Plan Review Details - Permit 07010773
Plan Review Stops For Permit 07010773
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-05 Cont ID  
Sent By jwitmer Date 2007-03-05 Time 10:49 Rev Time 12.22
Received By jwitmer Date 2007-03-05 Time 10:49 Sent To  
Notes
2007-03-05 13:31:40BUILDING PLAN REVIEW
 PERMIT: 07010773
 ADD: 326 FERN ST
 CONT: ALONSO & ASSOCIATES, INC
 TEL: (561)253-5350
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FORCOMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 4)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 5)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 6) SHEET A-1.0.0 EXIT REQUIREMENTS ARE ONLY REFRENCED
 UNDER THE NFPA NOT THE REQUIREMENTS OF THE 2006
 FBC-BUILDING AND THE 2006 EXISTING BUILDING CODE.
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIEMENTS, THE MOST RESTRICTIVE
 SHALL GOVERN.
 WHERE THERE IS A CONFLICT BETWEEN A GENERAL REQUIEMENT
 AND A SPECIFIC REQUIREMENT, THE SPECIFIC REQUIREMENT
 SHALL BE APPLICABLE.
  
 7) A-1.0.0 PLANS INDICATE A TYPE I BUILDING, NO
 INDICATION AS TO THE FIRE RESISTANCY "AOR B".
  
 8) THIS REVIEW WILL ALSO ENCORPORATE THE 2004 EXISTING
 BUILDING CODE CHAPTER 8 CHANGE OF OCCUPANCY.
 THE PLANS REFLECT A CHANGE IN OCCUPANCY ENVOKING
 CHAPTER 8SECTION 812.4.1 MEANS OF EGRESSHAZARD
 CATEGORIES IN REGAARDS TO LIFE SAFETY AND MEANS OF
 EGRESS SHALL BE IN ACCORDANCE WITH TABLE 812.4.1. THE
 BUILDING IS GOING TO A MORE RESTRICITVE HAZARD
 CATEGORY. SEE 812.4.1.1.
 812.4.1.1 WHEN A CHANGE OF OCCUPANCY GROUP IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 812.4.1 THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FBC-BUILDING. TABLE
 1016.1 REQUIRES THE EXIT ACCESS CORRIDORS TO BE 1HR
 RATED WHEN AN OCCUPANT LOAD OF GREATER THAN 10.
  
 8A) THE ISSUE OF FIRE RATED CORRIDORS NEEDS TO BE
 ADDRESSED, THE INDEX INDICATES SHEET A-4.2.8 WALL TYPES
 NO SUCH DETAILS ARE FOUND ON THIS SHEET.
  
 8B) THIS BUILDING BEING A 6 STORY BUILDING DOES REQUIRE
 ELEVATOR LOBBIES FOUND IN 707.14.1.
 707.14.1 ELEVATOR LOBBY.
 ELEVATORS OPENING INTO A FIRE-RESISTANCE-RATED CORRIDOR
 AS REQUIRED BY SECTION 1016.1 SHALL BE PROVIDED WITH AN
 ELEVATOR LOBBY AT EACH FLOOR CONTAINING SUCH A
 CORRIDOR. THE LOBBY SHALL SEPARATE THE ELEVATORS FROM
 THE CORRIDOR BY FIRE PARTITIONS AND THE REQUIRED
 OPENING PROTECTION. ELEVATOR LOBBIES SHALL HAVE AT
 LEAST ONE MEANS OF EGRESS COMPLYING WITH CHAPTER 10 AND
 OTHER PROVISIONS WITHIN THIS CODE.
  
 9A) SHEET A-1.1.1 PLANS INDICATE AN ACCESSIBLE DOOR AS
 32" SEE FIGURE 24(B) AS TO WHERE THE MEASUREMENT FOR
 THE 32" IS TO TAKE PLACE, FROM THE FACE OF THE DOOR TO
 THE OTHER DOOR JAMB OR DOOR STOP.
  
 9B) SHEET A-1.1.1 PLANS INDICATE FLORIDA ACCESSIBILTY
 CODE- LATEST EDITION, PLEASE CORRECT TO THE 2004 WITH
 2005, 2006 REVISIONS.THE SECOND LINE IN ON THE
 ACCESSIBILTY NOTES INDICATES THE 2002 ACCESSIBILITY
 CODE.
  
 9C) SHEET A-2.2.1 THIS IS A PLAN OF THE ADDITIONAL
 PARKING ACROSS THE STREET FOR THE CONDOMINIUMS, THERE
 QRE AN ADDITIONAL 90 PARKING SPACES LOCATED IN THE LOT
 ACROSS FROM THE BUILDING ITSELF BUT ONLY ONE ACCESSIBLE
 PARKING SPACE, AN ADDITIONAL 3 ACCESSIBLE SPACES ARE
 REQUIRED. 11-4.1.2(5)(A).
  
 10) THE EXISTING SITE PLAN AND PLANS FOR THE 3RD, 4TH &
 5TH FLOOR INDICATE A SKYBRIDGE, PLANS ALSO INDICATE
 THAT THE WALL WIL BE BLOCKED UP, BLOCKING ACCESS FROM
 THE OTHER BUILDING. IS THIS BRIDGE TO BE REMOVED? IF
 NOT, WHO WILL MAINTAIN THE BRIDGE TO KEEP UP THE
 MAINTENANCE?
  
 11) SHEET A-4.1.1 PLEASE PROVIDE WHERE THE NORTH
 PROPERTY LINE WOULD BE IN REGARDS TO THE BUILDING FOR
 THE NORTH WALL. TABLE 704.8 FBC-B. THE EXTERIOR DOORS
 CAN NOT SWING OVER THE PROPERTY LINE. 3202.2DOORS AND
 WINDOWS SHALL NOT PROJECT OVER THE PROPERTY LINE INTO
 THE RIGHT-OF-WAY.
  
 12) SHEET A-4.1.2 IT APPEARS TO BE A TYPO THE EAST SIDE
 OF THE BUILDING APPEARS TO HAVE WORK ON THE WINDOWS
 MARKER# 14 BUT IN THE KEY NOTES THERE IS NO NUMBER 14
 BUT (2) NUMBER 13'S.
  
 13) SHEET A-1.0.0 INDICATES THIS IS A FULLY FIRE
 SPRINKLERED BUILDING, BUT NO FIRE SPRINKLER PLANS WERE
 SUBMITTED FOR TABLE 601 AND TABLE 704.8 FL BUILDING
 CODE. EXISTING BUILDING CODE 812.4.3.3EXCEPTION# 3
 WHERE EXTERIOR OPENING PROTECTIVES ARE REQUIRED, AN
 AUTOMATIC SPRINKLER SYSTEM THROUGHOUT MAY BE
 SUBSTITUTED FOR OPENING PROTECTIVES. PLEASE PROVIDE THE
 FIRRE SPRINKLER PLANS WITH CALCULATIONS.
  
 14)THERE APPEARS TO BE A DESCREPANCY BETWEEN A-3.1.1
 AND A-4.2.1. IT WOULD APPEAR THE TRASH ROOM WOULD BE ON
 THE GRADE LEVEL FLOOR, ALTHOUGH THE GRADE LEVEL PLAN
 A-4.2.1 STATES THE TRASH ROOM BELOW. PLEASE CLARIFY.
  
 15) SHEET A-4.2.1
  
 15A) THE STAIR TOWER# 2 INDICATES AN EXTENSION OF THE
 STAIRWELL TO THE EXTERIOR OF THE BUILDING. THIS
 EXTENSION OR EXIT PASSAGE WAY REQUIRES A 2HRFIRE
 RATING JUST AS THE REMAINDER OF THE STAIRWELL, BEING
 OVER 4 STORIES IN HEIGTH. LEASE SEE 812.4.4.EBC
 ENCLOSURES FOR VERTICAL SHAFTS, DOORS WILL REQUIRE 1
 1/2 HR PROTECTIVES.THEREDOESN'T APPEAR TO BE A DOOR
 SCHEDULE , PLEASE PROVIDE ADOOR SHCEDULE .
  
 15B) STAIR TOWER# 1 ALSO WILL NEED TO INDICATE WALL AND
 DOOR RATINGS, 812.4.4EXISTING BUILDING CODE.
  
 15C) THE FRENCH DOORS AT STAIR TOWER # 1 APPEAR TO BE A
 PAIR OF 30" DOORS, EBC 812.5 EXISTING BUILDINGS OR
 PORTIONS THERE OF THAT UNDER GO A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE FBC,
 BUILDING.
  
 15D)TO THE NORTH OF THE MAIN LOBBY THERE IS A MENS
 RESTROOM AND NORTH OF THE TOLIETS A EXISTING STAIR
 GOING NOWHERE A WALL BLOCKS THEM OFF?
  
 15E) TRASH ROOM IS INDICATED WITH A DOOR 7-A LOUVERED
 DOORS, FIRST CAN'T CROSS THE PROPERTY LINE AND SECOND
 REQUIRE FIRE RATED DOORS. SEE EBC 812.4.4.1.
 VERTICAL SHAFTS SHALL BE DESIGNED TO THE FL BUILD
 CODE.
  
 15F) NEW STAIRWELL TO THE BASEMENT AT THE NORTH END OF
 THE BUILDING, NOTE# 18 INDICATES NEW 1 HR RATED BLOCK
 WALL, PROVIDE INFORMATION FOR THE BLOCK WALL TO FLOOR
 SLAB TRANSITION. FBC 713.1.
  
 16) A-4.2.2
  
 16A) TRASH CHUTE REQUIRES A VESTIBULE,707.13.3 REFUSE
 AND LAUNDRY CHUTE ACCESS ROOMS.
 ACCESS OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS COMPLETELY ENCLOSED BY
 CONSTRUCTION THAT HAS A FIRE-RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR AND OPENINGS INTO THE ACCESS ROOMS
 SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN ? HOUR AND SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE.
  
 16B) REFUSE CHUTE ENCLOSURES EBC 812.4.4.3 OTHER
 VERTICAL SHAFTSSHALL BE ENCLOSED AS REQUIRED BY THE
 FBC, BUILDINGFBC 707.4 SHAFT ENCLOSURES 2HR FOR FOUR
 STORIES OR MORE.
  
 16C) 707.13.1 REFUSE AND LAUNDRY CHUTE ENCLOSURES.
 A SHAFT ENCLOSURE CONTAINING A REFUSE OR LAUNDRY CHUTE
 SHALL NOT BE USED FOR ANY OTHER PURPOSE AND SHALL BE
 ENCLOSED IN ACCORDANCE WITH SECTION 707.4 . OPENINGS
 INTO THE SHAFT, INCLUDING THOSE FROM ACCESS ROOMS AND
 TERMINATION ROOMS, SHALL BE PROTECTED IN ACCORDANCE
 WITH THIS SECTION AND SECTION 715 . OPENINGS INTO
 CHUTES SHALL NOT BE LOCATED IN EXIT ACCESS CORRIDORS.
 OPENING PROTECTIVES SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE ACTUATION OF A SMOKE
 DETECTOR INSTALLED IN ACCORDANCE WITH SECTION 907.10 ,
 EXCEPT THAT HEAT-ACTIVATED CLOSING DEVICES SHALL BE
 PERMITTED BETWEEN THE SHAFT AND THE TERMINATION ROOM.
  
 16D) PROVIDE INFORMATION ON THE PRE-ENGINEERED METAL
 BALCONIES, ADDITIONAL INFORMATION REQUIRED 106.1.2*
  
 16E) PROVIDE CALCULATIONS FOR:1607.7.1.1 CONCENTRATED
 LOAD.
 HANDRAIL ASSEMBLIES AND GUARDS SHALL BE ABLE TO RESIST
 A SINGLE CONCENTRATED LOAD OF 200 POUNDS (0.89 KN),
 APPLIED IN ANY DIRECTION AT ANY POINT ALONG THE TOP,
 AND HAVE ATTACHMENT DEVICES AND SUPPORTING STRUCTURE TO
 TRANSFER THIS LOADING TO APPROPRIATE STRUCTURAL
 ELEMENTS OF THE BUILDING. THIS LOAD NEED NOT BE ASSUMED
 TO ACT CONCURRENTLY WITH THE LOADS SPECIFIED IN THE
 PRECEDING PARAGRAPH.
  
 17)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 18)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS ,FIXED, STOREFRONT
 B) WINDOWS, OPERTABLE
 C) MULLIONS
 D) GLAZED DOORS SWING, SLIDING
 E)DOORS HOLLOW CORE METAL
 F) ROOFING ASSEMBLIES
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 19)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 20)PLEASE PROVIDE THE FOLLOWING INFORMATION FOR FLAT
 ROOF
 SYSTEMS BEING REPLACED., NOT INCOMPLIANCE WITH THE
 FOLLOW ITEMS:
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 __X_ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 _X__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 _X__THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 21)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-30 Cont ID  
Sent By dpalmer Date 2007-01-30 Time 16:48 Rev Time 0.00
Received By dpalmer Date 2007-01-30 Time 08:35 Sent To  
Notes
2007-01-30 16:51:49**** UNSAT ****
  
 *** IMPORTANT***
 * PLEASE KNOW THAT BASED ON THE COMMENTS BELOW AND
 PLANS NOT BEING COMPLETE AT THIS TIME, WHEN PLANS ARE
 RESUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS MADE
 WHICH WERE NOT MADE ON THIS REVIEW.
 ** PLEASE ALSO KNOW THAT THIS IS A CHANGE IN OCCUPANCY
 WHICH WILL REQUIRE TECHNICAL CODE COMPLIANCE FOR THE
 CURRENT CODES AND WELL AS OTHER REQUIREMENTS FOR CODE
 COMPLIANCE FOR BUILDING, FIRE ETC.
 THERE ARE A SUBSTANTIAL AMOUNT OF ITEMS WHICH CAN NOT
 BE REVIEWED AT THIS TIME.
  
 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT
 CORRECT.
 PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN
 OCT 1ST OF 2005. PLEASE ALSO SEE THAT AS OF DECEMBER
 8TH, 2006 THE CODES CHANGED TO THE 2006 REVISIONS TO
 THE 2004 FBC. PLEASE SEE THIS INCLUDES ALL MECHANICAL,
 PLUMBING BUILDING ETC.
 PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO
 ADOPTED THE NEW 2005 NFPA-70 (NEC).
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL
 COVE SHEET AND ELECTRICAL PLANS AT A MINIMUM.
 2005 NFPA-70, 2002 NFPA-72, 2003 NFPA-20, 2003
 NFPA-101, 2003 NFPA-1.
  
 ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY
 ALSO BE STATED TO BE DONE, THIS IS FOR ELECTRICAL
 REVIEW ONLY.
  
 2) NOTE: PLEASE SEE THAT THE BASE ELECTRICAL PLANS
 SHALL INDICATE THE MINIMUM LEVELS FOR ALL HORNS,
 STROBES, OR HORN/STROBE DEVICES AS REQUIRED UNDER FBC
 2004 11-4.28.1,.2 AND .3(4). THE PLANS NEED TO INDICATE
 THESE DEVICES ON THE SYMBOL LEGENDS AND CORRELATE WITH
 PLANS.
 PLEASE BE SURE ALL MINIMUM LEVELS AS REQUIRED ARE
 INDICATED.
 PLEASE SEE NO FIRE ALARM PLANS AND FIRE SPRINKLER PLANS
 WERE SUBMITTED WHICH WILL BE REQUIRED FOR THE BASE
 BUILDING PROTECTION AND IS REQUIRED TO BE SUBMITTED
 WITH MAIN BUILDING PLANS FOR REVIEW OF THESE REQUIRED
 ITEMS
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 3) NOTE: PLEASE SEE COMMENTS POSSIBLY FROM ZONING AND
 BUILDING REVIEW WITH RESPECT TO PARKING AND REQUIRED
 MINIMUM LIGHTING LEVELS AND LOCATIONS OF PARKING.
 ZONING MAY COMMENT BASED ON DIVISION 4, DMP 86294. (NOT
 AN ELECTRICAL REQUIREMENT, HOWEVER WILL AFFECT THE
 ELECTRICAL PLANS.
  
 4) NOTE: PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION
 FOR ANY SITE LIGHTING POLES. PLEASE ALSO BE SURE THE
 INFORMATION PROVIDED SHALL INCLUDE THE EFFECTIVE
 PROJECTED AREA (EPA) OF THE FIXTURE. PLEASE KNOW THAT
 THE MINIMUM WIND LOAD FOR POLES SHALL BE STATED ON
 PLANS AND IF THE INFORMATION FOR THE POLE CALCULATIONS
 IS NOT KNOWN AT THIS TIME BASED ON WHETHER OR NOT THE
 MANUFACTURE HAS BEEN CHOSEN, THIS MAY BE SET UP AS A
 *PROVISO*, HOWEVER THE MINIMUM WIND SPEEDS SHALL BE ON
 PLANS.
 PLEASE BE SURE TO INCLUDE ANY LIGHTING CIRCUITING FROM
 HOUSE PANELS ETC.
 PLEASE KNOW THAT ANY PARKING ACROSS THE STREET WHICH IS
 LOCATED ON ANOTHER LEGAL PROPERTY MAY NOT BE FED FROM
 THIS BUILDING ELECTRICAL SERVICE.
 ** PLEASE SEE FBC 2004.
 FBC ADMIN SECTION 106.1.2
  
 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR
 BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2.
  
 6) NOTE: PLEASE SUBMIT MINIMUM ENERGY CALCULATIONS AND
 PERFORMANCE CALCULATIONS BASED ON THE AREA BEING DONE.
 PLEASE SEE ALL AREAS FOR COMMON AREAS WHICH ARE NOT
 PART OF THE RESIDENTIAL SHALL BE SHOWN AND COMPLY WITH
 THE 2006 REVISIONS TO THE 2004 FBC CHAPTER 13.PLEASE
 SEE 13-415.1.AB.1 AND 13-415.2.
 PLEASE SEE THAT ALL ELECTRICAL AS SHOWN ON PLANS SHALL
 BE INCLUDED IN THE ENERGY CALCULATIONS AS WELL AS THE
 ELECTRICAL IN ENERGY CALCULATIONS NEEDS TO BE SHOWN ON
 PLANS.(PLEASE SEE ELEC ON CALCS NOT ON PLANS)
 PLEASE SEE ALL RESIDENTIAL AREAS ARE STILL FIGURED INTO
 ENERGY CALCULATIONS EVEN IF THOSE AREAS ARE EXEMPT FROM
 AUTOMATED CONTROL DEVICES.
 * PLEASE KNOW THESE SHALL BE SIGNED, DATED AND SEALED,
 BY THE ENGINEER OF RECORD. 13-103.1.1.1
  
 7) NOTE: PLEASE SEE THAT LIGHTING CONTROLS ARE REQUIRED
 FOR AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE SEE FBC
 2004 (2006 REVISIONS) 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE ALL COMMON AREAS AND SEPARATE SPACES
 CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS. PLEASE
 SEE THIS INCLUDES ALL FLOORS AND LEVELS.
  
 8) NOTE: PLEASE SEE MISSING DEDICATED EQUIPMENT ROOM
 FOR THE ELEVATOR. PLEASE SEE THE NEC 620. 620.22,
 620.23, 620.24 AND 620.51.
 PLEASE SEE MISSING THE DEDICATED CIRCUITS FOR THIS ROOM
 AND OTHER ELEVATOR RELATED LIGHTING ETC WHICH MAY NOT
 FEED ANY OTHER AREAS. PLEASE SEE PLANSDO NOT INDICATE
 THESE CIRCUITS AT THIS TIME AND AS COMPLETE CODE
 COMPLIANCE FOR ELEVATOR ROOMS, CONTROLS, DETECTION
 DEVICES ETC WILL BE REQUIRED TO THE MEET THE CURRENT
 CODE IF NOT ALREADY.
 PLEASE ALSO SEE THE STATE ELEVATOR CODE.
 PLEASE ALSO PROVIDE MORE INFORMATION FOR THE ELEVATOR
 MOTOR ITSELF. PLEASE VERIFY THE CONDUCTORS ETC. 620.11,
 620.12 ETC.
  
 9) NOTE:PLEASE SEE MISSING CIRCUITING ON SOME COMMON
 AREAS ELECTRICAL FIXTURES AND DEVICES. PLEASE COMPLETE
 ALL CIRCUITING ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULE(S).
 PLEASE SEE COMMENTS LATER WITH RESPECT TO MANY PANEL
 SCHEDULES WHICH WERE NOT SUBMITTED FOR REVIEW.
 408.4, 310.16,ETC
 PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT
 LIGHTS.
  
 10) NOTE: PLEASE PLACE ALL FIXTURE DESIGNATIONS ON
 PLANS AND CORRELATE WITH THE SUBMITTED FIXTURE LEGEND.
 PLEASE KNOW THAT MANY AREAS CAN NOT BE VERIFIED AT THIS
 TIME.
 FBC 106.1.2.
  
 11) NOTE: PLEASE SEE MISSING EMERGENCY BATTERY BACK UP
 LIGHTS REQUIRED IN STAIRS, ELEVATOR EQUIPMENT ROOM, AND
 ELECTRICAL EQUIPMENT ROOMS. PLEASE SEE OTHER ROOMS FOR
 GENERATOR, FIRE PUMP ETC WILL ALSO REQUIRE THIS ,
 HOWEVER PLEASE SEE OTHER COMMENTS FOR RELOCATION OF
 THESE WHICH WILL AFFECT THE LOCATIONS.
 NFPA-101 7.8, 7.9
 NFPA-70 700.16, AND 700.12E.
  
 12) NOTE: PLEASE SUBMIT AND PROVIDE PHOTO-METRICS FOR
 ALL EGRESS PATHS.
 PLEASE SHOW COMPLETED ELECTRICAL PLANS FOR ALL EGRESS
 STAIRS AND PATHS. PLEASE SHOW ALL EXISTING MEETING THE
 CURRENT CODES OR NEW TO BE INSTALLED. PLEASE SEE
 CIRCUITING AND TYPE OF FIXTURES ARE ALSO REQUIRED.
 PLEASE SEE MINIMUM LEVELS UNDER NORMAL AND UNDER
 EMERGENCY ARE REQUIRED FOR ALL EGRESS PATHS. THIS WOULD
 INCLUDE ANY EGRESS FROM BASEMENT TO PUBLIC RIGHT OF WAY
 AND EGRESS OUT OF BUILDING TO PUBLIC RIGHT OF WAY.
 PLEASE SEE ANY STAIR AREAS OUTSIDE WHICH HAS NOT PLACED
 THE OCCUPANT TO THE PUBLIC RIGHT OF WAY WILL REQUIRE
 EMERGENCY ILLUMINATION AT THESE LOCATIONS. PLEASE SEE
 NFPA-101 7.8.1.3, 7.9.2.2.
  
 13) NOTE: PLEASE SEE RISER AS SUBMITTED IS NOT COMPLETE
 AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE. PLEASE KNOW COMPLETE
 CODE COMPLIANCE MUST BE MET. PLEASE SEE THERE ARE PANEL
 SCHEDULES FOR NEW PANELS WHICH WERE NOT SUBMITTED OR
 SHOWN. PLEASE SUBMIT ALL INFORMATION FOR EXISTING
 SERVICE AND WHAT ALL THIS EXISTING EQUIPMENT IS
 FEEDING. PLEASE BE SURE TO SEE COMMENTS WITH RESPECT TO
 FIRE PUMP AND EPSS.
 PLEASE SEE RISER SHOWS A NEW MDP ALSO, HOWEVER NOT
 PANEL SCHEDULE WAS SUBMITTED OR SHOWN. PLEASE SEE OTHER
 ELECTRICAL PANELS FOR FUTURE USE WERE NOT SUBMITTED.
 PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH
 ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING,
 SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC
 RATINGS FOR ALL SERVICE EQUIPMENT ETC.
 ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70,
 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24,
 110.26 ETC.
 PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC.
  
 14) NOTE: PLEASE SEE NFPA-72 4.4.1 MORE SPECIFICALLY
 4.4.1.4.1, 4.4.1.4.2.1 AND .2.2.
 PLEASE INDICATE HOW THIS PROTECTION WILL BE PROVIDED
 FOR THE DEDICATE BRANCH CIRCUIT FOR THE FIRE ALARM
 CONTROL PANEL.
 ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE
 SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL
 PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS
 NOT ACCEPTABLE TO THIS AHJ.
 110.3, 90.4.
  
 16) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 SERVICE AND EACH OF THE PANELS AS BEING SHOWN EVEN
 THOSE BEING SET ASIDE FOR FUTURE USE. PLEASE SEE THAT
 NO LOAD CALCULATIONS WERE SUBMITTED FOR NEW SERVICE OR
 ANY EXISTING. PLEASE INDICATE LOAD SUMMARY FOR ALL OF
 THE SERVICES AND HOW THESE SIZES WERE DERIVED.
 PLEASE SEE NOTE #13 ABOVE AS THE SERVICE SIZE OR
 CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN
 NOT BE DETERMINED AT THIS TIME.
 PLEASE SEE ALL OF 220.(THERE ARE TOO MANY SECTIONS TO
 LIST)
 PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS
 LOADS AND LARGEST MOTORS LOADS AT 125%.
 FBC ADMIN SECTION 106.3.5.1.2, 106.1.2
  
 17) NOTE: PLEASE SEE NOTE ABOVE (#13) WHICH REQUEST THE
 AIC RATINGS FOR ALL EQUIPMENT. PLEASE BE SURE THESE
 CORRELATE WITH THE DIVISION SPEC SUBMITTED.
 106.1.2.
 NEC 110.9
  
 18) NOTE: PLEASE SEE 240.21C6 FOR MAIN DISCONNECTS OR
 MAIN CIRCUIT BREAKERS REQUIRED ON THE SECONDARY SIDE OF
 THE TRANSFORMERS CAN NOT BE VERIFIED AT THIS TIME.
 PLEASE ALSO SEE 408.36
  
 19) NOTE: PLEASE SEE NFPA-110 2002 CHAPTER 7 FOR
 COMPLIANCE FOR THE EPSS/ EMERGENCY GENERATOR. PLEASE
 SEE THERE ARE MANY ITEMS TO BE VERIFIED FOR BRING
 EXISTING UP TO CODE.
 A) PLEASE SEE 7.3.3 WHICH REQUIRES A MINIMUM OF 30FT
 CANDLES FOR ROOM. (ALSO PREVIOUS NOTE ABOVE FOR EM
 BATTERY BACK UP LIGHTING REQUIRED.
 B) PLEASE SEE THE LOCATION OF THE GENERATOR DOES NOT
 APPEAR IT CAN BE LOCATED IN THE BASEMENT BASED ON THE
 ELEVATION. PLEASE SEE 7.2.3*
 PLEASE SEE SOME OFTHE FOLLOWING TEXT IS EXTRACTED
 FROM THE CODE.
  
 A.7.2.3 EPSS EQUIPMENT SHOULD BE LOCATED ABOVE KNOWN
 PREVIOUS FLOODING ELEVATIONS WHERE POSSIBLE.
 A.7.2.4 WHEN INSTALLING THE EPSS EQUIPMENT AND RELATED
 AUXILIARIES, ENVIRONMENTAL CONSIDERATIONS SHOULD BE
 GIVEN, PARTICULARLY WITH REGARD TO THE INSTALLATION OF
 THE FUEL TANKS AND EXHAUST LINES, OR THE EPS BUILDING,
 OR BOTH.
 TO PROTECT AGAINST DISRUPTION OF POWER IN THE FACILITY,
 IT IS RECOMMENDED THAT THE TRANSFER SWITCH BE LOCATED
 AS CLOSE TO THE LOAD AS POSSIBLE. THE FOLLOWING ARE
 EXAMPLES OF EXTERNAL INFLUENCES:
 (1)NATURAL CONDITIONS
 (A)STORMS
 (B)FLOODS
 (C)EARTHQUAKES
 (D)TORNADOES
 (E)HURRICANES
 (F)LIGHTNING
 (G)ICE STORMS
 (H)WIND
 (I)FIRE
 (2)HUMAN-CAUSED CONDITIONS
 (A)VANDALISM
 (B)SABOTAGE
 (C)OTHER SIMILAR OCCURRENCES
 (3)MATERIAL AND EQUIPMENT FAILURES
 FOR NATURAL CONDITIONS, EPSS DESIGN SHOULD CONSIDER THE
 "100-YEAR STORM" FLOODING LEVEL OR THE FLOODING LEVEL
 PREDICTED BY THE SLOSH MODELS FOR A CLASS 4 HURRICANE.
 SLOSH STANDS FOR SEA, LAKE, OVERLAND, SURGES BY
 HURRICANES.
  
 THE ROOMS, SHELTERS, OR SEPARATE BUILDINGS HOUSING
 LEVEL 1 OR LEVEL 2 EPSS EQUIPMENT SHALL BE DESIGNED AND
 LOCATED TO MINIMIZE THE DAMAGE FROM FLOODING, INCLUDING
 THAT CAUSED BY THE FOLLOWING:
 (1)FLOODING RESULTING FROM FIRE FIGHTING
 (2)SEWER WATER BACKUP
 (3)SIMILAR DISASTERS OR OCCURRENCES
  
 C) PLEASE SEE THE MINIMUM CLEARANCE FOR ATS SWITCHES
 CAN NOT BE VERIFIED AT THIS TIME.
 D) PLEASE SEE 7.9.1 FOR FUEL SYSTEM REQUIREMENTS AS
 WELL AS NFPA-20 2003 SECTION 9.6.2.2 THE FUEL SUPPLY
 CAPACITY SHALL BE SUFFICIENT TO PROVIDE 8 HOURS OF FIRE
 PUMP OPERATION AT 100 PERCENT OF THE RATED PUMP
 CAPACITY IN ADDITION TO THE SUPPLY REQUIRED FOR OTHER
 DEMANDS.
 E) PLEASE SEE MANY ITEMS FOR THE EXISTING EMERGENCY
 SYSTEM CAN NOT BE VERIFIED. THE INFORMATION WHICH NEEDS
 TO BE SHOWN NEEDS TO BE PLACED ON PLANS AS IF THIS WAS
 A NEW BUILDING BEING CONSTRUCTED UNDER THE CURRENT
 CODES FOR THE ELECTRICAL AND EMERGENCY SYSTEMS. (EVEN
 IF SHOWN AS EXISTING MEETING THE CURRENT CODE).
  
 20) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE
 OF WORK WILL NEED TO BE ADJUSTED ONCE ALL REVIEWS ARE
 DONE AND PLANS ARE BROUGHT UP TO CODE.
 PLEASE SEE FBC 108.3 ADMIN SECTION.
  
 21) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE(S)
 SHALL BE SPECIFIC TO ALL AREAS/ROOMS AND SPACES IN
 WHICH THEY FEED. PLEASE SEE THE COMMENTARY SECTION OF
 THE 2005 NEC WHICH EXPLAINS THIS.PLEASE SEE THE
 REQUIREMENT THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.
 PLEASE BE SURE TO CORRELATE PLANS AND CIRCUITING SHOWN
 AT THIS TIME.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 22) NOTE: PLEASE SEE MISSING RECEPTACLES PER 210.52
 WHICH ARE REQUIRED FOR WALLS 2FT OR GREATER AND WITHIN
 6FT OF ANY DOOR OPENINGS.
  
 23) NOTE: PLEASE SEE LOCATION OF BATHROOM GFI
 RECEPTACLES WHICH ARE REQUIRED TO BE WITHIN 3FT OF THE
 LAVATORIES EDGE; HOWEVER MAY NOT CROSS OVER ONE
 LAVATORY TO UTILIZE THE RECEPT.
 PLEASE SEE THIS CAN BE CORRECTED BY PLACING AN
 ADDITIONAL GFI ON PLANS OR RELOCATING THE ONE ALREADY
 SHOWN TO BE LOCATED IN BETWEEN THE TWO LAVS.
 210.52D
  
 24) NOTE: PLEASE CLARIFY IF THIS BUILDING IS STILL
 ADJOINED TO THE BUILDING ACROSS THE ALLEY ON THE SOUTH
 SIDE.
 PLEASE SEE THIS MAY AFFECT USE ETC.
  
 25) NOTE: PLEASE INCLUDE ALL FIRE RATINGS FOR EXISTING
 FPL VAULT WALLS.
 PLEASE SEE BUILDING CODE REQUIREMENTS AS WELL AS NEC
 450.
  
 26) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM SIZE OF OVER
 CURRENT PROTECTION OF TRANSFORMER UNLESS MEETING NOTE
 #3 IS 125%.
  
 27) NOTE: PLEASE SEE GROUNDING ELECTRODE RISER AND
 NOTES AS THIS STATES FOOTER STEEL TO BE PART OF THE
 GROUNDING ELECTRODE SYSTEM. PLEASE KNOW AS THIS IS AN
 EXISTING BUILDING AND NOT NEW, THE EXISTING FOOTER (IF
 THEY CONTAINED STEEL) ARE NOT REQUIRED TO HAVE THE
 ATTACHMENT MADE AS THE CUTTING/CHIPPING INTO AN
 EXISTING FOOTER OF THIS AGE WOULD AFFECT THE STRUCTURAL
 INTEGRITY OF THE FOOTER. PLEASE KNOW THAT THIS IS
 PERMITTED HOWEVER NOT REQUIRED. IF SHOWN ON RISER THEN
 THIS WILL BE REQUIRED. PLEASE KNOW THAT ANY STRUCTURAL
 BUILDING STEEL WOULD BE REQUIRED.
 PLEASE SEE 250.50
  
 28) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM
 DOES NOT SEEM TO INCLUDE ANY CONNECTION TO THE FIRE
 SPRINKLER PIPE(S) AS REQUIRED. 250.50, 250.104 EXISTING
 OR NEW?
  
 29) NOTE: PLEASE CLARIFY THE DUPLEX WHICH IS A
 HALF/SWITCHED RECEPTACLE FOR THE DISPOSAL SHOWN ON
 PLANS. PLEASE KNOW THAT IF THIS DEVICE IS NOT GOING TO
 FEED BOTH THE DISHWASHER AND DISPOSAL AS TYPICALLY
 DONE, THEN THIS WOULD BE REQUIRED TO BE A SINGLE
 RECEPTACLE DEVICE NOT A DUPLEX.
 PLEASE KNOW THAT IF INDEED THIS DUPLEX IS GOING TO FEED
 BOTH THE DISPOSAL AND DISHWASHER THEN A 2-POLE CIRCUIT
 BREAKER IS REQUIRED AND CORRECTION OF PANEL SCHEDULE
 WILL NEED TO BE MADE.
 PLEASE SEE 210.3, 210.4, 210.7, 210.21, 210.23 ETC.
  
 30) NOTE: PLEASE SEE LOAD CALCULATIONS FOR UNITS ARE TO
 BE DONE PER NEC 220.82/220.84. PLEASE SEE THAT AS THIS
 IS NOT AN EXISTING UNIT, HOW IS THE FIRST 8KVA BEING
 INDICATED AT 100%? PLEASE SEE THIS WOULD BE THE FIRST
 10KAV FOR NEW CONSTRUCTION.
  
 31) NOTE: PLEASE CLARIFY ALL TRANSFORMERS BEING SHOWN
 ON SITE PLANS. ARE THESE ALL FEEDING THIS BUILDING?
  
 32) NOTE: PLEASE SEE RISER AS SHOWN DOES NOT INCLUDE
 ANY METERING DEVICES FOR THE ELECTRICAL FEEDING
 COMMERCIAL SPACES EITHER BY WAY OF CT OR METER CAN?
 PLEASE SEE FPL SERVICE GUIDELINES AS THIS IS REQUIRED
 TO BE INDICATED ON ELECTRICAL PLANS AT THIS TIME.
 PLEASE
  
 33) NOTE: PLEASE PROVIDE COMPLETE INFORMATION FOR FIRE
 PUMP, FIRE PUMP CONTROLLER AND ALL ASSOCIATE
 EQUIPMENT.
 PLEASE SEE THE FIRE PUMP RISER AS SHOWN AND HOW
 EQUIPMENT IS BEING FED FROM THE HOUSE SERVICE IS NOT
 PERMITTED. PLEASE SEE RISER ALSO SHOWS THIS BEING FED
 FROM OTHER SEPARATE SERVICE ALSO.
 PLEASE SEE 2005NEC 695 AND 2003 NFPA-20 (ALL).
 PLEASE INDICATE IF THESE ARE NEW TO BE INSTALLED OR
 EXISTING WHICH MEETS CURRENT CODES.
 PLEASE SEE THE LOCATIONS OF THE FIRE PUMP ETC NEEDS TO
 BE LOCATED PER CODES GIVEN AS NOTED.
 ** AS SHOWN CODE COMPLIANCE IS NOT ACHIEVED.
  
 34) NOTE: PLEASE SEE 240.24, 110.26 AND 408.17 FOR
 LOCATIONS OF OVER CURRENT PROTECTION IN STORAGE AREAS.
  
 PLEASE SEE AIR HANDLER UNITS WHICH IS BEING SHOWN IN
 STORAGE CLOSETS WHICH IS NOT PERMITTED.
  
 35) NOTE: PLEASE SEE ONE SET CONTAINING REPEATED
 SHEETS.
 PLEASE SUBMIT TWO COMPLETE SETS OF PLANS. PLEASE KNOW
 BASED ON SCOPE OF WORK, VALUE, CONSTRUCTION, AND THE
 SIZE OF THE EXISTING BUILDING ALONG WITH OTHER
 CONSIDERATIONS, THIS MAY REQUIRE AN ON-SITE INSPECTOR?
 IF THIS IS THE CASE, THEN THREE SETS OF SIGNED, DATED
 AND SEALED PLANS WILL BE REQUIRED.
 109.3.6, 106.1.2, 106.3.5.1.2
  
 36) NOTE: PLEASE SEE 109.3.6.4.4
 PLANS WHICH ARE SIGNED, DATED AND SEALED BY AN
 ARCHITECT OR ENGINEER SHALL CONTAIN A STATEMENT THAT: *
 TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND CHAPTER (FLORIDA
 STATUTES) 633.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES FOR ALL TRADES/TITLE SHEETS FOR EACH TRADE
 AND/OR TITLE BLOCKS.
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-30 08:35:29IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-02-27 Cont ID  
Sent By mawillia Date 2007-02-27 Time 15:19 Rev Time 0.00
Received By mawillia Date 2007-02-27 Time 15:19 Sent To  
Notes
2007-02-27 16:17:27*****DENIED*****
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 03.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT HINDER OR INTERFERE WITH ACCESS TO THE PROPERTY OR
 THE VICINITY THEREOF (INCLUDING FIRE LANES).
  
 04.PLEASE INDICATE IF THE BUILDING OR PORTIONS OF THE
 BUILDING WILL BE OCCUPIED DURING THE PROPOSED SCOPE OF
 WORK.IF SO, THIS WILL BE PERMITTED ONLY WHERE
 REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN PLACE AND MAINTAINED, OR WHERE
 ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE AHJ
 ARE IN PLACE.
  
 05.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 06.PLEASE LIST THE FIRE RATING FOR THE DOORS LEADING
 TO THE STAIR TOWERS (MARKED AS 2).
  
 07.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING.AS PER WEST PALM
 BEACH CODE, THOSE NUMBERS SHALL BE NO LESS THAN 6" IN
 HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 08.PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATIONS FOR THE WALLS AND CEILINGS FOR THE
 EXITS, EXIT ACCESS CORRIDORS, AND OTHER SPACES.
  
 09.PROVIDE A LIFE SAFETY PLAN SHEET INDICATING THE
 TRAVEL DISTANCE TO THE EXITS.THE LOCATION OF THE
 2A:10BC RATED FIRE EXTINGUISHERS (SATISFYING THE 75
 FEET TRAVEL DISTANCE) AND SMOKE ALARMS MAY ALSO BE
 INCLUDED.
  
 10.IT IS NOTED THAT THIS BUILDING IS SPRINKLERED,
 PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM.
 SHOULD THERE BE A MODIFICATION TO THIS SYSTEM DUE TO
 THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED.
  
 11.IT IS ASSUMED THAT THIS BUILDING HAS A FIRE ALARM
 SYSTEM, PLEASE PROVIDE A LAYOUT OF THE FIRE ALARM
 SYSTEM.SHOULD THERE BE A MODIFICATION TO THIS SYSTEM
 DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED.
  
 12.PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS
 FOR ALL THE GUARDRAILS AND HANDRAILS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLAN) EACH COMMENT
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-18 Cont ID  
Sent By jwitmer Date 2007-01-18 Time 07:48 Rev Time 0.00
Received By jwitmer Date 2007-01-18 Time 08:55 Sent To  
Notes
2007-01-29 08:58:21TO "COMM" BD#17
2007-01-18 08:57:08WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-02-16 Cont ID  
Sent By rregueir Date 2007-02-16 Time 14:31 Rev Time 0.00
Received By rregueir Date 2007-02-15 Time 09:30 Sent To  
Notes
2007-02-16 14:48:59----------------DENIED-----------------------
  
 1. AHU H IN STORAGE ROOM,PG M8.1.3 SHOWS SUPPLY AND
 RETURN PENETRATING A ONE HOUR RATED WALL INTO A MEANS
 OF EGRESS CORRIDOR. PLEASE SHOW HOW THESE OPENINGS WILL
 BE PROTECTED PER FBC,M 607
  
 2. RELATED TO COOMENT 1, EQUIPMENTS AND DUCTWORK FOR
 EXIT ENCLOSURE VENTILLATION SHALL COMPLY WITH ONE OF
 THE THREE OPTIONS AS LISTED IN FBC,M 401.4.
  
 3. PLANS INDICATE A WATER HEATER LOCATED IN A/C CLOSET.
 AHU MOUNTING DETAIL DOES NOT SHOW ALLOWANCE FOR A WATER
 HEATER. LOCATION OF WATER HEATER UNDER THAT AHU WILL
 CONFLICT WITH AUXILIARY DRAIN PAN USED FOR OVERFLOW
 PROTECTION. PLEASE CLARIFY SHOWING COMPLIANCE WITH
 FBC,M 307.2.3
  
 4. SUBMIT A HORIZONTAL BUILDING CONDENSATE DRAIN
 ISOMETRIC DIAGRAM SHOWING ALL PIPE SIZES, MATERIAL AND
 INDICATE WHERE THE CONDENSATE TERMINATES. SUBMIT
 VERTICAL RISER DIAGRAMS SHOWING ALL PIPE SIZES,
 MATERIAL, VENTS, ETC PER FBC 106.3.5.1.3(4)(13)
  
 5. AHU DETAIL CALLS FOR PVC PIPE TO RUN TO AUXILIARY
 DRAIN PAN. PVC CAN NOT BE LOCATED IN A PLENUM PER FBC,M
 602.2.1.
  
 6. PRE-ENGINEERED A/C STANDS (FOR ROOFTOP) ARE
 CONSIDERED STRUCTURAL COMPONENTS AS DEFINED UNDER FAC
 9B-72. THEREFORE, PRODUCT APPROVALS MUST BE SUBMITTED
 AT TIME OF APPLICATION.
  
 7. PLEASE PROVIDE OUTDOOR AIR CALCULATIONS SHOWING
 COMPLIANCE WITH THE REQUIREMENTS OF FBC,M CHAPTER 403.
  
 8. FIRE DAMPER DETAIL: FIRE DAMPERS, SMOKE DAMPERS,
 COMBINATION FIRE/SMOKE DAMPERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS PER FBC,M 607.2
  
 9. SHAFTS TERMINATING AT 2ND FLOOR SLAB SHALL HAVE AN
 ENCLOSURE AT THE BOTTOM OF THE SHAFT PER FBC 707.11.
  
 10 PLEASE SUBMIT INFORMATION FROM THE A/C SPLIT SYSTEMS
 MANUFACTURER SHOWING PIPE SIZES FOR LONG-LINE
 APPLICATIONS AS WELL AS ALLOWABLE ELEVATION DIFFERENCES
 BETWEEN SPLIT SYSTEM COMPONENTS.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-02-14 Cont ID  
Sent By kstevens Date 2007-02-14 Time 14:45 Rev Time 0.00
Received By kstevens Date 2007-02-12 Time 18:57 Sent To  
Notes
2007-02-14 16:53:15DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 EXISTING BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A-1.1.1 SUBMIT A DETAIL SHOWING COMPLIANCE FOR
 THE DRINKING FOUNTAIN PER SECTION 11-4.15 AND ALL
 SUBSECTIONS. SHOW COMPLIANCE WITH SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 2. SHTS A-1.1.1 & A-4.2.1 FOR THE COMMON USE/PUBLIC
 TOILET ROOMS SHOW THE FOLLOWING:
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT (SHOWN AS 9")
 C. 11-4.16.5 FLUSH CONTROLS
 D. DISPENSERS
 FOR TOILET STALLS
 A. 11-4.17.3 EXCEPTION NEW CONST(1)(2) INDICATE
 INTERIOR DIMENSIONS OF THE STALLS. (MINIMUM 7'0" WIDTH
 REQUIRED). SECTIONS 11-4.1.3(11) & 11-4.1.6(II). SEE
 FIGURE 30E.
 FOR URINALS
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 FOR LAVS
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 INDICATE THE W/C TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE, AND THE LAV TO BE A MINIMUM
 OF 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE.
 FIGURES 11-28 & 11-32.
  
 3. SHT A-3.1.1 INDICATES A TRASH CHUTE. IF THERE IS
 WATER TO A FIXTURE, THEN THERE SHOULD BE A DRAIN.
 PLEASE INDICATE IF THERE IS A FLOOR DRAIN IN THE TRASH
 ROOM. SECTIONS 301.2 & 301.3.
  
 4. SHTS A4.1.0 & A-4.1.1 KEY NOTE LEGEND #7. IN THE
 DEMOLITION OF ANY DRAINAGE SYSTEM, DEAD ENDS ARE
 PROHIBITED. SECTION 704.5. PLEASE INDICATE ON THE
 PLANS. ALL DEMO'D & CAPPED PIPING SHALL BE INSPECTED
 PRIOR TO COVERING.
  
 5. SHTS A-4.1.2, A-4.1.3, A-4.1.4, A-4.1.5, A-4.1.6 KEY
 NOTE #4. IN THE DEMOLITION OF ANY DRAINAGE SYSTEM, DEAD
 ENDS ARE PROHIBITED. SECTION 704.5. PLEASE INDICATE ON
 THE PLANS. ALL DEMO'D & CAPPED PIPING SHALL BE
 INSPECTED PRIOR TO COVERING.
  
 6. SHT A-4.2.0 PLEASE INDICATE THE OCCUPANCY & USE FOR
 THE BASEMENT. SECTION 302.
  
 7. SHT A-4.2.1 FIRST FLOOR TO BE REVIEWED AS A SHELL
 ONLY. INDICATE THE PREVIOUS OCCUPANCY AND THE EXPECTED
 OCCUPANCY OF THE GROUND FLOOR TO SEE IF CHANGE OF
 OCCUPANCY REQUIREMENTS ARE NEEDED.CHAPTER 812.
  
 8. SHT A-4.2.1 A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1.
  
 9. ALL UNITS INDICATE SPECIFICATION "A" OR "B" FOR THE
 BATHROOMS. PAGES 7.34 & 7.35.
  
 10. SHT A-4.2.2 THRU A-4.2.6 ALL UNITS SHALL COMPLY
 WITH FHA-98 DESIGN MANUAL REQUIREMENTS. PLEASE SHOW THE
 FOLLOWING FOR EACH UNIT:
 A. REINFORCING FOR THE GRAB BARS AT THE TOILET PER
 PAGES 6.3, THRU 6.5.
 B. INDICATE THE SPACING FOR THE W/C'S PER PAGE 6.7.
 C. SHOW THE BACKING FOR THE TUB GRAB BARS PER PAGES 6.8
 & 6.9.
 D. SHOW THE MINIMUM CLEAR FLOOR SPACE AT FIXTURES &
 APPLIANCES FOR THE KITCHEN.
 E. INDICATE THE MINIMUM CLEARANCES BETWEEN COUNTERS
 PER PAGES 7.3 THRU 7.8.
 F. SHOW THE REQUIREMENTS FOR "U" SHAPED KITCHENS PER
 PAGES 7.9 THRU 7.11.
 G. SHOW THE REQUIREMENTS FOR THE LAUNDRY EQUIPMENT PER
 PAGE 7.19.
 H. SHOW THE CLEAR FLOOR SPACE FOR THE W/C'S PER PAGES
 7.43 THRU 7.46.
 I. SHOW THE CLEAR FLOOR SPACE FOR THE LAVS PER PAGES
 7.47 THRU 7.52
 J. SHOW THE CLEAR FLOOR SPACE FOR THE TUBS PER PAGES
 7.53 THRU 7.55.
 K. SHOW THE CLEAR FLOOR SPACE FOR THE SHOWER PER PAGES
 7.56 THRU 7.59.
  
 11. SHT A-5.2.6 TRASH CHUTE PLAN & GENERAL KEY NOTE #16
 INDICATES A FLUSHING HEAD. BACKFLOW PROTECTION IS
 REQUIRED PER SECTION 608.13.5. AN "N-36" TYPE VACUUM
 BREAKER IS REQUIRED AT THE HIGH POINT OF THE SUPPLY
 LINE.
  
 12. SHT P7.1.1 PLEASE INDICATE IF EXISTING PLUMBING
 WILL DISCHARGE FROM THE BUILDING SEPARATELY. IF THE
 EXISTING FIXTURES ARE CONNECTING TO THE SANITARY
 BUILDING DRAIN SHOWN ON THIS SHEET, THEN SHOW THE
 PIPING TO ALL FIXTURES, NEW AND EXISTING. TABLES
 710.1(1) & 710.1(2). SOW ALL PIPE SIZES, TRAPS, VENTS,
 AND DFU'S.
  
 13. SHT P7.1.1 THE FIRST FLOOR SANITARY PLAN INDICATES
 80FU FOR FUTURE RESTURANT. THIS SHALL BE PIPED
 SEPARATELY TO A GREASE INTERCEPTOR, A MINIMUM 750
 GALLON AND WILL BE LOCATED OUTSIDE THE BUILDING. THE
 OUTLET OF THE GREASE INTERCEPTOR SHALL BE CONNECTED TO
 THE SANITARY SEWER. AT THE TIME OF RESTURANT BUILDOUT,
 THE CONTRACTOR SHALL CONTACT ENVIRONMENTAL COMPLIANCE
 FOR THE SIZING OF THE GREASE INTERCEPTOR. WASTE ORD.
 3434. IF SOME OF THE FIXTURE UNITS ARE FOR NON GREASE
 LADEN WASTE, THEN THE SANITARY LINE TO THE RESTAURANT
 CAN ACCEPT THE DISCHARGE FROM THOSE FIXTURES.
  
 14. SHT P7.1.4 FIRST FLOOR WATER PLAN SHALL INDICATE
 WHERE EXISTING RESTROOM FIXTURES CONNECT TO THE WATER
 MAIN. SHOW ALL WATER PIPING ON THE FLOOR PLAN AND THE
 WATER RISER ISOMETRIC. INDICATE THE LOCATION OF THE
 REQUIRED RPZV BACKFLOW. BACKFLOW SHALL BE AT LEAST THE
 SAME SIZE AS THE WATER LINE IN WHICH THEY ARE
 INSTALLED.SECTION 106.3.5.1.3(3)(8)(10)(13) & TABLE
 603.1(D).
  
 15. SHT P7.2.1 SANITARY ISOMETRIC FIRST FLOOR. RECHECK
 THE DFU'S & PIPE SIZING PER TABLES 710.1(1) &
 710.1(2).
  
 16. SHT P7.2.1 ELECTRIC W/HEATER DETAIL. THERMAL
 EXPANSION CONTROL IS REQUIRED PER SECTION 607.3.2.
 PLEASE INDICATE METHOD.
  
 17. SHT P7.2.2 PLEASE RECHECK THE DFU'S FOR STACK
 RISERS A,L,M,N,O,T,V,Q,Z & AB. PER TABLE 709.1 A
 BATHROOM GROUP IS 5FU. THIS INCLUDES A WATER CLOSET,
 TUB OR SHOWER, BIDET & 1 LAV. ADDITIONAL LAVS ARE 1FU
 WHERE APPLICABLE. MOST BATHROOMS ARE 5FU AND THE
 BATHROOMS WITH AN EXTRA LAV ARE 6FU. IF THE EXISTING
 FIXTURES ARE CONNECTING TO THE BUILDING SANITARY DRAIN
 ON THIS SHEET, PLEASE SHOW ALL PIPES FOR THE EXISTING
 FIXTURES CONNECTING TO THE BUILDING DRAIN AND ADD BTU'S
 TO SYSTEM. SECTION 106.1.1 & TABLES 710.1(1) 710.1(2).
  
 18. SHT P7.2.2 NO "Y" SANITARY RISER DIAGRAM HAS BEEN
 SUBMITTED. THIS RISER IS INDICATED ON THE FLOOR PLAN
 AND THE BUILDING SANITARY DRAIN ISOMETRIC. PLEASE
 SUBMIT A "Y" RISER SHOWING ALL PIPE SIZES, TRAPS, VENTS
 ETC. SECTION 106.3.5.1.3(4)(6)(13).
  
 19. SUBMIT AN EMERGENCY PAN DRAIN BUILDING DRAIN LINE
 ISOMETRIC FOR THE WATER HEATERS. SHOW ALL PIPE SIZES, &
 INDICATE THE TERMINATION POINT OF THE DRAIN LINE.
 SUBMIT RISER DIAGRAM ISOMETRICS FOR THE PAN DRAIN
 LINES. SECTION 106.3.5.1.3(13).
  
 20. SHT P7.2.3 WATER ISOMETRIC FOR THE 2ND THRU 6TH
 FLOORS UNITS 03 & 04. FULL OPEN VALVES ARE REQUIRED ON
 THE TOP OF ALL WATER DOWN-FEED LINES. SECTION
 606.1(4).
  
  
 21. SHT P7.2.3 WATER ISOMETRIC FOR THE 1ST FLOOR.
 INDICATE ALL FIXTURES, INCLUDING THE EXISTING ON THE
 WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, VALVES, AND
 WATER HAMMER ARRESTORS, (AS REQUIRED BY SECTION 604.9).
 SHOW ALL THE FIXTURES CONNECTING TO THE WATER MAIN AT
 THAT FLOOR LEVEL. SECTION 106.1.1.
  
 22. ALL PLUMBING, ELECTRICAL & MECHANICAL SHEETS. THE
 ADDRESS FOR THE PROFESSIONAL ENGINEERING BUSINESS ON
 THE TITLE BLOCKS DOES NOT REFLECT THE ADDRESS OF RECORD
 FROM THE DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE
 INDICATE CORRECT ADDRESS OR HAVE THE DBPR WEBSITE
 UPDATED WITH THE CORRECT ADDRESS. FAC 61G15-23.002(2) &
 FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-02-12 Cont ID  
Sent By astelly Date 2007-02-12 Time 10:55 Rev Time 0.00
Received By astelly Date 2007-02-12 Time 10:55 Sent To  
Notes
***NONE***