Plan Review Details - Permit 07010761
Plan Review Stops For Permit 07010761
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-02-21 Cont ID  
Sent By jgomez Date 2007-02-21 Time 12:22 Rev Time 0.50
Received By jgomez Date 2007-02-21 Time 12:08 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-02-16 Cont ID  
Sent By jgomez Date 2007-02-16 Time 17:28 Rev Time 0.50
Received By jgomez Date 2007-02-16 Time 17:27 Sent To  
Notes
2007-02-16 17:52:44BUILDING REVIEW 4TH CHECKLIST:
  
 1- ENGINEER CALCULATIONS:
 A) ENGINEER REVISED LETTER STATES THAT"NAIL
 SPACING OF 9"O.C. INACCORDANCE WITH THE NOA WORKS
 EXCEPT IN THE CORNER WHERE THE SPACING NEEDS TO BE
 REDUCED TO 5"O.C.".CALCULATED DESIGN PRESSUREAT
 PERIMETER AREAIS-59.2PSF.ACCORDING TO PAGE 17 OF
 NOA 02-0212.07 SUBMITTED THE MAXIMUM DESIGN PRESSURE
 USING 11GA RING SHANK NAILS IS -52.5. THEREFORE,ALSO
 NEEDSNAIL ENHANCING AS ALLOWED BY GENERAL LIMITATION
 #7.REVISE AS REQUIRED.
  
 B) ENGINEER TO REVISEBASE SHEET FASTENER SPACING
 CALCULATIONS ON LAST PAGE OF CALCULATIONS SUBMITTED.
 ACCORDING TO RAS 117 CALCULATIONS SEC. 8.1 THE MAXIMUM
 DESIGN PRESSURES FOR THE ACCEPTED ASSEMBLY ARE THE ONES
 APPLICABLE TO THE ROOF AREA (1).REVISE FASTENER
 SPACING FOR ZONE 1 AS REQUIRED.
  
 C) ENGINEER TO SEE ATTACHED COPY OF FLORIDA STATUTE
 REGARDING DESIGN PROFESSIONAL DOCUMENTS AND PLAN REVIEW
 FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-02-12 Cont ID  
Sent By jgomez Date 2007-02-12 Time 17:46 Rev Time 1.00
Received By jgomez Date 2007-02-12 Time 17:46 Sent To  
Notes
2007-02-12 18:06:42BUILDING REVIEW THIRD CHECKLIST:
 1- ENGINEERING CALCULATIONS SUBMITTED:
 A) FASTENER SPACING CALCULATIONS ARE WRONG. ENGINEER
 USED ANCHOR SPACING RN AND RS IN THE EQUATION ON LAST
 PAGE OF CALCULATIONS SUBMITTED.RAS 117 GENERAL
 EQUATION10.4.5 CALLS FOR ROW SPACING, NOT ANCHOR
 SPACING.NEED TO REVISE CALCULATIONS AS REQUIRED.
  
 B) ENGINEER USED 20SF AS THE TRIBUTARY AREA FOR THE
 DESIGN PRESSURES CALCULATIONS. NEED TO USE AT LEAT THE
 10SF TRIBUTARY AREA . THE EFFECTIVE WIND AREA SHALL NOT
 BE GREATERTHAN THE AREA THAT IS TRIBUTARY TO AN
 INDIVIDUAL FASTENER. SEE EFFECTIVE WIND AREA DEFINITION
 IN CHAPTER 16 FBC 2004.
  
 C) ENGINEER TO REVISE ALL FBC TABLES REFERENCED IN
 THE CALCULATIONS. NEED TO SEE REVISED FBC PAGES (BLUE
 PAGES) AND REVISE TABLES AS REQUIRED.
  
 D) ONLY THE DESIGN PRESSURES FOR ROOF ARE REQUIRED.
 THE REST OF THE DESIGN PRESSURES ARE NOT REQUIRED FOR A
 ROOF PERMIT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-30 Cont ID  
Sent By jgomez Date 2007-01-30 Time 18:29 Rev Time 1.00
Received By jgomez Date 2007-01-30 Time 17:45 Sent To  
Notes
2007-01-30 18:58:10BUILDING REVIEW SECOND CHECKLIST:
 1- ENGINEERING CALCULATIONS:
 A) ENGINEER TO READ GENERAL LIMITATION #7 ON PAGE 20
 OF 20 OF NOA 02-0212.07 AND PROVIDE THE REQUIRED RAS
 117 CALCULATIONS. INFORMATION SUBMITTED ARE NOT THE RAS
 117 CALCULATIONS.
  
 B) CALCULATED DESIGN PRESSURES ARE TOO LOW COMPARE
 TO TABLE 1609.6.2.1(2) OF 2004 FBC.ENGINEER TO
 PROVIDE ACTUAL CALCULATIONS SHOWING CALCULATED DESIGN
 PRESSURES. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: ENGINEER TO CHECK ROOF PLAN.THIS HOUSE HAS
 PITCH ROOF AND FLAT ROOF SYSTEMS, THEREFORE DESIGN
 PRESSURES ARE DIFFERENT FOR EACH ROOF TYPE.ALSO,
 CORRECT FLAT ROOF AREA NEED TO BE CONSIDER FOR DESIGN
 PRESSURES CALCULATIONS.
  
 C) ENGINEER TO IDENTIFY SPECIFIC APPROVED FLAT ROOF
 ASSEMBLY AND SPECIFIC FASTENING OPTIONS FOR WHICH HE IS
 PROVIDING ENHANCED FASTENING CALCULATIONS.SEE NOA
 SUBMITTED. COORDINATE WITH CONTRACTOR FOR SPECIFIC NAIL
 TYPE TO BE USED.
  
 D) ENGINEER TO PROVIDE ENGINEERING FIRM'S
 CERTIFICATE OF AUTHORIZATION AS REQUIRED BY FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15--23.001.
  
 E) CITY OF WEST PALM BEACH ADDRESS IS INCORRECT.
 REVISE AS REQUIRED.
  
 2-CORRECT NOA FOR ROOF TILE WAS REQUESTED ON PREVIOUS
 CHECKLIST.SUCH NOA WAS NOT PROVIDED.THE ONLY
 INFORMATION SUBMITTED WAS A COPY OF FLORIDA PRODUCT
 APPROVAL FL282-R1.THIS PRODUCT APPROVAL IS FOR
 ANOTHER TILE MANUFACTURER AND THERE WAS NO NOA
 SUBMITTED WITH IT. PROVIDE 2 COPIES OF COMPLETE AND
 CORRECT INFORMATION.
  
 3- ROOF TILE FASTENING WAS NOT PROVIDED AS REQUESTED ON
 PREVIOUS CHECKLIST.IF USING POLYFOAM, THEN PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9B-72.IS
 USING SCREWS OR NAILS CLEARLY IDENTIFY WHICH TYPE AND
 NUMBER TO VERIFY COMPLIANCE WITH THE PRODUCT APPROVAL
 AND DESIGN PRESSURES.
  
 4- NOTICE OF COMMENCEMENTSUBMITTEDEXPIRED ON
 12/24/2006. NEED TO PROVIDE NEW NOTICE OF COMMENCEMENT
 AS REQUIRED BY SEC. 713.13 FLORIDA STATUTES.
  
 5- PERMIT APPLICATION HAS THE GENERAL CONTRACTOR AS THE
 OWNER.GENERAL CONTRACTOR IS NOT THE OWNER.THESE ARE
 PUBLIC RECORDS AND THEY NEED TO HAVE CORRECT OWNER'S
 INFORMATION.PLEASE PROVIDE NEW PERMIT APPLICATION
 WITH CORRECT INFORMATION
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-12 Cont ID  
Sent By jgomez Date 2007-01-12 Time 16:38 Rev Time 0.75
Received By jgomez Date 2007-01-12 Time 16:38 Sent To  
Notes
2007-01-12 16:45:55BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTES.
  
 2- FLAT ROOF SYSTEM;
 A) SPECIFY BASE SHEET FASTENING OPTION AS REQUIRED
 BY CITY POLICY FOR ROOFING PERMITS. SEE ATTACHED COPY.
  
 B) GENERAL LIMITATION #7 CALLS FOR RAS 117
 CALCULATIONS TO BE SIGNED AND SEALED BY ARCHITECT,
 ENGINEER OR REGISTERED ROOFING CONSULTANT. PROVIDE SUCH
 INFORMATION. SEE GENERAL LIMITATION #7 ON PAGE 20 OF
 NOA #02-0212.07.
  
 3- ROOF TILE;
 A) PROVIDE CORRECT NOA THAT CORRESPONDS TO FLORIDA
 PRODUCT APPROVAL 3506. NEED NOA #02-0916.11. GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING NOA.
  
 B) SPECIFY HOW IS ROOF TILE GOING TO BE FASTENED. IF
 NAILS OR SCREWS, THEN SPECIFY NUMBER. IF USING
 POLYFOAM, THEN PROVIDE CORRESPONDING PRODUCT APPROVAL
 AS REQUIRED BY DCA RULE 9B-72.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712