Plan Review Details - Permit 07010599
Plan Review Stops For Permit 07010599
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-29 Cont ID  
Sent By jwitmer Date 2007-03-29 Time 07:41 Rev Time 0.55
Received By jwitmer Date 2007-03-29 Time 07:41 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-06 Cont ID  
Sent By jwitmer Date 2007-03-06 Time 11:22 Rev Time 0.55
Received By jwitmer Date 2007-03-06 Time 11:22 Sent To  
Notes
2007-03-06 11:24:39PERRMIT: 07010599
 ADD: 2247 PALM BCH LAKES # 208
 CONT: ANDREA CONSTRUCTION
 TEL: (561)358-4797
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE
 POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE
 FIRST INSPECTION.
  
 3) ARCHITECT ROGER MORSE, PLANS HAVE NOT BEEN DATED,
 WHEN SIGNED AND SEALED.
 61G1-16.004 (4) TITLE BLOCK INFORMATION REQUIRED , THE
 DATE THE PLANS ARE SIGNED AND SEALED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-01-22 Cont ID  
Sent By jwitmer Date 2007-01-22 Time 10:01 Rev Time 1.22
Received By jwitmer Date 2007-01-22 Time 10:01 Sent To  
Notes
2007-01-22 10:08:26BUILDING PLAN REVIEW
 PERMIT: 07010599
 ADD:2247 PALM BCH LAKES BLVD SUITE 208
 CONT: ANDREA
 TEL: (561)358-4797
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE; FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE
 POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE
 FIRST INSPECTION.
  
 3) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 2004FBC/ 2006 REVISIONS.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) LEVEL OF ALTERATION: LEVEL 1.2OR 3?
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) NUMBER OF FLOORS
  
 4) SHEET A-101, DOES NOT INDICATE THE SIZE OF THE
 DOORS,
 11-4.13.5 DOORWAYS, MINIMUM
 CLEAR WIDTH: DOORWAY SHALL HAVE A MINI-
 MUM CLEAR OPENING OF 32" WITH THE DOOR
 OPEN 90 DEGREES, MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE OPPOSITE STOP.
  
 5)THE KITCHENETTES SINK LOCATION DOESN'T PROVIDE
 CLEAR FLOOR SPACE;
 SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM)
 UNDERNEATH THE SINK.
  
 6) KICHENETTE DOOR11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 7) OFFICE# 3 IS MISSING THE 18" CLEAR FLOOR SPACE LATCH
 SIDE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-03-20 Cont ID  
Sent By dpalmer Date 2007-03-20 Time 11:05 Rev Time 0.00
Received By dpalmer Date 2007-03-20 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-03-05 Cont ID  
Sent By dpalmer Date 2007-03-05 Time 07:04 Rev Time 0.00
Received By dpalmer Date 2007-03-05 Time 07:04 Sent To  
Notes
2007-03-05 07:05:28*** UNSAT***
  
  
 1)NOTE:PLEASE KNOW TO QUALIFY UNDER "MANAGEMENT"
 MUST HAVE "QUALIFIED PERSONNEL" AS DEFINED ON THE NEC
 ART 100. THIS IS ONLY NOTED AND NO CHNAGES ARE NEEDED
  
 2) NOTE: PLEASE BE SURE TO STATE ALL MAXIMUM TIME FOR
 OC TYPE DEVICES TO BE 30 MINS PER 13-415.1.ABC.1.1.
 PART OF THIS ISSTATED ON PLANS.
  
 3) PLEASE SEE NO ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS, LIGHTING POWER DENSITIES SHOWN OR
 SUBMITTED.
 13-415.1.AB.1.1, 13-415.2
  
 ** PLEASE SEE THE PLANS WILL BE COMING BACK FOR OTHER
 TRADES AS THE ARCHITECT DID NOT DATE PLANS AS REQUIRED
 PER FS481.221
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-01-15 Cont ID  
Sent By dpalmer Date 2007-01-15 Time 08:47 Rev Time 0.00
Received By dpalmer Date 2007-01-15 Time 08:43 Sent To  
Notes
2007-01-15 08:48:39PLANS REMOVED FROM INCOMING FOR REVIEW, ROUTED BACK TO
 INCOMING AWAITING SPACE ON THE BOB BOARD.
2007-01-15 08:48:33** UNSAT **
  
 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON
 PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. THIS IS
 REQUIRED ON ARCH COVER SHEET AS WELL AS ON ELECTRICAL.
 THE ELECTRICAL SHEET DOES CONTAIN SOME OF THESE
 ALREADY, HOWEVER PLEASE SEE MISSING.
  
 PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER
 DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE
 RELEVANT.
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70
 (NEC). (THE 2005 NEC IS SHOWN)
 2002 NFPA-72
 2003 NFPA-101.
  
 2) NOTE: PLEASE SEE THE WATER HEATER SYMBOL WHICH
 INDICATES A 60AMP MOLDED CASE SWITCH WHICH IS OK AS
 30AMP OCP IS SHOWN IN PANEL. PLEASE SUBMIT THE
 MANUFACTURE' SPECS/CUT SHEETS IF THIS IS A
 INSTA-HOT/TANK-LESS WATER HEATER UNIT.MINIMUM
 CLEARANCES SHALL BE PER MANUFACTURE' SPECS.
 PLEASE BE SURE THE LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY IS SHOWN. (NRTL). 110.3,
 90.7
  
 3) NOTE: PLEASE BE SURE TO INDICATE ALL CIRCUITS ON
 PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE.
 PLEASE LABEL ALL LOCATIONS ON PANELS WHICH CORRELATE TO
 ROOMS/AREAS WHICH ARE BEING FED. THIS SHOULD BE MORE
 SPECIFIC. IE; OFFICE 1 RECEPTS,INTAKE RECEPTS,
 CONFERENCE RM ETC.
 THIS CAN BE DONE AT THIS TIME OR IT WILL BE REQUIRED
 BEFORE INSPECTION FOR FINAL.
 106.1.2, 106.3.5.1.2
 NEC 408.4, 310.16, 240.4 FOR VERIFICATION.
  
 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR HORN,
 STROBES AND/OR HORN STROBE DEVICES PER FBC 11-4.28.1,
 .2 AND .3(4).STROBE LEVEL IS NOTED.
 PLEASE SEE ANY OTHER LOCATIONS WHICH MAY BE BROUGHT UP
 BY FIRE MARSHAL' REVIEW.
 THE INSTALLATION OF ANY ADDITIONAL DEVICES TO THE
 EXISTING FIRE ALARM SYSTEM WILL BE REQUIRED UNDER
 SEPARATE PLANS, PERMIT, HOWEVER THESE REQUIRED LEVELS
 ARE TO BE SHOWN ON BASE PLANS.
  
 5) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER
 13-415.1.AB.1, PERFORMANCE CALCULATIONS PER 13-415.2.
 THESE ARE REQUIRED TO BE SIGNED DATED AND SEALED BY THE
 DESIGNER OF RECORD.
 PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES
 TO BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION
 ON PLANS. PLEASE BE SURE TO CORRELATE WITH THE
 PERFORMANCE CALCULATIONS AND ENERGY CALCULATIONS.
 PLEASE SEE THE 2006 REVISIONS TO THE 2004 FBC CHAPTER
 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SUBMIT AUTOMATED LIGHTING CONTROL METHODS,
 SCHEDULING, DEVICES AND TYPES OF DEVICES.
 PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE
 DEVICES. (30 MINS FOR OCCUPANCY TYPE AND 4HRS MAX FOR
 TIMER TYPE. THE TIMES ARE NOTED, HOWEVER ANY NEW
 DEVICES IF TYPICAL THEN WOULD CONTAIN THE SAME
 IDENTIFICATION.
 PLEASE KNOW THAT MOST ARE SHOWN; HOWEVER PLEASE SEE
 MISSING AT ENTRANCE INTO SPACE.
 PLEASE PROVIDE A DETAIL FOR THE CIRCUITING THE
 EMERGENCY AND EXIT LIGHTS. (THERE IS A NOTE ON PLANS,
 HOWEVER SUBMIT DETAIL AS NUMEROUS SITUATIONS IN THE
 JURISDICTION HAS HAD THESE FIXTURES BEING WIRED ON THE
 LOAD SIDE OF THESE DEVICES.
 PLEASE KNOW AS NO INFORMATION WAS SUBMITTED FOR REVIEW,
 A COMPLETE REVIEW FOR COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
  
  
 6) NOTE: PLEASE CLARIFY THE LOCATIONS O THE PANELS AS
 NOTED. PLEASE ALSO CLARIFY WHERE PANEL COVER MENTIONS
 THE COVERS ARE NOT LOCKABLE?
 PLEASE PROVIDE INFORMATION ON PLANS WHETHER BUILDING IS
 UNDER MANAGEMENT OF QUALIFIED PERSONNEL.
 240.24, (A), (B), (C).
  
  
 7) NOTE: PLEASE CLARIFY IN SERVICE CALCULATIONS ARE
 SHOWN AT 125% FOR CONTINUOUS LOADS.
 215.3, 230.42 ETC.
 220.12, 220.14, 220.43, 220.44 ETC.
  
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-03-22 Cont ID  
Sent By mawillia Date 2007-03-22 Time 12:13 Rev Time 0.00
Received By mawillia Date 2007-03-22 Time 11:57 Sent To  
Notes
2007-03-22 12:07:32*****APPROVED*****
  
 ALL PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED;PLAN SHEETS A-102 AND E-101 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  
 PLEASE BE ADVISED THAT AT THE TIME OF FIRE INSPECTION
 FOR BUSINESS TAX SIGNOFF BY WEST PALM BEACH FIRE
 PREVENTION BUREAU, A FIRE EXTINGUISHER SHALL BE
 REQUIRED IN THE TENANT SPACE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-03-13 Cont ID  
Sent By mawillia Date 2007-03-13 Time 13:14 Rev Time 0.00
Received By mawillia Date 2007-03-13 Time 13:13 Sent To  
Notes
2007-03-13 13:14:45*****UNSAT*****
  
 COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE BEEN
 SATISFIED WITH THE EXCEPTION OF THE FOLLOWING WHICH
 STILL NEED TO BE ADDRESSED:
  
  
 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE,
 SHALL BE REFERENCED.ON SHEET A-001 UNDER CODE
 CLASSIFICATION,ADD "NFPA 101 2003 EDITION"
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ON
 SHEET A-001 UNDER CODE CLASSIFICATION, ADD "NFPA 241"
  
 08.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR
 WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS.AS PER NFPA 101: 38.3.3.1 -
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR B IN EXITS AND EXIT ACCESS CORRIDORS AND
 SHALL BE CLASS A, B, OR C IN ALL OTHER AREAS.PLEASE
 SPECIFY
  
 09.INDICATE THE LOCATION OF THE 2A:10BC FIRE
 EXTINGUISHER WHICH SATIFIES THE 75' TRAVEL DISTANCE
 REQUIREMENT.PLEASE BE ADVISED THAT AT THE TIME OF
 FIRE INSPECTION FOR BUSINESS TAX SIGNOFF BY WEST PALM
 BEACH FIRE PREVENTION BUREAU, A FIRE EXTINGUISHER WILL
 BE LOCATED IN THE TENANT SPACE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE (ON THE
 PLAN) EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-01-24 Cont ID  
Sent By mawillia Date 2007-01-24 Time 17:10 Rev Time 0.00
Received By mawillia Date 2007-01-24 Time 17:10 Sent To  
Notes
2007-01-24 17:14:58*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE,
 SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.
  
 4.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INERFERE OR
 HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE.
  
 5.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR
 THIS TENANT SPACE.
  
 6.FIRE ALARM STROBE NEEDED IN THE CONFERENCE ROOM.
  
 7.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM IS
 MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE SHOP
 DRAWINGS/PLANS AND PERMIT WILL BE REQUIRED.
  
 8.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR
 WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND IN ALL OTHER AREAS.
  
 9.INDICATE THE LOCATION OF THE 2A:10BC FIRE
 EXTINGUISHER WHICH SATISFIES THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-20 Cont ID  
Sent By adarroug Date 2007-03-20 Time 09:47 Rev Time 0.00
Received By adarroug Date 2007-03-20 Time 09:47 Sent To  
Notes
2007-03-20 09:49:23TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-02 Cont ID  
Sent By adarroug Date 2007-03-02 Time 09:37 Rev Time 0.00
Received By adarroug Date 2007-03-02 Time 09:37 Sent To  
Notes
2007-03-02 09:37:44TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-01-26 Cont ID  
Sent By jleech Date 2007-01-26 Time 08:24 Rev Time 0.00
Received By jleech Date 2007-01-12 Time 16:22 Sent To  
Notes
2007-01-17 08:56:15TO "BOB"#10
2007-01-12 16:22:35WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-01-17 Cont ID  
Sent By tgordon Date 2007-01-17 Time 11:16 Rev Time 0.25
Received By tgordon Date 2007-01-17 Time 11:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 08:49 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 08:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-01-26 Cont ID  
Sent By jleech Date 2007-01-26 Time 08:25 Rev Time 0.00
Received By jleech Date 2007-01-26 Time 08:25 Sent To  
Notes
2007-01-26 08:30:22DENIED;
 KITCHENETTE SHALL COMPLY WITH FBC-2004 BUILDING CHAPTER
 11 ACCESSIBILITY CODESECTIONS 11-4.24.2 THRU
 11-4.24.7. SHOW DETAIL WITH ALL REQUIRED MESSUREMENTS.
 THE KITCHENETTE DOOR CANNOT SWING INTO THE CLEAR FLOOR
 SPACE OF THE SINK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695