Plan Review Details - Permit 07010753
Plan Review Stops For Permit 07010753
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-02-01 Cont ID  
Sent By jgomez Date 2007-02-01 Time 12:54 Rev Time 0.75
Received By jgomez Date 2007-02-01 Time 12:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-11 Cont ID  
Sent By jgomez Date 2007-01-11 Time 13:45 Rev Time 0.75
Received By jgomez Date 2007-01-11 Time 12:37 Sent To  
Notes
2007-01-11 13:58:26BUILDING REVIEW CHECKLIST:
 1- RAS 117 CALCULATIONS FOR FLAT ROOF SYSTEM:
 A) ENGINEER'S CALCULATIONS REFER TO NOA 03-0501.02
 ASSEMBLY ON PAGE 28. NOA 03-0501.02 SUBMITTED SHOWS
 PAGE 26 AS THE SELECTED ASSEMBLY. ASSEMBLY ON PAGE 28
 IS DIFFERENT THAN ASSEMBLY ON PAGE 26. PROVIDE MATCHING
 INFORMATION.
  
 B)FROM NOA 03-0501.02 ENGINEER TO CLEARLY IDENTIFY
 BASE SHEET FASTENING OPTION AND CORRECT DESIGN
 PRESSURES. SPECIFY FASTENING TYPE AND CORRECT DESIGN
 PRESSURES THAT MATCHSELECTED FASTENING OPTION. ONE
 SUBMITTED DOESN'T MATCH.
  
 C)ENGINEER TO CLARIFY HOW CAN A 4" OVERLAP HAVE
 TWO ROWS OF NAILS IF THE MINIMUM FASTENER SEPARATION
 SHALL NOT BE LEES THAN 4"O.C.. SEE SEC. 8.1 OF RAS 117.
 ALSO, PROVIDE MANUFACTURER'S APPROVAL OF PROPOSED
 INSTALLATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 D) ENGINEER IS USING THE CALCULATIONS FOR INSULATION
 ATTACHMENT. THIS IS A NON-INSULATED SYSTEM. NEED TO USE
 CORRECT EQUATIONS. SEE SEC. 10 OF RAS 117.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 10:31 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 10:30 Sent To B
Notes
2007-02-01 10:31:16TO "JGOMEZ" DESK/RESUB


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved