Plan Review Details - Permit 07010690
Plan Review Stops For Permit 07010690 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2007-03-27 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-03-27 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-03-27 |
Time |
15:08 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2007-02-21 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-02-21 |
Time |
17:54 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2007-02-21 |
Time |
17:39 |
Sent To |
|
|
Notes |
2007-02-21 18:07:38 | BUILDING REVIEW FOURTH CHECKLIST: | | 1- GENERAL LIMITATION #7 ON FLAT ROOF SYSTEM NOA | | 06-0410.06 SUBMITTED REQUIRESRAS 117 NAIL ENHANCING | | CALCULATIONS FOR PERIMETER AND CORNER AREAS TO BE DONE | | AND SIGNED,SEALED BY AN ARCHITECT, ENGINEER OR | | REGISTERED ROOF CONSULTANT. PROVIDE SUCH CALCULATIONS | | AS REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF | | NOA SUBMITTED. | | | | 2-A)IF SUBMITTING CALCULATIONS DONE BY ROBERT | | NIEMINEN, PE, THEN THEY NEED TO HAVE ORIGINAL SEAL AND | | SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES | | AND SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. | | | | B) PROPOSED SPACING FOR NAIL ENHANCING AT PERIMETER | | AREA(PAGE 2 OF 2) DOESN'T MEET REQUIRED SPACING. | | PROVIDE ACTUAL RAS 117 CALCULATIONS TO SHOW SPACING. | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. | | | | C) IF USING SUBMITTED ENGINEER'S REPORT, THEN COMPLY | | WITH LIMITATIONS OF USE #D AND CONCLUSIONS.NEED | | WITHDRAWAL TESTING FOR BASE SHEET FASTENERS AND | | QUALIFIED PROFESSIONAL TO DETERMINE BUILDING EXPOSURE | | CATEGORY AND ENCLOSURE CONDITIONS (SEE PAGE 3 OF 3). | | | | 3- INFORMATION SHOWN ON HIGH VELOCITY HURRICANE ZONE | | PERMIT APPLICATION DOESN'T MATCH ENGINEER REPORT | | SUBMITTED.SEE DESIGN PRESSURES AND LAPWIDTH.ON | | THE OTHER HAND, THIS FORMIS NOT REQUIRED IN THIS | | MUNICIPALITY. | | | | | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-01-29 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-01-29 |
Time |
07:57 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2007-01-29 |
Time |
07:39 |
Sent To |
|
|
Notes |
2007-01-29 08:09:31 | BUILDING REVIEW THIRD CHECKLIST: | | 1- PRODUCT APPROVAL NOA #03-0130.08 EXPIRED ON | | 09/13/06. PROVIDE CURRENT NOA. | | | | 2- SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE | | INSTALLED AS REQUIRED BY CITY POLICY FOR ROOFING | | PERMITS. SEE ATTACHED COPY OF CITY POLICY. | | | | 3- IF SELECTED ASSEMBLY HAS MORE THAN ONE BASE SHEET | | FASTENING OPTIONS, THEN SPECIFY WHICH OPTION IS GOING | | TO BE USED. SEE CITY POLICY FOR ROOFING PERMITS. | | | | 4- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | LIMITATION #7, THEN PROVIDE RASS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS. | | CALCULATIONS SHALL BE SIGNED AND SEALED BY ARCHITECT, | | ENGINEER OR REGISTERED ROOFING CONSULTANT. SEE GENERAL | | LIMITATION #7 ON PAGE 45 OF 45 OF NOA SUBMITTED. | | | | 5- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | LIMITATION #9, THEN IT CAN'T BE USED IN THIS AREA | | BECAUSE ASSEMBLY CAN'T BE ENHANCED TO INCREASE THE | | DESIGN PRESSURES. SEE GENERAL LIMITATION #9 ON PAGE 45 | | OF 45 OF NOA SUBMITTED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-01-24 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-01-24 |
Time |
18:48 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2007-01-24 |
Time |
18:48 |
Sent To |
|
|
Notes |
2007-01-24 18:55:26 | BUILDING REVIEWSECOND CHECKLIST: | | | | 1- FLAT ROOF PRODUCT APPROVAL SUBMITTED: | | A) FLORIDA PRODUCT APPROVAL FL1654-R1 IS FOR FLAT | | ROOF SYSTEMS ON CONCRETE DECKS.CLARIFY IF HOUSE HAS | | FLAT CONCRETE DECK AND SPECIFIED TYPE OF DECK. | | | | B) INFORMATION SUBMITTED ALONG WITH FL1654-R1 HAS | | NOTHINGTO DO WITH THIS FLORIDA PRODUCT APPROVAL. THE | | CORRECT REPORT THAT GOES ALONG WITH THE FLORIDA PRODUCT | | APPROVAL IS EVALUATION REPORT 022201.05.04-2. GO TO DCA | | WEBSITE WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRECT | | INFORMATION. | | | | B) ACCORDING TO EVALUATION REPORT 02201.05.04-2, | | WHICH IS THE REPORT THAT CORRESPONDS TO FL 1654-R1, | | NEED TO PROVIDE CALCULATIONS FOR ENHANCED FASTENING AT | | PERIMETER AND CORNER AREAS.SEE LIMITATION # 3(C) ON | | PAGE 3 OF 4.AND, CALCULATIONS NEED TO BE PERFORMED BY | | A QUALIFIED DESIGN PROFESSIONAL. | | | | C) ENHANCED NAILING OF FLAT DECKS LETTER SUBMITTED | | NEED TO BE PERFORMED BY QUALIFIED DESIGN PROFESSIONAL. | | SEE ITEM B ABOVE. ALSO, INFORMATION IS INCOMPLETE AND | | LETTER IS TOO OLD. | | | | | | | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-01-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-01-11 |
Time |
16:30 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2007-01-11 |
Time |
16:30 |
Sent To |
|
|
Notes |
2007-01-11 16:47:21 | BUILDING REVIEW CHECKLIST: | | 1- SEE ATTACHED COPY OF CITY POLICY FOR ROOFING | | PERMITS. NEED THE FOLLOWING: | | A) FLAT ROOF SYSTEM NEED TO PROVIDE TECHNICAL REPORT | | THAT WAS SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL1213. | | VISIT WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL RELEVANT | | INFORMATION.ONLY THE FLORIDA PRODUCT APPROVAL COVER | | PAGES WERE SUBMITTED. SEE ATTACHED COPY OF CITY | | POLICY. | | | | B) PROVIDE FLORIDA PRODUCT APPROVAL FL1213 FOR 2004 | | CODE VERSION. ONE SUBMITTED IS FOR 2001. | | | | C) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING | | TO BE INSTALLED AS REQUIRED BY CITY POLICY. | | | | D) ON SELECTED ASSEMBLY CLEARLY IDENTIFY WHICH BASE | | SHEET FASTENING OPTION IS GOING TO BE INSTALLED. SEE | | CITYPOLICY. | | | | E) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT CORNER AND PERIMETER AREAS. SEE | | GENERAL LIMITATION #7 ON LAST PAGE OF NOA. CALCULATIONS | | NEED TO BE SIGNED AND SEALED BY ARCHITECT, ENGINEER OR | | REGISTERED ROOFING CONSULTANT. | | | | F) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | LIMITATION #9, THEN IT MAY NOT BE USED IN THIS AREA | | BECAUSE OF THE REQUIRED DESIGN PRESSURES. | | | | 2- ROOF SHINGLES. PROVIDE COMPLETE TECHNICAL REPORT. | | ONLY THE FLORIDA PRODUCT APPROVAL FL3663 COVER PAGES | | WERE SUBMITTED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-03-26 |
|
|
Cont ID |
|
Sent By |
mmiller |
Date |
2007-03-26 |
Time |
18:13 |
Rev Time |
0.00 |
Received By |
mmiller |
Date |
2007-03-26 |
Time |
18:13 |
Sent To |
|
|
Notes |
2007-03-26 18:14:23 | SENT TO JULIO GOMEZ'S DESK MMILLER |
|
|
|