Cont ID |
|
Sent By |
adavila |
Date |
2007-04-30 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
adavila |
Date |
2007-04-30 |
Time |
10:49 |
Sent To |
I |
|
Notes |
2007-04-30 16:07:34 | PER ERIC SCHNEIDER, PRINCIPAL PLANNER. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2007-03-02 |
|
|
Cont ID |
|
Sent By |
adavila |
Date |
2007-03-02 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
adavila |
Date |
2007-03-02 |
Time |
16:40 |
Sent To |
I |
|
Notes |
2007-03-02 16:45:20 | PLANNING AND ZONING DEPARTMENT | | | | ***FAILED*** | | | | 1.PROVIDE RESPONSE TO COMMENTS IN WRITING. | | | | 2.PROVIDE COPY OF RECORDED UNITY OF TITLE FOR THE | | FOLLOWING PARCELS: 74434309050050040 AND | | 74434309050050030. | | | | 3.PER SECTION 94-304(D)(2)(B), EVERY SWIMMING POOL | | SHALL BE ENCLOSED BY A FENCE OR SIMILAR STRUCTURE WHICH | | IS INSTALLED TO OBSTRUCT ACCESS BY PERSONS OTHER THAN | | THE OWNERS OR OCCUPANTS OF THE RESIDENCE WITHIN WHICH A | | SWIMMING POOL IS LOCATED. | | A.PLEASE SHOW ON THE SURVEY LOCATION OF FENCE. | | | | 4.A FENCE PERMIT APPLICATION SHALL BE SUBMITTED PRIOR | | TO POOL PERMIT APPROVAL. | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-01-27 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2007-01-27 |
Time |
09:42 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2007-01-22 |
Time |
16:12 |
Sent To |
I |
|
Notes |
2007-01-22 16:14:28 | DENIED, | | 1. THE POOL LAYOUT ON THE SURVEYS AND POOL PLANS DOES | | NOT MATCH.POOL PLANS SHOWS THE SPA, WHICH IS 14'11" | | FROM REAR PROPERTY LINE AND SURVEY SHOWS THE POOL AT | | 17'-2". | | 2. SHALL MOVE THE POOL EQUIPMENT FROM PROPOSED | | LOCATION, DOES NOT MEET THE REQUIRED SETBACK FOR POOL | | EQUIPMENT. | | 3. THE POOL EQUIPMENT SHALL NOT BE CLOSER THAN 11FT | | FROM THE REAR PROPERTY LINE. SEC 94-303 MECHANICAL/POOL | | EQUIPMENT/GENERATOR MAY NOT PROJECT MORE THAN FOUR FEET | | INTO A SETBACK. | | | | NOTE: 35TH STREET IS CONSIDERED THE FRONT OF PROPERTY | | (SHORTESS PORTION OF THE LOT) AND POINSETTIA AVE | | (PLATTED DIXIE HWY) IS THE CONSIDERED THE CORNER/SIDE | | PROPERTY. | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|