Plan Review Details - Permit 07010734
Plan Review Stops For Permit 07010734
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-05-11 Cont ID  
Sent By mjacobs Date 2007-05-11 Time 13:48 Rev Time 0.00
Received By mjacobs Date 2007-05-11 Time 11:47 Sent To  
Notes
2007-05-11 14:32:045/11/07 GAVE PLANS TO 'LM'MJ

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-02-26 Cont ID  
Sent By mjacobs Date 2007-02-26 Time 12:40 Rev Time 0.00
Received By mjacobs Date 2007-02-26 Time 09:34 Sent To E
Notes
2007-02-26 10:55:13BUILDING PLAN REVIEW
 PERMIT: 07010734
 ADD:229 SANTA LUCIA DR.
 CONT: TREND WEST, INC.
 TEL: (561)547-2944
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE A WALL SECTION FRAMING DETAIL OF THE NEW
 2X6 WALL. SHOW THE ELEVATION DRAWINGS WITH THE FRAMING
 DETAILS FOR THE DOOR AND WINDOWS OPENINGS. ALSO SHOW
 THE CONNECTION OF THE TOP AND BOTTOM PLATES.
  
 3)WPB AMENDMENTS 108.3*IF IN THE OPINION OF THE
 BUILDING OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, ARCHITECTURAL AND DESIGN FEES.OUR
 VALUATION REFERENCE IS ICC (BVD), MARSHALL-SWIFT AND
 MEANS COST ANALYSIS SERVICES.
  
 4)R602.2.3 WOOD STUD WALLS SHALL BE CAPPED WITH A
 DOUBLE TOP PLATE INSTALLED TO PROVIDE OVERLAPPING AT
 CORNERS AND INTERSECTIONS WITH BEARING PARTITIONS.
 PLATES SHALL BE A NOMINAL 2 INCHES IN DEPTH AND HAVE
 WIDTH AR LEAST EQUAL TO THE WIDTH OF THE STUDS.
  
 5)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-23 Cont ID  
Sent By btrobaug Date 2007-07-23 Time 13:00 Rev Time 0.00
Received By btrobaug Date 2007-07-23 Time 12:20 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-02-27 Cont ID  
Sent By btrobaug Date 2007-02-27 Time 11:00 Rev Time 0.50
Received By btrobaug Date 2007-02-27 Time 10:31 Sent To P
Notes
2007-02-27 11:04:12 
  
  
 PROVISO
 BATHROOM BRANCH CIRCUITS IN ADDITION TO THE NUMBER OF
 BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. 210.11(C)(3).
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 11:59 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 11:59 Sent To E
Notes
2007-07-18 12:00:14TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 10:55 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 10:55 Sent To P
Notes
2007-05-18 10:55:27TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-24 Cont ID  
Sent By adarroug Date 2007-04-24 Time 14:02 Rev Time 0.00
Received By adarroug Date 2007-04-24 Time 14:02 Sent To P
Notes
2007-04-24 14:02:34TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-09 Cont ID  
Sent By tgordon Date 2007-03-09 Time 13:49 Rev Time 0.00
Received By tgordon Date 2007-01-17 Time 09:10 Sent To  
Notes
2007-01-17 09:12:35TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-03-09 Cont ID  
Sent By tgordon Date 2007-03-09 Time 13:46 Rev Time 0.20
Received By tgordon Date 2007-03-09 Time 13:46 Sent To  
Notes
2007-03-09 13:49:03NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-05-25 Cont ID  
Sent By mperson Date 2007-05-25 Time 14:27 Rev Time 0.45
Received By mperson Date 2007-05-25 Time 14:27 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-05-15 Cont ID  
Sent By mperson Date 2007-05-15 Time 11:12 Rev Time 0.45
Received By mperson Date 2007-05-15 Time 11:12 Sent To PC
Notes
2007-05-15 11:32:17DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **NO** SHEET P.1: THE WASHING MACHINE MUST
 DISCHARGE DOWNSTREAM OF THE WET-VENTED BATHROOM GROUP
 PER FBC-2004 PLUMBING, SECTION 909.1.
  
 3. **OK**
  
 THE FOLLOWING ARE NEW CORRECTIONS REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 4. SHEET P.1 THE FOLLOWING CORRECTION IS REQUIRED FOR
 THE WASHING MACHINE.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER.
 NOTE: PLEASE INDICATE THE TRAP FOR THE WASHING MACHINE
 ON THE RESUBMITTAL.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 NOTE: PLEASE INDICATE THE STANDPIPE FOR THE WASHING
 MACHINE ON THE RESUBMITTAL.
  
 5. SHEET P.1 PLEASE INDICATE THE REQUIRED TRAPS FOR
 THE FOLLOWING FIXTURES PER FBC-2004 PLUMBING, SECTION
 1002.1.
 A} SHOWER
 B} TUB
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-07 Cont ID  
Sent By jleech Date 2007-03-07 Time 14:31 Rev Time 0.00
Received By jleech Date 2007-03-07 Time 14:31 Sent To M
Notes
2007-03-07 14:57:06DENIED;
 1. AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE 3"
 FBC-2004 PLUMBING SECTION 406.3. A CLEANOUT IS REQUIRED
 AT 48" AFF.
 2. THE W/M MUST DISCHARGE DOWN STREAM OF THE BATHROOM
 GROUP. SECTION 909.1. AND VENT REQUIRED.
 3. THE WET VENT FOR THE BATHROOM IS REQUIRED TO BE 3"
 SEE SIZING TABLE 909.3 AND TABLE 709.1 TO SIZE FIXTURES
 THE FIXTURE UNITS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695