Plan Review Details - Permit 07010673
Plan Review Stops For Permit 07010673
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-17 Cont ID  
Sent By rmcdouga Date 2007-04-17 Time 08:03 Rev Time 0.00
Received By rmcdouga Date 2007-04-16 Time 16:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-05 Cont ID  
Sent By rmcdouga Date 2007-04-05 Time 14:24 Rev Time 0.00
Received By rmcdouga Date 2007-04-05 Time 14:24 Sent To  
Notes
2007-04-05 15:39:25DENIED BY BUILDING
  
 1)104.2.1.3 THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPECIFICATIONS. "NO
 WHITE OUT".THE CHANGES THAT WERE MADE ON SHEET G-1 TO
 UPDATE THE EDITION OF ASCE 7 ARE NOT ACCEPTABLE. ANY
 CHANGES TO SEALED DRAWINGS ARE REQUIRED TO BE MADE BY
 THE PERSON THAT SIGNED AND SEALED THOSE DRAWINGS. THE
 ITEM THAT IS CHANGED CAN BE CROSSED OUT BY THE
 ARCHITECT AND CHANGED BUT " WHITE-OUT" CAN NOT BE USED
 OR A NEW CORRECTED SIGNED AND SEALED SHEET CAN BE
 SUBMITTED.
  
 2)THE RESPONSE TO ITEM NUMBER (4) FROM THE PREVIOUS
 REVIEW IS NOT ADEQUATE. 4) PROVIDE A SITE PLAN SHOWING
 COMPLIANCE WITH R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 THE SITE PLAN IS REQUIRED TO SHOW THE FALL IN GRADE
 AWAY FROM THE STRUCTURE AND THE PATH OF THE SURFACE
 WATER TO THE APPROVED COLLECTION POINT. IT IS TO SHOW
 ANY SWALES, DRAINS OR OTHER MEANS USED TO CONTAIN THE
 SURFACE WATER ON THE LOT WITHOUT DIVERTING IT TO THE
 ADJACENT LOTS AND DIRECT IT TO THE APPROVED COLLECTION
 POINT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-05 Cont ID  
Sent By rmcdouga Date 2007-03-05 Time 16:30 Rev Time 0.00
Received By rmcdouga Date 2007-03-05 Time 06:48 Sent To  
Notes
2007-03-02 18:22:50DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)ON SHEET G1 THE NOTE UNDER THE LOAD SCHEDULE
 REFERENCES ASCE7-98. THE CORRECT EDITION IS ASCE7-02.
  
 4) PROVIDE A SITE PLAN SHOWING COMPLIANCE WITH R401.3
 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 5) SHOW COMPLIANCE WITH R309.1 OPENING PROTECTION.
 OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM
 USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED.
 OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL
 BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 1 3 / 8
 INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMB CORE
 STEEL DOORS NOT LESS THAN 1 3 / 8 INCHES (35 MM) THICK,
 OR 20-MINUTE FIRE-RATED DOORS.
  
 6) SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED. THE
 GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND ITS
 ATTIC AREA BY NOT LESS THAN ? -INCH (12.7 MM) GYPSUM
 BOARD APPLIED TO THE GARAGE SIDE. GARAGES BENEATH
 HABITABLE ROOMS SHALL BE SEPARATED FROM ALL HABITABLE
 ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH (15.9 MM) TYPE
 X GYPSUM BOARD OR EQUIVALENT. WHERE THE SEPARATION IS A
 FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE
 SEPARATION SHALL ALSO BE PROTECTED BY NOT LESS THAN
 ?-INCH (12.7 MM) GYPSUM BOARD OR EQUIVALENT.
  
 7) THE TRUSS CONNECTOR SCHEDULE ON S3 SPECIFIES A USP
 RT16 CONNECTOR ATTACHED TO CONCRETE. THE CATALOG LISTS
 THIS AS A WOOD TO WOOD CONNECTOR. SUBMIT A PRODUCT
 APPROVAL OR TECHNICAL BULLETIN FROM THE MANUFACTURER
 WHICH SPECIFIES THIS APPLICATION AND THE REACTION
 RESISTANCE VALUES.
  
 8) DETAIL 7 ON S4 SPECIFIES A SIMPSON HUC48 AND HUC410
 ATTACHED TO MASONRY WITH TAP CONS. SUBMIT A PRODUCT
 APPROVAL OR TECHNICAL BULLETIN FROM THE MANUFACTURER
 WHICH SPECIFIES THIS APPLICATION AND THE REACTION
 RESISTANCE VALUES.
  
 9) THE ROOF FRAMING PLAN ON S2 IS MISSING THE LINES FOR
 THE BEAM B2 AT THE AT THE LIVING ROOM WINDOWS.
  
 10) SUBMIT SPECIFICATIONS FROM THE FIREPLACE AND FLUE
 MANUFACTURER INDICATING THE REQUIREMENTS FOR CHIMNEY
 CAPS. THE SPECIFICATIONS SHOULD SPECIFY THE REQUIRED
 CLEARANCES TO COMBUSTIBLES, OPENING REQUIREMENTS FOR
 PROPER DRAFT ETC.
  
 11) THE PRODUCT APPROVALS FOR THE CLOPAY OVERHEAD
 GARAGE DOORS IS LIMITED TO A MAXIMUM SIZE OF 9' X 8'.
 THE PLANS SPECIFY 9' X 9' GARAGE DOORS.
  
 12) THE PRODUCT APPROVALS FOR THE PGT FIXED WINDOWS IS
 LIMITED TO A MAXIMUM AREA OF 32 SQFT. MOST OF THE FIXED
 WINDOWS SPECIFIED ON THE PLANS EXCEED THIS.
  
 13) INDICATE WHICH ONE OF THE FASTENING OPTIONS LISTED
 IN THE PRODUCT APPROVAL FOR THE ENTEGRA ROOF TILE WILL
 BE USED. CIRCLE THE APPROPRIATE ITEM IN THE PRODUCT
 APPROVAL.
  
 14) SPECIFY THE CEILING COVERINGS FOR THE COVERED PATIO
 AND ENTRY. THE SPECIFICATIONS FOR THE BBQ GRILL STATE
 THAT IT IS NOT TO BE INSTALLED BELOW OVERHEAD
 UNPROTECTED COMBUSTIBLE CONSTRUCTION.
  
 15) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 EXHAUST HOOD AT THE BBQ ON THE COVERED PORCH.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-23 Cont ID  
Sent By btrobaug Date 2007-07-23 Time 08:44 Rev Time 0.00
Received By btrobaug Date 2007-07-23 Time 07:44 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-01-18 Cont ID  
Sent By btrobaug Date 2007-01-18 Time 11:20 Rev Time 1.00
Received By btrobaug Date 2007-01-17 Time 06:43 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-07-17 Cont ID  
Sent By adarroug Date 2007-07-17 Time 16:19 Rev Time 0.00
Received By adarroug Date 2007-07-17 Time 16:19 Sent To E
Notes
2007-07-17 16:19:57TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-07-12 Time 09:07 Rev Time 0.00
Received By adarroug Date 2007-07-12 Time 09:07 Sent To M
Notes
2007-07-12 09:08:17TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 09:57 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 09:57 Sent To B
Notes
2007-04-12 09:57:20TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-09 Cont ID  
Sent By adarroug Date 2007-04-09 Time 15:53 Rev Time 0.00
Received By adarroug Date 2007-04-09 Time 15:53 Sent To Z
Notes
2007-04-09 15:54:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 09:28 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 09:28 Sent To M
Notes
2007-03-22 09:29:21TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-15 Cont ID  
Sent By adavila Date 2007-03-21 Time 16:37 Rev Time 0.00
Received By adarroug Date 2007-03-15 Time 10:58 Sent To Z
Notes
2007-03-15 10:58:56TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-05 Cont ID  
Sent By rmcdouga Date 2007-03-05 Time 16:31 Rev Time 0.00
Received By rmcdouga Date 2007-01-16 Time 08:15 Sent To  
Notes
2007-01-16 08:15:51TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-16 Cont ID  
Sent By tgordon Date 2007-07-16 Time 16:10 Rev Time 0.20
Received By tgordon Date 2007-07-16 Time 16:10 Sent To P
Notes
2007-07-16 16:10:54REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-03-26 Cont ID  
Sent By tgordon Date 2007-03-26 Time 11:36 Rev Time 0.25
Received By tgordon Date 2007-03-26 Time 11:36 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-01-18 Cont ID  
Sent By tgordon Date 2007-01-18 Time 16:29 Rev Time 0.45
Received By tgordon Date 2007-01-18 Time 16:29 Sent To B
Notes
2007-01-18 16:31:36*** DENIED ***
 1) SEE MECHANICAL PLANS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-07-30 Cont ID  
Sent By jleech Date 2007-07-30 Time 09:24 Rev Time 0.00
Received By jleech Date 2007-07-30 Time 09:24 Sent To  
Notes
2007-07-30 09:25:02AS-BUILT RISER DIAGRAM OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-02 Cont ID  
Sent By jleech Date 2007-04-02 Time 08:33 Rev Time 0.00
Received By jleech Date 2007-04-02 Time 08:33 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-18 Cont ID  
Sent By jleech Date 2007-01-18 Time 14:44 Rev Time 0.00
Received By jleech Date 2007-01-18 Time 14:43 Sent To M
Notes
2007-01-18 14:52:50DENIED;
 1.HORIZONTAL DRY VENTS ARE NOT PERMITED. SEC. 905.3
 2.VEGGIE SINK MISSING OR BAR SINK NOT SURE WITH IS NOT
 SHOWN ON PLANS.
 3.PLEASE LIST BATHROOM GROUPS, SEE ONE SET OF PLANS
 MARKED IN RED.
 4. RISER DIAGRAM DOES NOT FOLLOW FLOOR PLAN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2007-04-11 Cont ID  
Sent By adavila Date 2007-04-11 Time 09:54 Rev Time 0.00
Received By adavila Date 2007-04-10 Time 09:54 Sent To I
Notes
2007-04-11 09:55:08PER LINDA MIA FRANCO, SENIOR PLANNER.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-03-21 Cont ID  
Sent By adavila Date 2007-03-21 Time 15:36 Rev Time 0.00
Received By adavila Date 2007-03-21 Time 09:30 Sent To I
Notes
2007-03-21 15:37:58PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.BUILDING HEIGHT SHALL NOT EXCEED 30 FEET ABOVE
 GRADE; THE TOP OF THE CHIMNEY SHALL NOT EXCEED 33 FEET
 ABOVE GRADE.PLEASE PROVIDE BUILDING HEIGHT DIMENSIONS
 FROM GRADE.
  
 2.PLEASE NOTE THAT A SEPARATE PERMIT SHALL BE PULLED
 FOR THE FENCE/GATE/POOL/DECK (REPEAT COMMENT).THESE
 SHALL BE CROSSED OUT FROM THE SITE PLAN.
  
 3.PLEASE NOTE THAT THE SPA IS ENCROACHING IN THE
 REQUIRED REAR SETBACK.PURSUANT TO SECTION
 94-304(B)(7), THE SPA SHALL NOT BE MORE THAN 3 FEET
 ABOVE GRADE.
  
 4.SURVEY IS NOT ABSTRACTED; IT SHALL SHOW ALL
 SETBACKS AND EASEMENTS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR LINDA
 MIA FRANCO, SENIOR PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-01-17 Cont ID  
Sent By mmclean Date 2007-01-17 Time 15:01 Rev Time 0.00
Received By mmclean Date 2007-01-17 Time 10:19 Sent To E
Notes
2007-01-17 15:33:10DENIED,
 1. THE PROPOSED HEIGHT OF THE STRUCTURE HAS EXCEEDED
 THE HEIGHT REQUIREMENT FOR ZONING & LAND DEVELOPMENT.
 CHIMNEY FEATURES MAY EXCEED DISTRICT HEIGHT (30FT)
 REQUIREMENTS BY 10 PERCENT (10%)SEC 94-306(A)
 2. ELEVATION PLANS SHOWS THE STRUCTURE AT 37+FT.
 3. SEPARATE PEMIT SHALL BE PULLED FOR THE
 FENCE/GATE/POOL/DECK/SCREEN ENCLOSURE)
 NOTE: SEC 94-304(2)(B) - EVERY SWIMMING POOL SHALL BE
 ENCLOSED BY A FENCE OR SIMILAR STRUCTURE WHICH IS
 INSTALLED TO OBSTRUCT ACCESS BY PERSONS OTHER THAN THE
 OWNERS OR OCCUPANTS OF THE RESIDENCE WITHIIN WHICH A
 SWIMMING POOL IS LOCATED.BARRIERS OR FENCES SHALL BE
 AT LEAST FOUR FEET IN HEIGHT ABOVE GRADE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720